Published byIrving Ingraham Modified over 9 years ago
2
Ted “Smitty” Smith
3
I have included in the following slides some key sections from each of the codes you will primarily encounter on the test. I recommend reading each of the key sections noted. The Denver Building Amendments can be difficult to navigate. I recommend reading through one time the entire Chapter 5 and reading through two times the entire Chapter 9. The majority of the second part of your test will be answered in Chapter 9 of the Denver Building Amendments.
4
NEC Article 760.142 Article 760.154(B)(1) Article 760.130(A) Article 760.143 Article 760.176
5
10.4.1.2 10.5.5.2.2 10.5.5.2.3 10.5.6.3 10.5.6.4.1 10.5.9.1.1 10.5.9.3.2 10.5.9.6.1 10.5.9.6.2 10.11.5.2 10.16.3.1 10.16.3.2 10.17.1.13 10.18.2.3
6
14.2.2.1 14.2.7.2 14.2.8 T14.3.1 Section 8 T14.3.1 Section 9 (h) T14.3.1 Section 19(3) 14.4.5.3 14.4.5.3.1 14.4.5.3.2 T14.4.5 Section 5(a) T14.4.5 Section 15(h) 14.4.5.3.3 14.4.6 14.4.8.1 14.6.1.3
7
17.5.2 17.6.3.1.2 17.7.3.2.1 17.3.2.3.1 17.7.6.3.1 T17.7.6.3.3.1 17.12.2 18.3.3.2 18.3.4.2 18.3.5.2 18.4.1.1 18.4.4.1 18.5.2.4 18.5.2.6 18.5.4.4.1 18.5.4.4.4
8
23.2.3.1 23.5.2 23.8.1.1 23.8.4.7 23.8.5.5.2 23.8.5.6.2 23.8.6.2.1 23.8.6.2.4 23.16.4 23.18.4.2
9
510.1.1.3 907.1.2.2 Exceptions 1 and 2 907.1.6 Exception 2 907.1.6 Exception 9 907.2.13.1 (6) 907.2.23 Also be sure to check exception 907.6.2.1 907.7.3.1 907.7.3.1.2
10
This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National Fire Alarm and Signaling Code and the Denver Building Amendments. If you put the slide show into slide show mode, the slides will transition automatically and allow you 3 minutes for each question. The answers will stay up for only 15 seconds. When you reach the end of the practice test there will be a slide that reads STOP. You can then click on the slide and the questions will be repeated without the timer so that you can write down questions and answers and take notes. During the timed section, do not worry about writing down the correct answer. Proceed through the timed section then review the questions and answer again without the timer.
11
Conductors of ______ AWG shall be permitted only where spliced with a connector listed as suitable when used in a PLFA circuit.
12
26 760.142
13
Type ________ cable may be used in place of FPLP cable in a plenum area for PLFA circuit.
14
CMP 760.154 (A)
15
Conductors for NPLFA wiring methods shall be cables that are made of solid or stranded copper or aluminum only. True or False
16
False Copper Only 760.130 (A)
17
Complete records of all signals received by a supervising station shall be kept for a period of ________________.
18
1 year NFPA 72 26.4.6.1
19
A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.
20
2500 NFPA 72 27.5.2.1.2
21
A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________. A. comply with NFPA 72 B. not be required to comply with NFPA 72 C. comply with chapters 17 and 18 of NFPA 72 only D. comply with the NEC only
22
A. comply with NFPA 72 (23.2.3.1)
23
A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures. 3 6 10 15
24
10 (23.4.2.2 List item 1)
25
A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring. Supervisory Alarm Trouble None of the above
26
Trouble (23.5.2)
27
Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device. 5 seconds 10 seconds 30 seconds 1 minute
28
10 seconds (23.8.1.1)
29
Power limited fire alarm circuit conductors shall not be strapped, taped, or attached by any means to the exterior of any conduit or other raceway as a means of support. True False
30
True NEC 760.143
31
Visible notification signals _______________________ be required in exit stair enclosures and exit passageways. Shall Shall not
32
Shall not (23.8.6.2.1)
33
Type NPLFP cable shall be listed for use if used in other spaces used for environmental air and shall also be listed as having adequate fire resistance and ________________characteristics.
34
Low smoke producing NEC 760.176(C)
35
New and existing buildings shall have approved address numbers, building numbers or letters, or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Addresses are not required to be posted at the rear of the property at the alleyway. True or False
36
False Must be at alleyway also DBA 505.1
37
High Rise buildings shall be supplied by a minimum of three independent public water mains. True or False
38
False Two DBA 507.2.3
39
A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies. One Two Three Four
40
Two (10.5.3.2)
41
A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted. One Two Three Four
42
Three (10.9.3)
43
A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition. One Two Three Four
44
Two (10.11.1.1)
45
In existing buildings undergoing a panel replacement, remote annunciators with silence and reset functions may be provided when approved by the dire code official. The units shall be equipped with enable/disable switches and shall be contained behind a transparent, lockable cover. True or False
46
False Shall not be equipped with an enable/disable DBA 907.1.2.2 Exception 1
47
Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector. 6 inches 12 inches 18 inches 24 inches
48
12 inches ( 17.7.3.2.1)
49
The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________. Monthly Quarterly Semi-annually Annually
50
Semi-Annually (Table 14.3.1 Page 57)
51
Systems undergoing maintenance or modification shall not have any portion of the system our of service for more than 8 hours. True or False
52
False 10 DBA 907.1.6
53
Automatic smoke detection is required not less than one foot but no more than three feet on the occupied side of each door that enters a refuge area, elevator lobby and exit stairway in building types R-4. True or False
54
True DBA 907.2.13.1 (6)
55
An approved automatic smoke detection system shall be installed in areas containing stationary storage battery systems having a liquid capacity of more than 75 gallons. Where the alarm is installed, provide signage indicating “Battery Room Alarm-Call 911.” True or False
56
False 50 gallons DBA 907.2.23
57
Where practical difficulties are associated with replacement of fire alarm systems in existing high rises two fire alarm control panels shall not be allowed during the phased upgrade. Existing and new fire alarm control panels shall be co located at a location approved by the fire code official. True or False
58
False Two panels are allowed DBA 907.1.6 Exception 2
59
In a nightclub means shall be provided to reduce or eliminate background noise upon activation of the fire alarm system. True or False
60
True DBA 907.6.2.1
61
Annunciator panels shall be point lit graphic or computer graphic or a directory LED point display. True or False
62
True DBA 907.7.3.1
63
In a group I occupancy a manual fire alarm system is allowed. True or False
64
True DBA 907.2.6
65
Buildings with a floor used for human occupancy located more than 50 feet above the lowest level of fire department vehicle access shall be provided with a fire command center. True or False
66
False DBA 907.2.13
67
In a group E occupancy a manual fire alarm system is not required if 20 or less occupants and 120V AC single or multiple station residential smoke alarms with battery back up, wired to a switched source are provided. True or False
68
False Unswitched DBA 907.2.3 Exception 2
69
STOP
70
Conductors of ______ AWG shall be permitted only where spliced with a connector listed as suitable when used in a PLFA circuit.
71
26 760.142
72
Type ________ cable may be used in place of FPLP cable in a plenum area for PLFA circuit.
73
CMP 760.154 (A)
74
Conductors for NPLFA wiring methods shall be cables that are made of solid or stranded copper or aluminum only. True or False
75
False Copper Only 760.130 (A)
76
Complete records of all signals received by a supervising station shall be kept for a period of ________________.
77
1 year NFPA 72 26.4.6.1
78
A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.
79
2500 NFPA 72 27.5.2.1.2
80
A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________. A. comply with NFPA 72 B. not be required to comply with NFPA 72 C. comply with chapters 17 and 18 of NFPA 72 only D. comply with the NEC only
81
A. comply with NFPA 72 (23.2.3.1)
82
A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures. 3 6 10 15
83
10 (23.4.2.2 List item 1)
84
A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring. Supervisory Alarm Trouble None of the above
85
Trouble (23.5.2)
86
Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device. 5 seconds 10 seconds 30 seconds 1 minute
87
10 seconds (23.8.1.1)
88
Power limited fire alarm circuit conductors shall not be strapped, taped, or attached by any means to the exterior of any conduit or other raceway as a means of support. True False
89
True NEC 760.143
90
Visible notification signals _______________________ be required in exit stair enclosures and exit passageways. Shall Shall not
91
Shall not (23.8.6.2.1)
92
Type NPLFP cable shall be listed for use if used in other spaces used for environmental air and shall also be listed as having adequate fire resistance and ________________characteristics.
93
Low smoke producing NEC 760.176(C)
94
New and existing buildings shall have approved address numbers, building numbers or letters, or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Addresses are not required to be posted at the rear of the property at the alleyway. True or False
95
False Must be at alleyway also DBA 505.1
96
High Rise buildings shall be supplied by a minimum of three independent public water mains. True or False
97
False Two DBA 507.2.3
98
A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies. One Two Three Four
99
Two (10.5.3.2)
100
A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted. One Two Three Four
101
Three (10.9.3)
102
A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition. One Two Three Four
103
Two (10.11.1.1)
104
In existing buildings undergoing a panel replacement, remote annunciators with silence and reset functions may be provided when approved by the dire code official. The units shall be equipped with enable/disable switches and shall be contained behind a transparent, lockable cover. True or False
105
False Shall not be equipped with an enable/disable DBA 907.1.2.2 Exception 1
106
Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector. 6 inches 12 inches 18 inches 24 inches
107
12 inches ( 17.7.3.2.1)
108
The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________. Monthly Quarterly Semi-annually Annually
109
Semi-Annually (Table 14.3.1 Page 57)
110
Systems undergoing maintenance or modification shall not have any portion of the system our of service for more than 8 hours. True or False
111
False 10 DBA 907.1.6
112
Automatic smoke detection is required not less than one foot but no more than three feet on the occupied side of each door that enters a refuge area, elevator lobby and exit stairway in building types R-4. True or False
113
True DBA 907.2.13.1 (6)
114
An approved automatic smoke detection system shall be installed in areas containing stationary storage battery systems having a liquid capacity of more than 75 gallons. Where the alarm is installed, provide signage indicating “Battery Room Alarm-Call 911.” True or False
115
False 50 gallons DBA 907.2.23
116
Where practical difficulties are associated with replacement of fire alarm systems in existing high rises two fire alarm control panels shall not be allowed during the phased upgrade. Existing and new fire alarm control panels shall be co located at a location approved by the fire code official. True or False
117
False Two panels are allowed DBA 907.1.6 Exception 2
118
In a nightclub means shall be provided to reduce or eliminate background noise upon activation of the fire alarm system. True or False
119
True DBA 907.6.2.1
120
Annunciator panels shall be point lit graphic or computer graphic or a directory LED point display. True or False
121
True DBA 907.7.3.1
122
In a group I occupancy a manual fire alarm system is allowed. True or False
123
True DBA 907.2.6
124
Buildings with a floor used for human occupancy located more than 50 feet above the lowest level of fire department vehicle access shall be provided with a fire command center. True or False
125
False DBA 907.2.13
126
In a group E occupancy a manual fire alarm system is not required if 20 or less occupants and 120V AC single or multiple station residential smoke alarms with battery back up, wired to a switched source are provided. True or False
127
False Unswitched DBA 907.2.3 Exception 2