1 High Voltage Insulation Diagnostics
WELCOME! Presented by: Bostjan Flis

2 Content overview Application areas of HV insulation testing
What influences insulation resistance Symptoms of bad insulation Testing methods Insulation testing with DC test voltage - insulation characteristics Insulation testing with DC test voltage - test parameters Limit values Connection schemes Test data evaluation i.e. statistics keeping General requirements for HV insulation testers Metrel HV insulation testers Metrel's solution providing, services and development

3 Application areas of HV insulation testing
Insulation resistance testing is part of predictive maintenance of: Rotary machines (generators, motors) Transformers (industry, utilities, power distribution) Cables Measuring transducers Distribution boards Benefits: Lower TCO (total cost of ownership) increased electrical safety prevention against fire hazard

4 What influences insulation resistance
Thermal exposure Overload Moisture Electrical shocks Mechanical shocks (vibrations, bad transportation) Dirt (oil, dust, conductive materials) General ageing of insulation Symptoms of bad insulation Insulation breakdowns in a form of electrical short-circuits Fire Long-term downgrading values of insulation resistance Insulation resistance values under by standards determined values

5 Insulation testing methods
AC insulation testing (50/60Hz, 1 minute) Insulation surge breakdown testing Insulation testing with switching voltage Insulation testing with DC voltage Dielectric losses (tgδ) Partial discharges - U – I characteristics

6 Insulation testing with DC test voltage - insulation characteristics
Riss1 and Riss2 Insulation surface resistance Riso Insulation resistance Ciso Capacitance of an insulation system Rpi Polarisation resistance Cpi Polarisations capacitance Itot Total insulation current IRiss Insulation surface leakage current IRiso Resisitve part of the insulation current IRCpi Polarisation current ICiso Capacitive part of the insulation current

7 Insulation parameters
Polarisation Index (PI) PI = R tot (10 Min) / R tot (1Min) Dielectric absoption ratio (DAR) DAR = R tot (1 Min) / R tot (30 Sek) Dielectric discharge (DD) DD = I DIS (1 min) / (U * C ISO ) I DIS ….a discharge current measured 1 minute after disconnecting the insulation system from the test voltage C ISO …. capacitance of the insulation system U …test voltage

8 Limit values for insulation testing with DC voltage
Insulation resistance Limit value General applications > 1MΩ per 1kV der Nennspannung des Prüflings Rotary machines according to IEEE a./ 1 MΩ + 1 MΩ/1kV b./ 5 MΩ for motors under 600V c./ 100 MΩ for motors above 600V Switching- and control devices according to IEC > 1kΩ for 1V of the UN of the test object Splitting transformers and safety low voltage transformers according to IEC 61558 a./ Basis insulation > 2MΩ b./ Additional insulation > 5MΩ c./ Reinforced insulation > 7MΩ Polarisation index (PI) PI Wert Evaluation 1 to 1.5 BAD (valid for older types of insulation materials) 2 to 4 SUFFICIENT (valid for older types of insulation materials) > 4 VERY GOOD (also for the modern type of insulation materials) Thumb rule (motors and generators): Dielektric absorption ratio (DAR) DAR value Evaluation < 1 BAD 1 ≤ DAR ≤ 1.25 SUFFICIENT > 1.4 VERY GOOD

9 Connection schemes Precondition!
Measuring object has to be disconnected from power supply network (voltage – free) Surface of the insulation system has to be dry and clean Power transformer HV vs LV HV vs G Multiple devices LV vs G

10 Test data evaluation i.e. statistics keeping
- Always assure the same measuring conditions (connection, temperature, test voltage, diagnostics parameters) Regular test intervals (6 months or one year) Results keeping for the entire life period of the equipment Observation of downgrading trends Temperature coefficient (all values are to be calculated on 75ºC)

11 General requirements for HV insulation testers
Test functions: Insulation resistance Step voltage test Capacitance PI, DD, DAR Current in µA and mA range Voltage AC/DC Other features: Guard terminal to eliminate surface insulation currents Automatic discharging of the test object after measurement Built-in timer On-Line graph R = f(t) EM immunity for usage in HV environments EM Filters for improved accuracy Good charging system (accus or mains or both) Accessories: Shielded test leads High quality test terminals (HV, antistatic, high surface resistance) PC Software for downloading of test results and creating test reports

12 Metrel HV insulation testers
Integrated features: Test voltage up to 10kV DC Resistance measuring range up to 10TΩ Automated calculation of PI, DAR and DD for profound insulation diagnostics On-Line R=f(t) display Test voltage setting in 25V steps Shielded 12kV test leads to reduce influence of external EM fields CAT IV/600V over-voltage category for utilities and industrial applications New TeraLink PRO Windows PC Software for TeraOhm 5kV Plus Handbook “Modern insulation testing” on CD

13 Metrel's solution providing, services and development
Product training in Metrel training centre On-Line technical support Application training and publications Repair & Calibration training Calibration equipment Repair & Calibration services Advanced technical solutions for all product‘s segments (Hardware, Firmware, PC Software) Customised solutions (Instruments, Software, Accessories)

14 WHY NOT METREL?

15 You have already made a good decision
THANK YOU! You have already made a good decision