Presentation is loading. Please wait.

Presentation is loading. Please wait.

Heating and Air Conditioning I

Similar presentations


Presentation on theme: "Heating and Air Conditioning I"— Presentation transcript:

1 Heating and Air Conditioning I
Principles of Heating, Ventilating and Air Conditioning R.H. Howell, H.J. Sauer, and W.J. Coad ASHRAE, 2005 basic textbook/reference material For ME 421 John P. Renie Adjunct Professor – Spring 2009

2 Chapter 9 – Duct and Pipe Sizing
Duct Systems. This chapter discussed the design of systems for conveying air and water. HVAC system must also distribute conditioned air from a central equipment location to the individual spaces requiring environmental control (fans and ducts, pumps and piping) Objective of duct system design: Provide a system that efficiently transmits the required flow rate of air to each space while maintaining a proper balance between investment and operating costs (within prescribed limits of velocities, noise intensity, and space availability) When heating, cooling and ventilation loads have been established – total flow rates of air can be determined. Size of the duct system governs frictional losses and thereby the size of the fan and power required to operate the duct system.

3 Chapter 9 – Duct and Pipe Sizing
Pressure Changes Resistance to airflow (in both supply and return ducts) must be overcome by mechanical energy – use of a fan. Usually incompressible flow can be assumed (standard density of lb/ft3 or 1.2 kg/m3) Total pressure is sum of static pressure and velocity pressure

4 Chapter 9 – Duct and Pipe Sizing
Pressure Changes Velocity given by (for flow rate and cross-sectional area)

5 Chapter 9 – Duct and Pipe Sizing
Pressure Changes Velocity pressure as function of velocity (standard pressure)

6 Chapter 9 – Duct and Pipe Sizing
Pressure Changes Velocity pressure as function of velocity (standard pressure)

7 Chapter 9 – Duct and Pipe Sizing
Pressure Changes If air is not at standard conditions … Total pressure is a measure of the total available energy at a cross section. Total pressure always decreases in the direction of airflow Static and velocity pressure are mutually convertible and either increase or decrease in the flow direction See Figure 9-1 for total and static pressure changes in a simplified fan/duct system.

8 Chapter 9 – Duct and Pipe Sizing
Pressure Changes – in a ducting system – Figure 9-1

9 Chapter 9 – Duct and Pipe Sizing
Pressure Changes Constant cross-sectional areas: total and static losses are equal – ducts (frictional) fittings (frictional and dynamic) Diverging sections: velocity pressure decreases, total pressure decreases, static pressure may increase (static regain) Converging sections: velocity pressure increases in direction of flow, total and static pressure decrease At exit: total pressure lass depends on the shape of the fitting and the flow characteristics – exit loss coefficients (<1, 0, or >1) When exit loss coefficient is less than one, the static pressure upstream of the exit is below the atmospheric value Total system resistance to airflow is noted as pt in Figure 9-1

10 Chapter 9 – Duct and Pipe Sizing
Pressure Changes Static pressure is used as the basis for system design; total pressure determines the actual mechanical energy that must be supplied to the system. Total pressure always decreases in the direction of the flow. Static pressure can decrease and then increase in the direction of the flow even going below atmospheric. Distinction between static pressure loss and static pressure change as a result of conversion of velocity pressure.

11 Chapter 9 – Duct and Pipe Sizing
Circular Equivalent of Rectangular Ducts Usually systems are size for rounded ducts – then rectangular ducts can be used upon proper conversion for proper flow rates Up to aspect ratios of 8:1, rectangular ducts have same pressure drops and mean velocities for round ducts of the same hydraulic diameter (4 x area/perimeter) Circular equivalents given by Mean velocity in a rectangular duct is less than a circular duct Multiplying or dividing by a factor in rectangular duct is same as that for a circular duct.

12 Chapter 9 – Duct and Pipe Sizing
Circular Equivalent of Rectangular Ducts

13 Chapter 9 – Duct and Pipe Sizing
Frictional Losses Pressure drop in a straight duct is caused by surface friction (see Air Friction Chart Figure 9-2) – standard density of air flowing through clean, rund, galvanized metal ducts – beaded slip covers on 48 inch centers – all temperatures 50 – 90 oF.

14 Chapter 9 – Duct and Pipe Sizing
Frictional Losses

15 Chapter 9 – Duct and Pipe Sizing
Frictional Losses

16 Chapter 9 – Duct and Pipe Sizing
Frictional Losses

17 Chapter 9 – Duct and Pipe Sizing
Dynamic Losses Eddying flow present – greater loss in total pressure Flow disturbances in fittings (entries, exits, transitions, and junctions) Fluid resistance coefficient – ratio of total pressure loss to velocity pressure at the referenced cross-section.

18 Chapter 9 – Duct and Pipe Sizing
Dynamic Losses Occurs along a duct length and cannot be sepearted from frictional loss. Frictional losses considered only for long fittings

19 Chapter 9 – Duct and Pipe Sizing
Dynamic Losses

20 Chapter 9 – Duct and Pipe Sizing
Dynamic Losses

21 Chapter 9 – Duct and Pipe Sizing
Ductwork Sectional Losses Total pressure loss is the combination of the frictional and dynamic losses in terms of Dp. SC is the sum of the local loss coefficients within the duct section. Each fitting loss coefficient must be referenced to that section’s velocity pressure.

22 Chapter 9 – Duct and Pipe Sizing
System Analysis The pressure drop between station 1 and station 2 can be determined for all main and branch ducts in a system (supply and return). The path with the greatest resistance to flow, usually the longest and the one with the most branches, is considered the critical path. The fan is design around satisfying the requirements of this path

23 Chapter 9 – Duct and Pipe Sizing
Duct Design Rules

24 Chapter 9 – Duct and Pipe Sizing
Duct Design Rules

25 Chapter 9 – Duct and Pipe Sizing
Design Velocities Optimization – taking in cost (owning and operating)

26 Chapter 9 – Duct and Pipe Sizing
Design Velocities

27 Chapter 9 – Duct and Pipe Sizing
Design Methods Acceptance of high-velocity transmission systems

28 Chapter 9 – Duct and Pipe Sizing
Design Methods – in general practice Equal Friction Method Size a system for constant pressure loss per unit length of duct After sizing, plot total pressure grade line plotted and optimized Velocity Reduction Method Select velocities at supply and return side of fan and work around the system, reducing the velocities – sizing the ducts accordingly Static Regain Method Ducts are sized so that the increase in static pressure at each take-off offsets the pressure loss of the succeeding section of the ductwork

29 Chapter 9 – Duct and Pipe Sizing
Duct Design Procedures

30 Chapter 9 – Duct and Pipe Sizing
Duct Design Procedures

31 Chapter 9 – Duct and Pipe Sizing
Fitting Loss Coefficients – Nomenclature for Fitting Database

32 Chapter 9 – Duct and Pipe Sizing
Fitting Loss Coefficients

33 Chapter 9 – Duct and Pipe Sizing
Fitting Loss Coefficients

34 Chapter 9 – Duct and Pipe Sizing
Fitting Loss Coefficients

35 Chapter 9 – Duct and Pipe Sizing
Fitting Loss Coefficients

36 Chapter 9 – Duct and Pipe Sizing
Fitting Loss Coefficients

37 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.1

38 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.1

39 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.1

40 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.1

41 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.1

42 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.1

43 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.2

44 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.2

45 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.2

46 Chapter 9 – Duct and Pipe Sizing
Duct Systems – Example 9.2


Download ppt "Heating and Air Conditioning I"

Similar presentations


Ads by Google