1 Slide 1 HVAC Systems AP1000 Chilled Water System

2 Slide 2 Central Chilled Water System VWS Design Basis –Containment Isolation: Safety-related, seismic, ASME III, 1E –Provides 40°F chilled water –VWS air-cooled chillers shall be designed for operation using outdoor air with a maximum summer design temperature of 115°F dry bulb / 85.5°F wet bulb and a minimum winter design temperature of -40°F based on 0% exceedance –VWS water-cooled chillers are designed for stable operation using Component Cooling Water System (CCS) water with a temperature range of 60 to 95°F.

3 Slide 3 Central Chilled Water System Sketch – High Capacity Subsystem

4 Slide 4 Central Chilled Water System Sketch – Low Capacity Subsystem

5 Slide 5 Containment Recirculation System

6 Slide 6 Containment Recirculation System Ductwork and Fan Coil Units

7 Slide 7 HVAC Systems – Containment Filtration

8 Slide 8 Radiologically Controlled Area Ventilation System Fuel Handling Area Subsystem

9 Slide 9 Radiologically Controlled Area Ventilation System (VAS) Aux/Annex Building Subsystem