1 Decoupling the Building Latent and Sensible Loads Using 100% Outside Air Systems ASHRAE Chicago Seminar 39 January 24, 2006 Stanley A. Mumma, Ph.D.,

Similar presentations


Presentation on theme: "1 Decoupling the Building Latent and Sensible Loads Using 100% Outside Air Systems ASHRAE Chicago Seminar 39 January 24, 2006 Stanley A. Mumma, Ph.D.,"— Presentation transcript:

1 1 Decoupling the Building Latent and Sensible Loads Using 100% Outside Air Systems ASHRAE Chicago Seminar 39 January 24, 2006 Stanley A. Mumma, Ph.D., P.E. Professor of Architectural Engineering Penn State University, Univ. Park, PA email: sam11@psu.edu http://doas-radiant.psu.edu

2 2 Outline What are 100% OA systems? What is the benefit of decoupling the space sensible and latent loads? What parallel sensible cooling equipment is available when dry ventilation air is delivered to the space? What are the operating benefits of these decoupled systems, including op. cost? A few pitfalls to avoid when applying these systems?

3 3 100% OA Systems 1. 100% OA, but at a low flow rate, approximately the rate required by ASHRAE Std. 62.1-2004: i.e. DOAS. Also needed: Parallel sensible cooling only system to meet the thermal loads. 2. 100% OA, at the flow rate required to meet the entire space sensible load— frequently up to 5 times the flow needed for ventilation alone. Will not be discussed here—but could be during the question time if interested.

4 4 DOAS Systems 20-70% less OA than VAV DOAS Unit W/ Energy Recovery Cool/Dry Supply Parallel Sen. Cooling System High Induction Diffuser Building With Sensible and Latent cooling decoupled

5 5 Why decouple sensible and latent space loads with DOAS? Tight humidity control minimizes the potential for IAQ problems and related sick-building illnesses*, and improves thermal comfort and productivity. *Which are caused largely by biological contaminants breeding in damp ducts, ceiling tiles, insulation, behind vapor barriers and carpet.

6 6 Potential Health/productivity Related Economic benefits of DOAS The significance of DOAS is illustrated by estimates that US companies lose as much as $48 Billion annually to cover medical expenses and $160 Billion annually in lost productivity as a result of sick-building illnesses. Source: ASHRAE Literature.

7 7 Medical & productivity cost (loss) to US business as % of GDP: (208/13,000)*100 = 1.6% National debt annual increase as a % of GDP: (300/13,000)*100 = 2.3% Katrina Gov. appropriations as %of GDP: (150/13,000)*100 = 1.2% How Much is $208 Billion/yr.--- in light of the ~ $13,000 Billion/yr 2006 USA GDP (value of goods and services)

8 8 Fan Coil Units Air Handling Units Unitary ACs Parallel Terminal Systems Radiant Cooling Panels Chilled Beams DOAS air Induction Nozzle Sen Cooling Coil Room air

9 9 Poor air distribution. Poor humidity control. Poor acoustical properties. Poor use of plenum and mechanical shaft space. Serious control problems, particularly with tracking return fan systems. Poor energy transport medium, air. Poor resistance to the threat of biological and chemical terrorism, and Poor and unpredictable ventilation performance. VAV problems solved with DOAS plus Radiant or Chilled Beam

10 10 Additional benefits of DOAS Beside solving problems that have gone unsolved for over 30 years with conventional VAV systems, note the following benefits: Greater than 50% reduction in mechanical system operating cost compared to VAV. Equal or lower first cost. Simpler controls. Generates up to 80% of points needed for basic LEED certification.

11 11 Outdoor air unit with TER OA Space 3, DOAS in parallel w/ CRCP Radiant Panel DOAS with Parallel Radiant

12 12 Sample DOAS pitfalls? Wrong supply air temperature. Wrong controls for the enthalpy wheel. Wrong controls for the heating coil. Wrong controls for the cooling coil. Wrong location for the heating coil.

13 13 Quick Review of DOAS system psychrometrics

14 14 28 140 168 196 112 84 56 Humidity ratio (grains/lb) OA EW RA 1 23 45 PH CC Space 1 2 34,5 wet dry Other regions? Next slide

15 15 28 140 168 196 112 84 56 Humidity ratio (grains/lb) wet dry EW control for various OA conditions EW on when OA h > RA h EW off EW to modulate or duty cycle to hold SAT SP when OA < SAT SP

16 16 28 140 168 196 112 84 56 Humidity ratio (grains/lb) Example of an incorrect EW control logic EW on EW off EW on Cleaning cycle when off! Frost protection when cold outside!

17 17 > 3 ton cooling lost with wheel off Reheat adds 2.8 tons of cooling load, plus the heating energy wasted in the 1,710 cfm OA sys. CC load ~ 10 ton EW off, huge control error when it could significantly reduce the CC load if operating. Neutral temperature a huge energy waste! CC Control based upon maintaining a SA DPT, what happens if the OA is hot and dry ?

18 18 Failing to minimize the use of a chiller when it is cool outside — can be a pitfall for DOAS systems. EW binary control—a duty cycle saves chiller operation. EW using a VFD, maximizes the free cooling of a DOAS.

19 19 EW Duty cycle defined EWeff, 0.8 RAT, 72F SAT=OAT when EW off (40F) SAT=OAT+(RAT-OAT)*EWeff (65.6F) OAT=40F By adjusting the EW ON time (54.7% or 8.2 min) in 1 period (15 min) can get an avg. temperature equal to the desired SAT (54F). Duty cycle changes to 100% ON at 40F OAT to avoid tripping freeze stats. NOTE: HC must be off since when EW off, DAT < DATSP and the CC must be off when the EW on!

20 20 Heating Coil begins modulation at -18F to maintain 54F SAT

21 21 Sample of the duty cycle operation as the OA DBT rises through 40F 15 min. cycle EW off EW on Duty cycle off, EW on 100% Not used when OA < 40F to prevent tripping the freeze stat during EW off part of cycle Beginning of EW duty cycle Target avg. duty cycle temperature

22 22 Conclusions 100% OA DOAS systems discussed. IAQ cost benefits of decoupling discussed. A few parallel systems introduced. Operational benefits explored. Humans are still capable of falling into pits. A few pitfalls discussed. I am convinced DOAS is the future since it solves VAV problems at lower first and operating costs, while providing improved IEQ and safety! More information is available on the DOAS web site noted on the first page.

23 23 If Questions or need more on the control logic, feel free to contact: S. A. Mumma, Prof of Arch. Engineering Penn State University 814-863-2091 e-mail: sam11@psu.edusam11@psu.edu Snail Mail: 214 Engineering Unit A University Park, PA 16802 Visit the: http://doas-radiant.psu.edu web site.http://doas-radiant.psu.edu