Presentation is loading. Please wait.

Presentation is loading. Please wait.

Variable Energy Cylcotron Centre 1 Control Philosophy of VEC & SCC Anindya Roy, C & I Group.

Similar presentations


Presentation on theme: "Variable Energy Cylcotron Centre 1 Control Philosophy of VEC & SCC Anindya Roy, C & I Group."— Presentation transcript:

1 Variable Energy Cylcotron Centre 1 Control Philosophy of VEC & SCC Anindya Roy, C & I Group

2 Variable Energy Cylcotron Centre2 Control Philosophy of VEC & SCC Control LAN PLC / NIFP PLC Device RS232 RS485 RS232 RS-422/485 Ethernet-Serial Control Database HMI Stations Device Layer Control Layer - 1 Control Layer - 2 PC based Controller Local database... PC based Controller

3 Variable Energy Cylcotron Centre3 Features of Control LAN Isolated from VECC General LAN to maximize Security. Free from Worms & Viruses. Star topology: 2-Tier Design – Central Switch in the Control Room & Floor Switches in different floors like Basement, Basement Mezzanine, Vault etc. Fiber Gigabit Backbone and end-to-end fiber connectivity in the Radioactive Zone for reliability. Node level speed: 100 Mbps. Media Converter for devices having no fiber port. Service zone: CAT5E UTP Cabling Tolerant to single switch / link failure due to Resiliency in Hardware. Network Management Software (NMS) for managing the network with indication for probable link failure In-house capability for maintenance and extension of SCC LAN, leading to minimum downtime and ease of operation. Presently copper cabling in all segments. Fiber cabling will be taken up shortly.

4 Variable Energy Cylcotron Centre4 Advantage of Fiber Cabling Immunity to EMI and RFI noise Not limited by 100 mtr segment length of UTP Copper Cabling. Permissible range allowed for Gigabit Ethernet : 550 mtr. (Multimode) Can be laid side by side with Power cable. Neither radiate noise nor get affected by noise radiated by other cable bundle. Lower signal attenuation. No cross talk hazard. Packet loss minimum. Longer life expectancy (Minimum 25 years of working life). Future proof cabling (Same cabling for Fast Ethernet, Gigabit Ethernet and ten- Gigabit Ethernet). No ground loop. Secure communication. Light signal can not be tapped. Most suitable for backbone application. For Industrial environment and hazardous areas Fiber is the ideal solution

5 Variable Energy Cylcotron Centre5 Resiliency in Hardware ERS 5530 Central Switches (Control Room) Floor Switch Distributed Multilink Trunking 4 Gbps (DMLT) 4 Gbps DMLT Fail-safe Stack Fail-safe Stacking configuration of Central switches provides redundancy with future extendibility Active-active mode provides double backbone bandwidth in normal operation i.e. 4 Gbps instead of 2 Gbps Distributed Multilink Trunking (DMLT) provides tolerance to single link failure between Central switches and Floor switches

6 Variable Energy Cylcotron Centre6 Subsystems of VEC & SCC Cryogenic Plant Cryogen Delivery System High Current Power Supplies Deflector Power Supply Vacuum System ECR Ion Source LCW Monitoring System Trim-coil Temperature Control System Radiation Monitoring System Sub-station Control System Door Control System Control Database SCC Control Room

7 Variable Energy Cylcotron Centre7 Cryogenic Plant Control System Scope of control Helium Liquefier- Refrigerator of 250W @ 4.5K refrigeration capacity for Superconducting Cyclotron Helium Liquefier- Refrigerator of 250W @ 4.5K refrigeration capacity for Superconducting Cyclotron 16500 litres Liquid nitrogen storage and distributions for Superconducting Cyclotron 16500 litres Liquid nitrogen storage and distributions for Superconducting Cyclotron Gas management systems like compressors, gas bags and buffer tanks Gas management systems like compressors, gas bags and buffer tanks Pneumatic and chilled water systems for the above Pneumatic and chilled water systems for the above Total over 500 field input outputs and 8 interlinked process control loops Total over 500 field input outputs and 8 interlinked process control loops

8 Variable Energy Cylcotron Centre8 Control Architecture of Cryogenic Plant Control LAN Eurotherm PC3000 PLC Controlling helium liquefier Modbus RTU Modbus TCP Gateway Schneider Premium PL7 PLC Controlling gas management, liquid nitrogen and pneumatic system EPICS IOC For both PLCS EPICS Data Archiver & Server Operator interfaces with EPICS Control & Archive viewer Modbus TCP

9 Variable Energy Cylcotron Centre9 Operator Interface of Cryogenic Plant Control System

10 Variable Energy Cylcotron Centre10 High Current Magnet Power Supplies Main Magnet Power Supplies (Nos. 2) Main Magnet Power Supplies (Nos. 2) 20 V, 1000 A, 10 ppm 20 V, 1000 A, 10 ppm Trim Coil Power Supplies (Nos. 18) Trim Coil Power Supplies (Nos. 18) 400 A, 10 ppm 400 A, 10 ppm Windows based HMI developed in VB 6 Windows based HMI developed in VB 6 All these power supplies are equipped with intelligent controllers and serial transceivers and can be operated and monitored remotely over a serial link

11 Variable Energy Cylcotron Centre11 Control Architecture

12 Variable Energy Cylcotron Centre12 Operator Interface for Main Magnet Power Supplies

13 Variable Energy Cylcotron Centre13 Operator Interface for Trim Coil Power Supplies

14 Variable Energy Cylcotron Centre14 Magnetic Field Mapping System Scope Field measurement - at different excitations up to ~26” radius & on discrete azimuthal bands beyond 26” radius Analysis of the measured raw data for magnet correction Finding the magnetic symmetry axis Correction of average iron field distribution by iron shims Minimization of first harmonic component by shimming Coil centering by support link force balance Salient features Automated High speed data taking - ~ 90 min per 100K Data Points 70 micron radial encoder resolution 0.004 deg. Angular Encoder resolution Special precision electronics (VFC, NMR, Jig controller, smart motors) PC based Client-Server architecture implemented using C & LabVIEW On-line plot and harmonic analysis for error correction.

15 Variable Energy Cylcotron Centre15 HMI & System set-up of MFM System

16 Variable Energy Cylcotron Centre16 Results of Magnetic Field Mapping Average Field Correction 1 st Harmonic Field Correction

17 Variable Energy Cylcotron Centre17 Deflector Power supply Control & Conditioning System Conditioning the deflector by conditional ramping of voltage depending on dark current EPICS IOC communicating with Deflector power supply, DAQ modules and Vacuum gauge controller in ASCII protocol over RS-232 EPICS Archiver for data storing and analysis Operator Interface

18 Variable Energy Cylcotron Centre18 Control Architecture of Deflector Power Supply Control & Conditioning System

19 Variable Energy Cylcotron Centre19 Vacuum Control System Control LAN EPICS IOC Vault Beam line PLC Main machine & Linear PLC Cave Beam line PLC HMI Station ORACLE Archiver 24 Pumping modules consisting of Scroll pump, Turbo pump, Rotary pump, UHV Valve, Pirani gauge & Combination gauge Distributed control architecture to minimise system downtime EPICS based IOC, VB based HMI & Oracle archiver Windows Activex components for building HMI

20 Variable Energy Cylcotron Centre20 Operator Interface of SCC Vacuum Control System

21 Variable Energy Cylcotron Centre21 Operator Interface of VEC Vacuum Control System

22 Variable Energy Cylcotron Centre22 Control architecture of ECR Ion Source Distributed realtime control system based on Field point RT modules from National Instruments

23 Variable Energy Cylcotron Centre23 Operator Interface of ECR Ion Source

24 Variable Energy Cylcotron Centre24 LCW Plant Monitoring System Scope of the system Monitoring 18 process parameters e.g. Temperature, Pressure, Flow, Conductivity, Level & pH Monitoring 18 process parameters e.g. Temperature, Pressure, Flow, Conductivity, Level & pH Modbus-TCP based DAQ modules Modbus-TCP based DAQ modules Windows based EPICS IOC & MMI developed using VB Windows based EPICS IOC & MMI developed using VB Control LAN Data Acquisition Module EPICS IOC & HMI Control Architecture MODBUS-TCP

25 Variable Energy Cylcotron Centre25 Operator Interface of LCW Plant

26 Variable Energy Cylcotron Centre26 Trim-coil Cooling Water Temperature Control System Monitoring 15 process parameters e.g. Temperature, Pressure, Flow, Conductivity & Level Monitoring 15 process parameters e.g. Temperature, Pressure, Flow, Conductivity & Level Controlling Trim-coil Cooling Water temperature, Conductivity & Surge tank level Controlling Trim-coil Cooling Water temperature, Conductivity & Surge tank level Providing interlock to TCPS Providing interlock to TCPS Siemens Redundant Controllers & ELIPSE SCADA based MMI Siemens Redundant Controllers & ELIPSE SCADA based MMI Control Architecture Control LAN EPICS IOC & HMI MODBUS-RTU Siemens Redundant Controllers 16 Ch Scanner Ethernet to Serial

27 Variable Energy Cylcotron Centre27 Operator Interface of Trim-coil Temperature Control System

28 Variable Energy Cylcotron Centre28 Substation Control System Scope of Control Four nos. of incoming feeder including two diesel generators Four nos. of incoming feeder including two diesel generators Bus coupler Bus coupler Fifteen nos. of outgoing feeders Fifteen nos. of outgoing feeders Five nos. of Tri-Vector Energy meters Five nos. of Tri-Vector Energy meters Control Architecture Control LAN IOC & Archiver MMI & Archive viewer Schneider Premium PLC Modbus TCP

29 Variable Energy Cylcotron Centre29 Operator Interface of Substation Control System

30 Variable Energy Cylcotron Centre30 Radiation Monitoring System 21 Neutron Flux Monitors and 12 Gamma Area Monitors Located at various locations in SCC building e.g. Vault, Basement, Caves, High-bay, RF Power supply Room, MMPS Room Dedicated multidrop RS-485 Control LAN for Remote monitoring at Health Physics Providing Interlock to Door Control System, RF System & Access Control System Door Control System 6 Radiation Shield Doors at Vault, Basement, Cave-1, Cave-2 & Cave-3 Provide safety interlock to ECR, RF & Shield wall plug operation Compel operator to search for human occupancy at Radiation zone before switching on Cyclotron by making safety-chain complete Interlocked with respective radiation monitors PLC based system for generating interlock and alarm

31 Variable Energy Cylcotron Centre31 Control Database Oracle 11g Database Server Dual Intel Xeon Processor, dual Power supply & RAID 6 Configuration to ensure data integrity DAT Drive for backup at regular interval to prevent data overflow Control data storage for Historic analysis Data exchange among different systems OracleArchiver for interfacing EPICS based system with Oracle database

32 Variable Energy Cylcotron Centre32 OracleArchiver – Integration between Oracle & EPICS An Extension for interfacing EPICS based system with Oracle database Developed using “Oracle C Ineterface” Supports scan & monitor types of data logging Inbuilt web server for distributed online viewing and historic data analysis Web based Addition/Removal/Modification of logged parameter Easy to configure!

33 Variable Energy Cylcotron Centre33 OracleArchiver – online viewing page

34 Variable Energy Cylcotron Centre34 OracleArchiver – historic analysis page

35 Variable Energy Cylcotron Centre35 OracleArchiver – Addition/Removal/Modification page

36 Variable Energy Cylcotron Centre36 Control Room PC based remote control and monitoring of all systems Assignable soft knobs for controlling multiple parameters Alarm, On-line numerical display and trending of important parameters KVM (L) KVM (R) KBMouseVDU Anti-room Console UTP CAT 5E Control LAN

37 Variable Energy Cylcotron Centre37 Beam Diagnostic Systems Viewer Probe Main Probe Magnetic Channels

38 Variable Energy Cylcotron Centre38 LCD TV BORESCOPE DRIVING MECHANISM LINEAR ENCODER Stepper Motor Driver Read-Out System Valve control/Read CCD CAMERA RS232 RS485 SERVER PC AT BASEMENT CONTROL LAN CLIENT PC AT CONTROL ROOM SUPERCONDUCTING CYCLOTRON Control Architecture & HMI of Viewer Probe

39 Variable Energy Cylcotron Centre39 Stepper Motor Driver Gate Valve & Limit Switch Reading Read out System Filter Box Electrometer 10 Ch. Curr. Scanner Lin. Encoder Step. Motor Super Conducting Cyclotron Control Architecture of Main Probe System Control LAN RS232 Ethernet to Serial HMI Station 4 finger Probe – Top, Middle, Bottom & ΔR MMI developed in VB6 with MSExcel data storing Plot against Radius with Zooming facility

40 Variable Energy Cylcotron Centre40 Operator Interface of Main Probe System

41 Variable Energy Cylcotron Centre41 *01* 23.456 mm*02* 23.456 mm*09* 23.456 mm*10* 23.456 mm RS485 SERVER PC AT BASEMENT CONTROL LAN CLIENT PC AT CONTROL ROOM Position Read- Out Modules GUI (Server) for Magnetic Channels Position Monitoring SCC MAGNETIC CHANNELS CURRENT MULTIPLEXER ELECTROMETER RS232 Control Architecture & HMI of Magnetic Channels

42 Variable Energy Cylcotron Centre42 Sincere regards to: N. C. Samanta B. Mukhopadhyay C. D. Dutta P. Y. Nabhiraj R. B. Bhole Biswajit Sarkar Tanushyam Bhattacharjee U. S. Panda Joydeep Mishra Niraj Chaddha

43 Variable Energy Cylcotron Centre43 Thank you!


Download ppt "Variable Energy Cylcotron Centre 1 Control Philosophy of VEC & SCC Anindya Roy, C & I Group."

Similar presentations