Presentation is loading. Please wait.

Presentation is loading. Please wait.

Air Handling Systems Heating Ventilation and Air Conditioning (HVAC) Part 2: Components Supplementary Training Modules on GMP Module 3, Part 2: Components.

Similar presentations


Presentation on theme: "Air Handling Systems Heating Ventilation and Air Conditioning (HVAC) Part 2: Components Supplementary Training Modules on GMP Module 3, Part 2: Components."— Presentation transcript:

1 Air Handling Systems Heating Ventilation and Air Conditioning (HVAC) Part 2: Components Supplementary Training Modules on GMP Module 3, Part 2: Components Slide 1 of 20 WHO - EDM

2 Module 3, Part 2: Components Slide 2 of 20 WHO - EDM Air Handling Systems Purpose of an air handling system Air Handling System Production Room With Defined Requirements Supply Air Outlet Air

3 Module 3, Part 2: Components Slide 3 of 20 WHO - EDM Air Handling Systems Objectives In the following slides, we will study the components of air handling systems in order to: 1. become familiar with the components 2. know their functions 3. become aware of possible problems

4 Module 3, Part 2: Components Slide 4 of 20 WHO - EDM Air Handling Systems + Production Room Exhaust air treatment Central air handling unit Terminal air treatment at production room level Fresh air treatment (make-up air) Main subsystems

5 Module 3, Part 2: Components Slide 5 of 20 WHO - EDM Air Handling Systems FilterSilencer Terminal filter Weather louvre Control damper Fan Flow rate controller Humidifier Heating coil Cooling coil with droplet separator Production Room Overview components + Prefilter Exhaust Air Grille Heater Secondary Filter Re-circulated air

6 Module 3, Part 2: Components Slide 6 of 20 WHO - EDM Air Handling Systems l Weather louvre l Silencer l Flow rate controller l Control damper To prevent insects, leaves, dirt and rain from entering To reduce noise caused by air circulation Automated adjustment of volume of air (night and day, pressure control) Fixed adjustment of volume of air Components (1)

7 Module 3, Part 2: Components Slide 7 of 20 WHO - EDM Air Handling Systems l Heating unit l Cooling unit /dehumidifier l Humidifier l Filters Ducts To heat the air to the proper temperature To cool the air to the required temperature or to remove moisture from the air To bring the air to the proper humidity, if too low To eliminate particles of pre-determined dimensions and/or micro-organisms To transport the air Components (2)

8 Module 3, Part 2: Components Slide 8 of 20 WHO - EDM Air Handling Systems l Flow rate controller l Control damper l Humidifier l Cooling battery l Filters l Ducts Blocked Poorly adjusted, bad pressure differential system Bad water/steam quality/poor drainage No elimination of condensed water/poor drainage Incorrect retention rate/damaged/badly installed Inappropriate material/internal insulator leaking Problems with components

9 Module 3, Part 2: Components Slide 9 of 20 WHO - EDM Air Handling Systems + Production Room Exhaust air Return air (re-circulated) Fresh air (make-up air) Supply air Air types

10 Module 3, Part 2: Components Slide 10 of 20 WHO - EDM Air Handling Systems Comparing International Cleanroom Classifications

11 Module 3, Part 2: Components Slide 11 of 20 WHO - EDM Air Handling Systems Filter classes Dust filters Standard Aerosol FineCoarseULPAHEPA 10 µ m > Dp > 1 µ m Dp > 10 µ m Dp < 1 µ m F5 - F9G1 - G4U 14- 17H 11 - 13 EN 1822 StandardEN 779 Standard

12 Module 3, Part 2: Components Slide 12 of 20 WHO - EDM Air Handling Systems

13 Module 3, Part 2: Components Slide 13 of 20 WHO - EDM Air Handling Systems Primary panel filter Secondary filter HEPA or tertiaary filter

14 Module 3, Part 2: Components Slide 14 of 20 WHO - EDM Air Handling Systems Humidifier Silencer Heating and cooling units

15 Module 3, Part 2: Components Slide 15 of 20 WHO - EDM Air Handling Systems Control damper for air flow De-humidification Filter Pressure Gauges AHU with fan Variable Speed Controller Humid room air Air heater Regeneration air Humid room air Adsorber wheel Dry air Air handling unit

16 Module 3, Part 2: Components Slide 16 of 20 WHO - EDM Air Handling Systems Swirl Type air diffusors with terminal filters 1 Filter 2 Tightening frame 3 Register outlet 4 Screw fixation for register 1 2 3 4

17 Module 3, Part 2: Components Slide 17 of 20 WHO - EDM Air Handling Systems Low induction swirl diffusor (preferred) High induction office type diffusor (avoid)

18 Module 3, Part 2: Components Slide 18 of 20 WHO - EDM Air Handling Systems Annex 1, 17.26 Regulation of room pressure – pressure differentials concept Room pressure gauges Room pressure indication panel

19 Module 3, Part 2: Components Slide 19 of 20 WHO - EDM Air Handling Systems Pressure cascade injectables P rotection from micro-organisms and particles Annex 1, 17.24, 17.25

20 Module 3, Part 2: Components Slide 20 of 20 WHO - EDM Air Handling Systems Pressure cascade solids Protection from cross-contamination


Download ppt "Air Handling Systems Heating Ventilation and Air Conditioning (HVAC) Part 2: Components Supplementary Training Modules on GMP Module 3, Part 2: Components."

Similar presentations


Ads by Google