2004 Florida Building Code Plumbing / Fuel Gas Version 1.0 / June 2004 – 4 hour version Florida Building Commission Department of Community Affairs, Codes.

Similar presentations


Presentation on theme: "2004 Florida Building Code Plumbing / Fuel Gas Version 1.0 / June 2004 – 4 hour version Florida Building Commission Department of Community Affairs, Codes."— Presentation transcript:

1 2004 Florida Building Code Plumbing / Fuel Gas Version 1.0 / June 2004 – 4 hour version Florida Building Commission Department of Community Affairs, Codes and Standards 2555 Shumard Oak Boulevard Tallahassee, FL (850)

2 CHAPTER 1 ADMINISTRATION No significant changes

3 CHAPTER 1 ADMINISTRATION Refers to Chapter 1 of the Florida Building Code, Building for administration and enforcement of the Florida Building Code, Plumbing.

4 CHAPTER 2 DEFINITIONS New or modified definitions

5 CHAPTER 2 DEFINITIONS AIR BREAK (Drainage System). A piping arrangement in which a drain from a fixture, appliance or device discharges indirectly into another fixture, receptacle or interceptor at a point below the flood level rim and above the trap seal.

6 CHAPTER 2 DEFINITIONS APPROVED AGENCY. An established and recognized agency approved by the code official and that is regularly engaged in conducting tests or furnishing inspection services.

7 CHAPTER 2 DEFINITIONS BALL COCK - now FILL VALVE. A water supply valve, opened or closed by means of a float or similar device, utilized to supply water to a tank. An antisiphon fill valve contains an antisiphon device in the form of an approved air gap or vacuum breaker that is an integral part of the fill valve unit and that is positioned on the discharge side of the water supply control valve.

8 CHAPTER 2 DEFINITIONS BUILDING DRAIN. That part of the lowest piping of a drainage system that receives the discharge from soil, waste and other drainage pipes inside and that extends 30 inches (762 mm) in developed length of pipe beyond the walls of the building and conveys the drainage to the building sewer. Combined. A building drain that conveys both sewage and storm water or other drainage. Sanitary. A building drain that conveys sewage only. Storm. A building drain that conveys storm water or other drainage, but not sewage.

9 CHAPTER 2 DEFINITIONS DRAINAGE SYSTEM. Storm. A drainage system that carries rainwater, surface water, and similar liquid wastes. (deletes condensate and cooling water from definition)

10 CHAPTER 2 DEFINITIONS GREASE INTERCEPTOR. An interceptor whose rated flow exceeds 50 gpm or has a minimum storage capacity of 750 gallons or more and is located outside the building.

11 CHAPTER 2 DEFINITIONS GREASE-LADEN WASTE. Effluent discharge that is produced from food processing, food preparation or other sources where grease, fats and oils enter automatic dishwasher prerinse stations, sinks or other appurtenances.

12 CHAPTER 2 DEFINITIONS GREASE TRAP. An interceptor whose rated flow is 50 gpm or less and is located inside the building.

13 CHAPTER 2 DEFINITIONS HOT WATER. Water at a temperature greater than or equal to 110º F (43º C).

14 CHAPTER 2 DEFINITIONS MACERATING TOILET SYSTEMS. An assembly consisting of a water closet and sump with a macerating pump that is designed to collect, grind and pump wastes from the water closet and up to two other fixtures connected to the sump.

15 CHAPTER 2 DEFINITIONS TEMPERED WATER. Water having a temperature range between 85º F (29º C) and 110º F (43º C).

16 CHAPTER 2 DEFINITIONS SEWER. Storm sewer. A sewer that conveys rainwater, surface water, subsurface water and similar liquid wastes. Deletes condensate and cooling water from definition and adds subsurface water

17 CHAPTER 2 DEFINITIONS THIRD-PARTY CERTIFICATION AGENCY. An approved agency operating a product or material certification system that incorporates initial product testing, assessment and surveillance of a manufacturer's quality control system.

18 CHAPTER 2 DEFINITIONS THIRD-PARTY CERTIFIED. Certification obtained by the manufacturer indicating that the function and performance characteristics of a product or material have been determined by testing and ongoing surveillance by an approved third-party certification agency. Assertion of certification is in the form of identification in accordance with the requirements of the third-party certification agency.

19 CHAPTER 2 DEFINITIONS THIRD-PARTY TESTED. Procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified requirements.

20 CHAPTER 3 GENERAL REGULATIONS Significant changes

21 CHAPTER 3 GENERAL REGULATIONS SECTION 301 GENERAL Added code conflict language that basically says that if the code requires something less stringent than the manufacturer's instructions, etc., the conditions of the listing and manufacturer's installation instructions shall apply.

22 CHAPTER 3 GENERAL REGULATIONS SECTION 303 MATERIALS Third-party testing and certification. All plumbing products and materials have to comply with the referenced standards. Alternative materials, design and methods of construction and equipment may be allowed (Section of Florida Building Code, Building)

23 CHAPTER 3 GENERAL REGULATIONS Table lists products and materials requiring third-parting testing and third-party certification.

24 TABLE PRODUCTS AND MATERIALS REQUIRING THIRD-PARTY TESTING AND THIRD-PARTY CERTIFICATION PRODUCT OR MATERIAL THIRD-PARTY CERTIFIED THIRD-PARTY TESTED Backflow prevention devicesRequired Plumbing appliancesRequired Plumbing fixtures Required Portable water supply systems components and potable water fixture fittings Required Sanitary drainage and vent system components Plastic pipe, fittings and pipe-related components All others Special waste system components Required Storm drainage system components Plastic pipe, fittings and pipe-related components All others Subsoil drainage system components Required Waste fixture settings Plastic pipe, fittings and pipe-related components All others Water distribution system safety devicesRequired

25 CHAPTER 3 GENERAL REGULATIONS SECTION 305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS Corrosion. Added Exception: Sleeving is not required for installation of CPVC into concrete or similar material.

26 CHAPTER 3 GENERAL REGULATIONS SECTION 305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS Freezing. Freeze protection is required where design temperature is less than 32º F.

27 CHAPTER 3 GENERAL REGULATIONS SECTION 307 STRUCTURAL SAFETY Added alteration to trusses: [B] Alteration to trusses. No alteration to truss members and components without written concurrence and approval of a registered design professional.

28 CHAPTER 3 GENERAL REGULATIONS SECTION 307 STRUCTURAL SAFETY Piping materials exposed within plenums. Piping materials exposed in plenums must comply with Florida Building Code, Mechanical

29 CHAPTER 3 GENERAL REGULATIONS SECTION 309 FLOOD HAZARD RESISTANCE Added requirements for piping in flood hazard areas.

30 CHAPTER 3 GENERAL REGULATIONS SECTION 312 TESTS AND INSPECTIONS Test gauges. Added requirements for test gauges.

31 CHAPTER 3 GENERAL REGULATIONS SECTION 314 CONDENSATE DISPOSAL Added requirements for condensate disposal—identical to Florida Building Code, Mechanical Section 307 (Condensate Disposal)

32 CHAPTER 3 GENERAL REGULATIONS SECTION 316 IRRIGATION Added to this section: General. Irrigation/sprinkler systems and risers for spray heads shall not be installed within 1 foot (305 mm) of the building sidewall.

33 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS Significant changes

34 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS New look to TABLE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES

35 TABLE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES No.Classification Use Group Description Water Closets Lavatories Bathtubs/ Showers Drinking Fountain Other 2BusinessBBuildings for the transaction of business, professional … 1 per 25 for the first 50 and 1 per 50… 1 per 40 for the first 50 and 1 per 80 for the… —1 per service sink 6Mercantile (f g) MRetail stores, service stations, shops… 1 per per 750 —1 per 1,000 (RESERVED) (Entire table not listed)

36 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 403 MINIMUM PLUMBING FACILITIES Exception: The location and maximum travel distances to required employee toilet facilities in factory and industrial occupancies are permitted to exceed that required in Section , provided the location and maximum travel distance are approved by the code official.

37 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 403 MINIMUM PLUMBING FACILITIES Location of employee toilet facilities in mercantile and assembly occupancies. 300 foot maximum to toilet facilities in covered malls; 500 feet in other than covered malls Change from 500 feet to 300 feet maximum travel distance to central toilet facilities for tenant spaces

38 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 403 MINIMUM PLUMBING FACILITIES Unisex toilet & bathing rooms. Fixtures located within unisex toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.

39 Table P403.8 Public Swimming Pool Fixtures Required Size Men’s RestroomsWomen’s Restrooms UrinalsWCLavatoryWCLavatory 0 – 2500 sq ft – 5000 sq ft – 7500 sq ft – 10,000 sq ft

40 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 406 AUTOMATIC CLOTHES WASHERS Requires a minimum 2” diameter trap and fixture drain for standpipe Requires that the fixture drain connect to a minimum 3” in diameter branch drain or drainage stack

41 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 410 DRINKING FOUNTAINS Approval. Bottled water dispensers permitted to substitute for not more than 50% of the required drinking fountains

42 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 417 SHOWERS Shower waste outlet. Shower drain waste outlet reduced from 2 inches to 1-1/2 inches

43 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 417 SHOWERS Shower lining. Added requirement to slope shower liners: Liners shall be pitched one-fourth unit vertical in 12 units horizontal (2-percent slope) toward the fixture drains.

44 CHAPTER 4 FIXTURES, FAUCETS & FIXTURE FITTINGS SECTION 424 FAUCETS & OTHER FIXTURE FITTINGS Shower valves. Master thermostatic mixing valves must comply with ASSE 1017.

45 CHAPTER 5 WATER HEATERS Significant changes

46 CHAPTER 5 WATER HEATERS SECTION 502 INSTALLATION Water heaters installed in garages. Water heaters shall be installed in accordance with the manufacturer's installation instructions, which shall be available on the job site at the time of inspection.

47 CHAPTER 5 WATER HEATERS SECTION 504 SAFETY DEVICES Discharge Relief valve allowed to discharge to water heater pan.

48 CHAPTER 5 WATER HEATERS SECTION 504 SAFETY DEVICES Required pan Pan size and drain Need to place water heaters in a pan if installed: Above the ground floor space In attic or ceiling areas, or Within the habitable space

49 CHAPTER 6 WATER SUPPLY & DISTRIBUTION Significant changes

50 CHAPTER 6 WATER SUPPLY & DISTRIBUTION SECTION 603 WATER SERVICE Separation of water service and building sewer. Allows water service pipe to be in same trench with building sewer (if using materials listed in Table 702.2) Required separation distance doesn't apply provided the water service pipe is sleeved to at least 5 feet (using materials listed in Tables 605.3, or 702.3).

51 CHAPTER 6 WATER SUPPLY & DISTRIBUTION SECTION 605 MATERIALS, JOINTS & CONNECTIONS Deleted water compatibility section, which stated that water service pipe and distribution pipe shall be resistant to corrosive and degrading action from the potable water supplied by the water purveyor or individual water supply system.

52 Table Pipe Fittings MaterialStandard Acrylonitrile butadiene styrene (ABS) plastic ASTM D 2468 Cast IronASME B 16.4; ASME B16.12 Chlorinated polyvinyl chloride (CPVC) plastic ASTM F 437; ASTM F 438; ASTM F 439 Copper or copper alloy ASME B 16.15; ASME B 16.18; ASME B 16.22; ASME B 16.23; ASME B 16.26; ASME B 16.29; ASME B Gray iron and ductile ironAWWA C110; AWWA C153 Malleable ironASME B 16.3

53 Table Pipe Fittings (cont’d) MaterialStandard Metal (brass) insert fittings utilizing a copper crimp ring CDR9 (PEX) tubing for Polyethylene/Aluminum/Polyethylene (PE- AL-PE) and Cross-linked Polyethylene/ Aluminum/Polyethylene (PEX-AL-PEX) ASTM F 1974 ASTM F 1807 Polyethylene (PE) plasticASTM D 2609 Polyvinyl chloride (PVC) plastic ASTM D 2464; ASTM D 2466; ASTM D 2467; CSA-B Stainless steel (Type 304/304L)ASTM A 312; ASTM A 778 Stainless steel (Type 316/316L)ASTM A 312; ASTM A 778 Steel ASME B 16.9; ASME B 16.11; ASME B 16.28

54 CHAPTER 6 WATER SUPPLY & DISTRIBUTION SECTION 610 DISINFECTION OF POTABLE WATER SYSTEM General. New or repaired potable water systems shall be purged of deleterious matter and, where required by the Administrative Authority, disinfected prior to utilization.

55 CHAPTER 7 SANITARY DRAINAGE Significant changes

56 CHAPTER 7 SANITARY DRAINAGE SECTION 701 GENERAL Drainage piping in food service areas. Prohibits exposed drainage piping above working, storage or eating surfaces in food service establishments.

57 CHAPTER 7 SANITARY DRAINAGE SECTION 708 CLEANOUTS Building sewers. For building sewers 12 inches and larger, manholes shall be provided and located not more than 200 feet from the junction of the building drain and building sewer…

58 Table Drainage Fixture Units for Fixtures and Groups Fixture Type Drainage Fixture Unit Value as Load Factors Minimum Size of Trap (inches) Automatic clothes washers, commercial a g 32 Automatic clothes washers, residential g 22 Bathroom group (with 3.5 gpf water closet) consisting of water closet, lavatory, bidet and bathtub or shower 6— Bathroom group as defined in Section 202 (1.6 gpf water closet) f 5— Bathroom group as defined in Section 202 (water closet flushing greater than 1.6 gpf) f 6—

59 Table Drainage Fixture Units (cont’d) Fixture Type Drainage Fixture Unit Value as Load Factors Minimum Size of Trap (inches) Bathroom group (with 1.6 gpf flushometer tank with water closet) 5.5 — Bathtub b (with or without overhead shower or whirlpool attachments) 21½ Bidet1 21¼ Combination sink and tray21½ Dental lavatory11¼ Dental unit or cuspidor11¼ Dishwashing machine c, domestic21½ Drinking fountain½1¼ Emergency floor drain02

60 Table Drainage Fixture Units (cont’d) Fixture Type Drainage Fixture Unit Value as Load Factors Minimum Size of Trap (inches) Floor drains22 Kitchen sink, domestic21½ Kitchen sink, domestic with food waste grinder and/or dishwasher 21½ Laundry tray (1 or 2 compartments)21½ Lavatory11¼ Shower compartment, domestic21½ 2 Sink21½ Urinal4FootnNote d Urinal, 1 gallon per flush or less2 e FootnNote d

61 Table Drainage Fixture Units (cont’d) Fixture Type Drainage Fixture Unit Value as Load Factors Minimum Size of Trap (inches) Wash sink (circular or multiple) each set of faucets 21½ Water closet, flushometer tank, public or private 4 e FootnNote d Water closet, private installation4Footnote d Water closet, public installation6Footnote d Water closet, private (1.6 gpf), private installation 3 e FootnNote d Water closet, private (3.5 gpf), private installation (flushing greater than 1.6 gpf) 4 e FootnNote d Water closet (1.6 gpf), flushometer tank, private installation 3.5Footnote d

62 Table Drainage Fixture Units (cont’d) Fixture Type Drainage Fixture Unit Value as Load Factors Minimum Size of Trap (inches) Water closet, public (1.6 gpf) public installation 4 e FootnNote d Water closet, public (3.5 gpf), public installation (flushing greater than 1.6 gpf) 6 e FootnNote d Notes: f.For fixtures added to a dwelling unit bathroom group, add the DFU value of those additional fixtures to the bathroom group fixture count. g.See Section for sizing requirements for fixture drain, branch drain, and drainage stack for an automatic clothes washer standpipe.

63 CHAPTER 7 SANITARY DRAINAGE SECTION 710 DRAINAGE SYSTEM SIZING Underground drainage piping. This section was in the 2001 FBC, P and has been deleted thereby removing the requirement for minimum 2-inch drains underground

64 CHAPTER 8 INDIRECT / SPECIAL WASTE No significant changes

65 CHAPTER 9 VENTS Significant changes

66 CHAPTER 9 VENTS SECTION 909 WET VENTING Vertical wet vent. Includes language for vertical wet vents Shall extend from the connection to the dry vent down to the lowest fixture drain connection Each fixture shall connect independently Water closet drains shall connect at the same elevation with other fixture drains connecting above or at same elevation as WC drains Dry vent connection to vertical wet vent shall be an individual or common vent serving one or two fixtures

67 CHAPTER 9 VENTS SECTION 912 COMBINATION DRAIN & VENT SYSTEM Type of fixtures. No food waste grinders, clinical sinks or standpipes permitted on combination drain and vent systems.

68 CHAPTER 10 TRAPS, INTERCEPTORS & SEPARATORS Significant changes

69 CHAPTER 10 TRAPS, INTERCEPTORS & SEPARATORS SECTION 1002 TRAP REQUIREMENTS Trap seals. Floor drains subject to evaporation must have trap seal primer valve (eliminates deep-seal trap option)

70 CHAPTER 10 TRAPS, INTERCEPTORS & SEPARATORS SECTION 1003 INTERCEPTORS AND SEPARATORS Adds requirement for a solids interceptor to separate the discharge before connecting to the grease trap Adds ASME A or ASME A to grease trap standards

71 CHAPTER 10 TRAPS, INTERCEPTORS & SEPARATORS SECTION 1003 INTERCEPTORS AND SEPARATORS Grease interceptors. Maximum volume for grease interceptors is 1250 gallons. Interceptors shall be constructed in accordance with Rule 64E-6, Florida Administrative Code. Inlet piping shall connect to a tee sweep or baffle that extends 24 inches below the water level.

72 CHAPTER 11 STORM DRAINAGE No significant changes

73 CHAPTER 11 STORM DRAINAGE SECTION 1106 SIZE OF CONDUCTORS, LEADERS AND STORM DRAINS Scupper sizing. Scuppers shall be sized in accordance with Table

74 Table Sizing Scuppers for a 5” Per Hour Rate of Rainfall Head in inches Horizontally Projected Roof Area (square feet) Length of Weir in inches

75 CHAPTER 12 FUEL PIPING Changes Chapter 12 (Fuel Piping) of 2001 Florida Building Code, Plumbing is deleted from 2004 Florida Building Code, Plumbing.

76 CHAPTER 12 SPECIAL PIPING & STORAGE SYSTEMS Chapter 12 is now Special Piping and Storage Systems No significant changes

77 CHAPTER 13 REFERENCED STANDARDS Changes – contains an updated listing This chapter lists the standards that are referenced in various sections of the 2004 Florida Building Code, Plumbing.

78 Plumbing-Related Chapters 2004 Florida Building Code, Residential

79 Chapter 25: Plumbing Administration Chapter 26 General Plumbing Requirements Chapter 27 Plumbing Fixtures Chapter 28 Water Heaters Chapter 29 Water Supply and Distribution Chapter 30 Sanitary Drainage Chapter 31 Vents Chapter 32 Traps Chapter 41 Swimming Pools Chapters specifically dealing with plumbing:

80 CHAPTER 25 PLUMBING ADMINISTRATION P Gravity sewer test. (same as Florida Building Code, Plumbing 312.6) P Drainage and vent water test. (same as Florida Building Code, Plumbing 312.2)

81 CHAPTER 26 GENERAL PLUMBING REQUIREMENTS P Floodplain management construction standards. Defers authority granted to local government by Title 44 CFR, sections 59 and 60. Local floodplain management ordinances are not amendments to the code.

82 CHAPTER 27 PLUMBING FIXTURES Significant changes

83 CHAPTER 27 PLUMBING FIXTURES SECTION P2709 SHOWER RECEPTORS P Lining required. Lining material shall extend not less than 3 inches beyond or around the rough jambs and not less than 3 inches above finished thresholds.

84 CHAPTER 29 WATER SUPPLY & DISTRIBUTION Significant changes

85 CHAPTER 29 WATER SUPPLY & DISTRIBUTION SECTION 2904 MATERIALS, JOINTS & CONNECTIONS P Under concrete slabs. PE-AL-PE not permitted under concrete slabs

86 CHAPTER 29 WATER SUPPLY & DISTRIBUTION No limit on hot water distances like in 2004 Florida Building Code, Plumbing which includes: The hot water system shall be provided with a method of maintaining the temperature if the developed length of hot water piping from the source of hot water supply to the farthest fixture exceeds 100 feet

87 CHAPTER 30 SANITARY DRAINAGE Significant changes

88 CHAPTER 30 SANITARY DRAINAGE SECTION P3005 DRAINAGE SYSTEM P Base of stacks. Allows cleanouts to be installed outside the building within 3 feet of the building wall.

89 CHAPTER 30 SANITARY DRAINAGE SECTION P3005 DRAINAGE SYSTEM P Building drains and building sewer junction. Does not require 3" WM vertical stacks

90 CHAPTER 31 VENTS Significant changes

91 CHAPTER 31 VENTS SECTION 3105 FIXTURE VENTS P Distance of trap from vent. No limit on WC trap-to-vent distance

92 Table Maximum Distance of Fixture Trap from Vent Size of Trap (inches) Size of Fixture Drain (inches) Slope (inch per foot) Distance from Trap (feet) 1¼ ¼3½ 1¼1½¼5 ¼5 2¼6 8 22¼ / /816 12

93 CHAPTER 32 TRAPS No changes necessary

94 CHAPTER 41 PRIVATE SWIMMING POOLS Significant changes

95 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Conformance Standard. Design, construction and workmanship shall be in conformity with the requirements of ANSI/NSPI 3-99; ANSI/NSPI 4-99; ANSI/NSPI 5-03; and ANSI/NSPI 6-92.

96 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Engineering design. R Water velocity. Pool piping shall be designed so the water velocity will not exceed 10 ft/s for pressure piping and 8 ft/s for suction piping, except that the water velocity shall not exceed 8 ft/s in copper tubing.

97 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Engineering design. R Piping installation. All piping materials shall be installed in strict accordance with the manufacturer's installation standards. Exception: Primer and glue on exposed aboveground piping not required to be colored.

98 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Pumps. R Installation. Pumps shall be installed in accordance with manufacturer recommendations.

99 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Valves. R Check valves. Where check valves are installed they shall be of the swing, spring or vertical check patterns.

100 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Pressure test. Removed requirement that all pool piping be inspected and approved before being covered or concealed.

101 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Pool fittings. R Skimmers. …skimmers shall be installed on the basis of one per 800 sq ft of surface area or fraction thereof, and shall be designed for a flow rate of at least 25 gpm per skimmer.

102 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Pool fittings. R Inlet fittings. Approved manufactured inlet fittings for the return of recirculated pool water shall be provided on the basis of at least one per 300 sq ft of surface area…

103 CHAPTER 41 SWIMMING POOLS SECTION R4101 PRIVATE SWIMMING POOLS R Equipment foundations and enclosures. All mechanical equipment shall be installed as per manufacturer's recommendations…

104 2004 Florida Building Code, Fuel Gas Significant changes

105 Florida Building Code, Fuel Gas CHAPTER 3 GENERAL REGULATIONS Section 301 (IFGC) General Fuel types. Allows serving gas supplier to convert gas equipment to a different gas.

106 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 301 (IFGC) General Wind resistance. Fuel gas appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the Florida Building Code, Mechanical.

107 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air General. Requirements for air for combustion, ventilation and dilution of flue gases for gas utilization equipment installed in buildings (refer to sections – or – 304.9) Direct-vent appliances, gas appliances of other than natural draft design, etc. shall be in accordance with equipment manufacturer’s instructions

108 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Indoor combustion air. Use or unless ACH is less than 0.40; then use to determine required volume of indoor air.

109 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Indoor opening size and location. Use and to size and locate openings used to connect indoor spaces.

110 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Outdoor combustion air. Outdoor combustion air shall be provided through opening(s) to the outdoors in accordance with Section or The minimum dimension of air openings shall be not less than 3 inches (76 mm).

111 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Combination indoor and outdoor combustion air. Use through when using a combination of indoor and outdoor combustion air.

112 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Mechanical combustion air supply. Where all combustion air is provided by a mechanical air supply system..the combustion air shall be supplied at a rate not less than 0.35 cu ft/min per 1000 Btu/h of total input rating of all appliances in the space.

113 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Louvers and grilles. Added screens; assume wood louvers will have 25% free area and metal louvers and grilles will have 75% free area; screens shall have a mesh size no smaller than ¼ inch; means have to be provided to prevent main burner from igniting if the louvers fail to open during burner start-up and to shut down the main burner if the louvers close during operation.

114 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Combustion air ducts. Numbers 6–8 have been added.

115 Florida Building Code, Fuel Gas Chapter 3, General Regulations Section 304 (IFGS) Combustion, Ventilation and Dilution Air Protection from fumes and gases. Refers to disposal of corrosive or flammable process fumes or gases—other than products of combustion.

116 Florida Building Code, Fuel Gas Chapter 3 General Regulations Section 305 (IFGC) Installation Where a code provision is less restrictive, the conditions of the listing and the manufacturer’s installation instructions shall apply.

117 Florida Building Code, Fuel Gas Chapter 4 Gas Piping Installations Section 402 (IFGS) Maximum gas demand Where an input rating is not indicated, the gas supplier, equipment manufacturer or a qualified agency are contacted…or the rating from Table shall be used for estimating the volume of gas to be supplied.

118 Table Approximate Gas Input for Typical Appliances Appliance Input BTU/H (Approx.) Space Heating Units Hydronic boiler Single family Multifamily, per unit Warm-air furnace Single family Multifamily, per unit 100,000 60, ,000 60,000 Space and Water Heating Units Hydronic boiler Single family Multifamily, per unit 120,000 75,000

119 Table Approximate Gas Input for Typical Appliances (cont'd) Appliance Input BTU/H (Approx.) Water Heating Appliances Water heater, automatic instantaneous Capacity at 2 gal/minute Capacity at 4 gal/minute Capacity at 6 gal/minute Water heater, automatic storage, 30- to 40-gal. tank Water heater, automatic storage, 50-gal. tank Water heater, domestic, circulating or side-arm 142, , ,400 35,000 50,000 35,000

120 Table Approximate Gas Input for Typical Appliances (cont'd) Appliance Input BTU/H (Approx.) Cooking Appliances Built-in oven or broiler unit, domestic Built-in top unit, domestic Range, free-standing, domestic 25,000 40,000 65,000 Other Appliances Barbecue Clothes dryer, Type 1 (domestic) Gas fireplace, direct vent Gas light Gas log Refrigerator 40,000 35,000 40,000 2,500 80,000 3,000

121 Florida Building Code, Fuel Gas Chapter 4 Gas Piping Installations Section 404 (IFGC) Piping System Installation Above-ground outdoor piping. All outdoor piping shall be elevated not less than 3-1/2 inches above ground and, where installed across roof surfaces, shall be elevated not less than 3-1/2 inches above the roof surface.

122 Florida Building Code, Fuel Gas Chapter 4 Gas Piping Installations Section 409 (IFGC) Shutoff Valves Equipment shutoff valve. Shutoff valves for vented decorative appliances and decorative appliances can be placed in remote areas Shutoff valve in fireplace. Equipment shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions.

123 Florida Building Code, Fuel Gas Chapter 4 Gas Piping Installations Section 411 (IFGC) Appliance Connections Outdoor appliance connectors. This section provides installation requirements for installing outdoor gas appliances and is consistent with the National Fuel Gas Code. Note that lengths shall not exceed 12 feet (3658 mm) and the connection shall only be made in the outdoor area where the equipment is to be used.

124 Florida Building Code, Fuel Gas IFGC/IFGS Chapter 8 Referenced Standards Updated reference standards

125 Florida Building Code, Residential Chapter 24 Fuel Gas Note that the Florida Building Code, Residential does not contain the same degree of detail as the Florida Building Code, Fuel Gas.


Download ppt "2004 Florida Building Code Plumbing / Fuel Gas Version 1.0 / June 2004 – 4 hour version Florida Building Commission Department of Community Affairs, Codes."