Automatic Transfer Switch (ATS) The Key to High Reliability Source Switching.

Similar presentations


Presentation on theme: "Automatic Transfer Switch (ATS) The Key to High Reliability Source Switching."— Presentation transcript:

1 Automatic Transfer Switch (ATS) The Key to High Reliability Source Switching

2 SEA Road Show - Scott Kolek Nov 13 th -16 th, ATS – The Key to High Reliability Source Switching Various technologies are used to switch critical loads from a primary to a backup power source. When nothing goes wrong in the facility (overloads, short circuits, etc.) most technologies perform adequately. When problems occur, certain ATS technologies will keep the power on…others will not. Knowing the differences and correctly applying ATS in your facility is key to providing high reliability source switching. This presentation will include: A definition of ATS An overview of typical ATS applications, constructions, and types A review of the IEC codes and testing procedures for ATS A comparison of the performance of each technology under IEC testing – under normal and abnormal circumstances Application guidelines for selectively coordinated, high reliability, fault- tolerant source switching. Overall recommendations for a Power Quality installations. Presentation Overview

3 Section 1 – ATS Basics  What is an ATS ?  What are typical applications of ATS?  Common constructions of ATS  Common types of ATS

4 SEA Road Show - Scott Kolek Nov 13 th -16 th, G What is an Automatic Transfer Switch (ATS) ? An ATS is a device designed to Automatically switch (transfer) between (2) sources of power to improve the reliability of the electrical supply to a connected load. Primary Source (typically a Utility Supply or Utility Bus) (Normally Energized) Backup Source (typically a Generator Supply (Normally De- Energized)

5 SEA Road Show - Scott Kolek Nov 13 th -16 th, Typical Applications of ATS Utility and Engine Generator  Single unit standby applications are very common Utility and Utility  Dual utility applications are becoming more common Generator and Generator  Prime power / standby application

6 SEA Road Show - Scott Kolek Nov 13 th -16 th, Types of ATS construction Knife Blade Type Knife Blade Type Twin Contactor Type Twin Contactor Type Twin MCCB Type Twin MCCB Type Power Contactor Type Power Contactor Type Static Transfer Type Static Transfer Type GE components GE Power Quality Market Trend

7 SEA Road Show - Scott Kolek Nov 13 th -16 th, Typical ATS Constructions Knife Blade  Typically Non-Load breaking  Usually Manually Operated (and slow)  Sometimes motor operated (still slow)  Low withstand ratings – no arc chutes or vents  Low endurance ratings = limited life

8 SEA Road Show - Scott Kolek Nov 13 th -16 th, Typical ATS Constructions Twin Contactor  Switching device having 1 position of rest (IEC def’n)  Returns to position of loss power (un-latched type) or add’l latching arrangement to hold position on loss of power  Built using 1 of up to 12 types of contactors under IEC Code, from basic contactor to high-capacity motor starters.  Often very basic controller  Mechanical/safety interlock often not available or optional  Variety of operators, from motor to electromagnets  Not a True double throw device - possible to close into both Sources IEC

9 SEA Road Show - Scott Kolek Nov 13 th -16 th, Typical ATS Constructions Twin MCCB (Molded Case Circuit Breaker)  2 Position device, typically operated from add-on motors  Built using 1 of up to 2 types of breaker under IEC Code, from basic instantaneous-trip type to short-time rated devices.  Mechanical/safety interlock is an add-on, sometimes optional  Motor operators usually slow, often unreliable for high duty.  Wide range of manf-assigned withstand ratings (low, med, or high)  Not a True double throw device - possible to close into both Sources IEC

10 SEA Road Show - Scott Kolek Nov 13 th -16 th, Typical ATS Constructions Power Contactor Type (GE Zenith Std.) UL 1008 IEC  Std. Double Throw mechanism - Inherent mechanical interlock against closing to both sources  No add-on interlocks required  Fewer moving parts  High Withstand Current ratings to allow fault clearing coordination  Integrated Arc quenching components  Solenoid Operated (very fast)

11 SEA Road Show - Scott Kolek Nov 13 th -16 th, Power Contactor ATS - Composition Arc quenching grids & enclosed arc chutes Movable contact assembly has 2 pieces, arcing contact and main current carrying contact. Arcing contacts make first, break last [See Video]. Silver alloy contacts Resists welding Enhanced withstand ratings “Over center” switching principal to achieve a mechanically locked position in either Source 1 or 2 High speed solenoid actuated drive assures contact transfer in msec (Click to see video)

12 SEA Road Show - Scott Kolek Nov 13 th -16 th, Typical ATS Constructions Static  Two live sources required. Solid-state switching >> no moving parts  Extremely FAST operation, transfer in less than ¼ cycle.  SCR technology  Typically used on critical loads where 2 reliable and independent power supplies available, or switching 2 x UPS Outputs.  Both sources must be in sync  Often cost prohibitive for Standby applications N E 1 2 L

13 SEA Road Show - Scott Kolek Nov 13 th -16 th, Standard Transition (No Center Position) Delayed Transition (With Center OFF Position) NOTE: “OFF” Position indicates Neither Source connected Closed Transition (Make-Before-Break Operation) NOTE: “P” Position indicates both sources paralleled for 5 cycles Standard Transfer Switch: Types

14 SEA Road Show - Scott Kolek Nov 13 th -16 th, Essentially (2) ATS in Parallel, (1) Automatic Switch (ATS) & (1) Manual Switch (MTS). ATS is withdrawable, similar to withdrawable CB’s (2) redundant paths from each source to load. ATS & MTS are mechanically and electrically interlocked –To prevents accidental closure of both sources Bypassing power from Source to Load permits testing or maintenance of ATS without interruption to load. Available in Open, Delayed, and Closed Transition If power fails while bypassed, Genset is auto started to permit fast transfer using MTS. Bypass Isolation ATS MECHANICAL INTERLOCKS TWO PATHS FROM SOURCE TO LOAD WITHDRAWABLE ATS FIXED MOUNT MTS

15 Section 2 - Codes & Standards for equipment applied as ATS  What are the Internationally- recognized codes?  What is the Performance difference of devices tested to these codes?

16 SEA Road Show - Scott Kolek Nov 13 th -16 th, Devices arranged for Source Switching, but not IEC rated as ATS Contactors & Motor Starters Circuit Breakers Contactors & Motor Starters Circuit Breakers Power Contactors Devices arranged for Source Switching, IEC rated as ATS Internationally-recognized ATS Codes and Standards IEC UL 508 IEC UL 489 IEC UL 1008 Devices may be arranged to function as an ATS, but not be rated as ATS by a Recognized body

17 SEA Road Show - Scott Kolek Nov 13 th -16 th, Twin Contactors Twin CB’s CB: Breaker typePC/CC: Contactor types. IEC Code Circuit Breaker Contactor Transfer Switching Equipment (IEC ‘A’) (IEC ‘AC-1’) Util. Cat. IEC Performance Testing of ATS - Overview (AC-33A, 33B)(AC-31A, 31B) Operational Performance Overload or Low current short circuit Performance High/Short Circuit Performance High Rated current Low majority No Current 31A: High Rated Current 33A: High 2 x Rated Current 31B: Low Rated Current 33B: Low 2 x Rated Current Low 6x Rated Current, High pf, for up to 630A Rating. (N/A >630A) Low 1.5x Rated Current, High pf 31A: High 1.5 Rated Current 33A: High 6x Rated Current 31B: Low 1.5 Rated Current 33B: Low 6x Rated Current GE ATS Ratings No Requirement s Break SC: Yes Make SC: Yes Make & Hold: No Withstand SC: No CC/PC Type: Break SC: No Make SC: Yes Make & Hold: Yes Withstand SC: Yes CB Type: Break SC: Yes Make SC: Yes Make & Hold: No Withstand SC: No

18 SEA Road Show - Scott Kolek Nov 13 th -16 th, Short Circuit Testing of PC-Type ATS PC-type ATS are tested to:  Withstand fault currents (remain closed), for a set period of time, permitting downstream devices to trip and isolate the fault.  Close into faults, to permit the Backup supply fault current necessary to clear the fault.  For this reason, PC-type ATS have Withstand and Close Ratings (WCR) vs. Traditional kAIC Fault rating (as in a CB). FaultTesting (click to see video)click to see video Contactors and Circuit Breakers have Fault current ratings, expressed in kAIC

19 SEA Road Show - Scott Kolek Nov 13 th -16 th, Performance of ATS Technologies - Summary Twin CB’s CB: Breaker typePC/CC: Contactor types. Twin Contactors Low Operation switching of Rated Load Building Event OK Switching Motors w/ 6-10X start OK (up to 630A) >630A Not OK 31A, 31B 33A, 33B OK High Duty Cycle/Switching OK Not OK 31A, 31B 33A, 33B Switching into a short circuit on load side of ATS. Short on load side of ATS Need upstream SCPD to trip Big problem Inst. Trip. Selectivity w/ downstream SCPD ??? Same as above Designed to withstand & permit downstream SCPD to clear Not OK “Real life” performance of ATS in your facility Same as CB Designed to close into and withstand to permit downstream SCPD to clear

20 Section 3 - Application Guidelines for PQ Installations

21 SEA Road Show - Scott Kolek Nov 13 th -16 th, Recommendations to customers & Design Institute :  Specify ATS certified As an ATS to IEC or UL 1008 Un-certified ATS have not been tested for the purposes of source switching.  Specify an ATS with adequate duty cycle rating “A” or “B” IEC Utilization Catagories, based on application  Specify an ATS with adequate overload capability for switching inductive loads “31” or “33” IEC Utilization Catagories, based on application  Specify PC Type of ATS for critical load application … Specify PC-type where fault withstand, vs, tripping under faults, is required for proper system Selective Coordination for faults below ATS.

22 SEA Road Show - Scott Kolek Nov 13 th -16 th, Product Information availability :  An extensive amount of information is available 24 x 7, on the Web, including:  Product Brochures  Guideform Specifications  Drawings  Operation & Maintenance Manuals  Application Information  All information has recently been updated, re-organized, and made easily accessible.  See it all at: GEZenith.comGEZenith.com

23 SEA Road Show - Scott Kolek Nov 13 th -16 th, Support Team in place : Your Country / Area Sales Manager cc: Huang YF (GE PQ ATS Asia ) cc: Scott Kolek (GE PQ ATS Global ) Pre-Sales Application Support: Place an Order: Your Country / Area Sales Manager cc: Huang YF (GE PQ ATS Asia ) cc: Susan Barnes [001] (GE Zenith USA) cc: Scott Kolek [ (GE PQ ATS) Aftermarket Service & Inquiries: Your country / Area Sales Manger. APO Service team – Chen Hao, Yeung Albert. - Same process as UPS. cc: Jason Lin ( GE Zenith USA ) cc: Huang YF (GE PQ ATS Asia ) Pricing/RFQ (please provide Model #): Your Country / Area Sales Manager cc: Susan Barnes (GE Zenith USA) cc: Scott Kolek (GE PQ ATS Global) cc: Huang YF (GE PQ ATS Asia )

24 SEA Road Show - Scott Kolek Nov 13 th -16 th, The GE Zenith Range of ATS ZTX Series  Residential/Light Commercial applications  Amp & Volt ratings  2, 3, or 4-Pole. Std transition. ZTG series  Pre-Engineered & Standard applications requiring dependability and ease of operation  Standard & Delayed Transition  Amp & Volt ratings  2, 3 or 4-Pole ZTS series  Spec Grade & Custom applications  Standard, Delayed, Closed Transition  Bypass versions available with all Transition modes  Amp ratings Volt ratings  2, 3 or 4-Pole

25 Section 4: GE Zenith New Controls  Coming May 2007

26 SEA Road Show - Scott Kolek Nov 13 th -16 th, Our New Controls… (A preview) Ease of Use Graphical Interface Embedded ‘Help’ screens Security Role Based Access Revision control /History Integrated Functionality ATS Control Metering Genset Monitoring Data Logger Diagnostics & Events Capture Soft Key Navigation Role Based Access Revision control /History Front Port Access Easy adjustment of settings using Launchpad thru front USB port Dedicated Control Pushbuttons Auto/Man Engine Control Test Features User-tailored “Info” screen Quick View Mimic Source Availability Source Connected Status Key Status LED’s Graphical Display Large metering values Wide viewing angle Multi-Language Support

27 SEA Road Show - Scott Kolek Nov 13 th -16 th, New ATS Controller (MX350) for New GE Zenith ‘ZTE’ ATS Modular, Card-Cage Construction for Ease of Service and Expandability

28 SEA Road Show - Scott Kolek Nov 13 th -16 th, Competition ParityComparative Advantage Gap New ZTE vs. Features Fill Current Competitive Control Gaps (Not Avail) NEW – Easy & Fast Set/Save/Re-load Config using LaunchPad (SW ships free w/ each ATS. Std front-connect USB port) NEW – Chinese & Spanish Languages (English, German, French, Spanish, Portuguese) NEW – Graphical OIP w/ Customer-Config INFO & HELP screens for simple, intuitive operation (Softload model only) NEW – Expanded Service Diagnostics + Utility Fail & Emerg. Pwr. system Performance info NEW – Auto Load Shed on sensed ANSI 81U, 27/59, or Overload (Not Avail) (Separate Metering) NEW – Built-in Power Quality Metering, including THD & waveform oscillography New Features Many ZTS options made Std. – 365 Day Ex (CDP), R103 (Util 47), R16 (Ph Rot), Q2 (Peak Shave), AB3/4 (Bypass Pos), DSLC (Disc Sw), TMS (Trans Mode for CT), Gen-Gen exerciser, User MB Address setup.

29 SEA Road Show - Scott Kolek Nov 13 th -16 th, ParityComparative Advantage Gap NEW – Flexible Control Switches – Setup in LaunchPad NEW – Event and metering integration: High speed event capture + Pre/Post event metering & oscillography for efficient & accurate fault diagnostics New T5/T7 vs. (Not Avail) (Not Avail) NEW – Direct source sensing up to 690VAC Without need for step-down transformers NEW – Direct Genset Communications and Failsafe Programmable Remote I/O reduce total installed costs NEW – Extensive Modbus Data map of all events, metered data, and diagnostics for BMS system NEW – Remote service connect, diagnostics, and calibration using built-in TCP/IP Network Connection (Not Avail) NEW – Reassignment of switch features in the field to accommodate site changes (using LaunchPad). (Not Avail) Features New Features (cont) NEW – Full range of transfer types, inc. Softload NEW – Built-in Serial and TCP/IP Communications for easy facility integration (Separate Cards) (Significant differences for Softload NEW – Field-upgradeable for additional I/O and new features ($$$$) Competition

30 SEA Road Show - Scott Kolek Nov 13 th -16 th,


Download ppt "Automatic Transfer Switch (ATS) The Key to High Reliability Source Switching."