Presentation is loading. Please wait.

Presentation is loading. Please wait.

1 GE Digital Energy Instrument Transformers, Inc. Test Switches & Plugs Type FT Type RT Type PK-2.

Similar presentations


Presentation on theme: "1 GE Digital Energy Instrument Transformers, Inc. Test Switches & Plugs Type FT Type RT Type PK-2."— Presentation transcript:

1 1 GE Digital Energy Instrument Transformers, Inc. Test Switches & Plugs Type FT Type RT Type PK-2

2 2 GE Digital Energy Instrument Transformers, Inc. Agenda  What are Test Switches & Test Plugs?  10 Pole FT Test Switches Features & Uses Design Details Selection & Ordering Information Typical Connection Diagram  10 Pole FT Test Plugs “In-Service Series” Application “Separate Source” Application  Typical FT Test Switch Installations  RT Rack Mounted Test Switches  ABB to ITI Cross Reference for FT Test Switches  4 & 6 Pole PK-2 Test Blocks and Plugs Ordering Information Features & Uses Design Details

3 3 GE Digital Energy Instrument Transformers, Inc. What are Test Switches & Test Plugs? Test Switches are devices designed for mounting on switchboard panels for use in conjunction with proper test equipment to facilitate the testing of instruments, meters, and relays. Test Plugs are multi circuit devices designed to be used with test switches to enable easy measurement, calibration, verification or maintenance of instruments, meters, and relays.

4 4 GE Digital Energy Instrument Transformers, Inc. FT Test Switches 10 Pole FT Test Switch 10 Pole FT Test Plug Consist of (2) components

5 5 GE Digital Energy Instrument Transformers, Inc. 10 Pole FT Test Switch -- Features & Uses Semi-flush mounted in front panel Rear termination provisions Configurable to meet customer requirements Black or clear (optional) safety cover Provisions for meter type seal Isolate relay inputs & outputs for injection of current & voltage from separate sources (Use “Separate Source” Test Plug) Measure system currents & voltages during field testing & commissioning (Use “In-Service Series” Test Plug) FTC-066 Test Switch with clear cover FT-066 Test Switch with black cover

6 6 GE Digital Energy Instrument Transformers, Inc. 10 Pole FT Test Switch Front view with cover removed Blades open 10 Poles labeled “A” thru “J” ITI P/N FT-099

7 7 GE Digital Energy Instrument Transformers, Inc. FT Test Switch – Rear terminals Threaded rear terminals Terminal numbers molded into base Nickel plated brass pan head screws, flats, & locks supplied loose Threaded studs and hex nuts available as option

8 8 GE Digital Energy Instrument Transformers, Inc. FT Pole Assemblies “P” = Potential “C” = Current Non-Shorting “C-C” Current Shorting (2-Poles Required) “C-C-C” Current Shorting (3-Poles Required) “C-C-C-C” Current Shorting (4-Poles Required)

9 9 GE Digital Energy Instrument Transformers, Inc. 10 Pole FT Test Switch Typical Selection table (Note poles A through J……Reference slide 4) “P” = Potential (Poles A, B, & J) “C” = Current Non-Shorting (Pole C) “C-C” = Current Shorting (2-Poles Required) (Poles D-E, F-G, & H-I) Schematic Symbols

10 10 GE Digital Energy Instrument Transformers, Inc. FT Test Switch Potential Pole “P” Non-Shorting Blade used for voltage and trip circuits Blade assembly of (1) position potential pole (P) Rear Termination Provision

11 11 GE Digital Energy Instrument Transformers, Inc. Blade assembly of (2) position current shorting pole with current test jack (C-C) Shorting Blade Bottom cam of the shorting blade makes contact with the shorting spring of the pole to the right before disengaging from the jaw (Make before break contact) Shorting Spring from Non-Shorting Pole to Right Non-Shorting Blade with Current Test Jack Rear Termination Provision FT Current Shorting Pole ‘C-C’ Jaw Let’s take a look at the current test jack pole to the right

12 12 GE Digital Energy Instrument Transformers, Inc. FT Non-Shorting Current Pole ‘C’ Blade assembly of non-shorting current pole with current test jack (C) --- Part of 2-pole (C-C) Current Test Jack for insertion of current test probe Rear Termination Provision Jaw Non-Shorting Blade (Open)

13 13 GE Digital Energy Instrument Transformers, Inc. FT Test Switch Handles Optional interlocking bar kit (3) Potential blades tied together with interlocking bar kit Molded slot for circuit identification card

14 14 GE Digital Energy Instrument Transformers, Inc. FT Test Switch Part Number System See next slide for typical selection chart

15 15 GE Digital Energy Instrument Transformers, Inc. Typical FT Test Switch & Test Plug Selection Chart Test Switch Part Number FT-066 In-Service Series Test Plug Part Number Potential Pole Position “A” (2) Pole Current Shorting with Test Jack Position “F-G”

16 16 GE Digital Energy Instrument Transformers, Inc. Non-Standard FT Test Switch Specification Form Step 1 The switch body can support 1 to 10 poles in slots marked A through J. Enter a letter from the legend. Leave unused slots blank. Legend: P = Potential, Black; T = Potential, Red; O = Potential, Orange; Y = Potential, Yellow; G = Potential, Green; B = Potential, Blue; W = Potential, White C = Current, Non-shorting, Black R = Current, Non-shorting, Red C--C, C--C--C, C--C--C--C = Current, Shorting with current test jack right most position, Black R--R, R--R--R, R--R--R--R = Current, Shorting with current test jack right most position, Red CO = Current, Orange; CY = Current, Yellow;CG = Current, Green; CB = Current, Blue; CW = Current, White Note: Some functions will require more than one slot in the switch body Step 2 If a tie bar is required check this box and draw a dark heavy line over the poles to be joined. In the example above positions H, I, & J will operate together. Step 3 Select a cover style Clear (Installs over open or closed switches) Black (Installs over closed switches only) Step 4 Select a rear terminal type Screws (Standard)Studs (Optional) A BCDEFGHIJ CC--CR--R- -R PPP Example: A BCDEFGHIJ

17 17 GE Digital Energy Instrument Transformers, Inc. 10 Pole FT Test Switch Typical Connection FT-076

18 18 GE Digital Energy Instrument Transformers, Inc. 10-Pole “In-Service Series” Test Plug Used in conjunction with 10-pole test switch Various designs to match specific 10 pole test switches Used to connect devices to measure currents & voltages being applied to the switchboard relays & meters without interrupting or short circuiting the circuit

19 19 GE Digital Energy Instrument Transformers, Inc. “In-Service Series” Test Plug Application Circuit detail of FT test switch prior to insertion of “In-Service Series” Test Plug FT Test Switch Existing Meter or Relay Existing Meter or Relay Circuit detail of FT test switch after insertion of “In-Service Series” Test Plug & connection of external instruments External Current Measuring Instruments FT Test Switch Bi-Conductor Paddle & Leads Instrument Ground… Use “Potential Stab”

20 20 GE Digital Energy Instrument Transformers, Inc. 10-Pole “Separate Source” Test Plug Used in conjunction with 10-pole test switch Used to isolate and connect the “out of service” relays or switchboard devices to external test instruments Currently Not Available from ITI ABB Part Number States Part Number FTP10-10

21 21 GE Digital Energy Instrument Transformers, Inc. Bi-Conductor Paddle & Lead to External Current Supply “Separate Source” Test Plug Application Circuit detail of FT test switch prior to insertion of “Separate Source” Test Plug FT Test Switch Existing Meter or Relay Separate Source Current Supply Circuit detail of FT test switch after insertion of “Separate Source” Test Plug & connection of external current supply Existing Meter or Relay FT Test Switch

22 22 GE Digital Energy Instrument Transformers, Inc. MV MCC MV Switchgear FT Switches – Typical Installations Relay / Control Panels

23 23 GE Digital Energy Instrument Transformers, Inc. Multilin Standard RT Model Up to (3) type FT Switches per panel Black panel – 19 inches wide x 5.22” high Full width clear cover – handles either open or closed Meter seal provisions Padlock provisions Access to panel mounting hardware prevented with cover installed Clear safety shield at rear screw terminal area Right FT suffix Center FT suffix Left FT suffix RT LLL CCC RRR Part number system

24 24 GE Digital Energy Instrument Transformers, Inc. Optional RT Models Available Up to (3) type FT switches per panel Panel heights: 3.47” 5.22” 5.22” offset 6.97” Panel colors: ANSI 61 & 49 gray Brushed aluminum Full width clear cover – handles either open or closed

25 25 GE Digital Energy Instrument Transformers, Inc. Part number system for optional RT models

26 26 GE Digital Energy Instrument Transformers, Inc. FT Test Switch - ABB to ITI Cross Reference (*) Consult factory for other part numbers (*) This cross reference is intended to be accurate; however, all equivalent part numbers are based on available competitor product data only. Therefore this cross reference should be used as a guide only. All recommended ITI configurations to be confirmed by customer before placing orders.

27 27 GE Digital Energy Instrument Transformers, Inc. PK-2 Test Blocks & Plugs 4 & 6 Pole PK-2 Test Block 4 & 6 Pole PK-2 Test Plug P/N G14-Pole; surface mount on 1 to 2 inch panels P/N G26-Pole; surface mount on 1 to 2 inch panels P/N G34-Pole; semi-flush on 0.12 inch panels surface mount on 0.12 to 0.5 inch panels P/N G46-Pole; semi-flush on 0.12 inch panels surface mount on 0.12 to 0.5 inch panels P/N G14-Pole P/N G26-Pole

28 28 GE Digital Energy Instrument Transformers, Inc. PK-2 Test Blocks – Features & Uses Semi-flush or surface mounted Cover removal automatically shorts current circuits Rear termination provisions Provided with unmounted auxiliary contacts, jumpers, and hardware for field installation into test block Reference application data for typical arrangements of contacts & jumpers Type PK-2 in “search”; Select “PK-2 test Blocks and Plugs – Product Information”; Select “Brochures” Routine testing accomplished by removing cover and inserting the properly connected test plug Normal connections restored by replacing cover

29 29 GE Digital Energy Instrument Transformers, Inc. PK-2 Test Blocks Legend: 6-Pole Test Block with Cover Removed (Component parts defined below) (1) Auxiliary ContactMaintains circuit with cover or plug not installed (2) Auxiliary ContactShort circuits CT with cover or plug not installed (3) JumperUsed with contacts (2) or (4) -- short circuits CT or interconnects phases when cover-fastening stud is to be bypassed (4)Auxiliary ContactEqual to one pole of contact (2) & used with jumper (3)

30 30 GE Digital Energy Instrument Transformers, Inc. PK-2 Test Plugs Test Links supplied with plug (4) with the 4-pole (6) With the 6-pole Links can be installed vertically or horizontally Refer to application data for typical test link arrangements Type PK-2 in “search”; Select “PK-2 test Blocks and Plugs – Product Information”; Select “Brochures” Test Links

31 31 GE Digital Energy Instrument Transformers, Inc. QUESTIONS


Download ppt "1 GE Digital Energy Instrument Transformers, Inc. Test Switches & Plugs Type FT Type RT Type PK-2."