Spyder Re-flash 2.0 How-To

Similar presentations


Presentation on theme: "Spyder Re-flash 2.0 How-To"— Presentation transcript:

1 Spyder Re-flash 2.0 How-To

2 What’s New In Re-Flash Tool 2.0?
Updated user interface Removed some extraneous information columns in the discovery window All relevant destination firmware descriptions are filtered and viewable without the need to navigate to the correct folder Updated firmware images Communication issue fixed in all Spyder Lon and full sized BACnet Some sites have reported Spyders “falling off the network” for a period of time The new firmware does NOT affect compatibility, so all options in the new re-flash tool include this fix Firmware upgrade image created for full sized BACnet version 6.20 It was previously not possible to upgrade this version of Spyder BACnet

3 Re-Flash Tool Remember that Re-flashing for compatibility purposes can be avoided by installing the latest Spyder Tool The only exception is if you have an older (pre-1220 date code) Spyder and desire new features like compatibility with TR71/75; then you MUST flash forward AND use the new tool to gain those new features Download the Re-flash tool from the Forum Uninstall any previous version of Re-flash tool before installing 2.0 Run the executable and the re-flash program plus all current re-flash images will be installed Runs on Win XP 32 bit, Win7 32 and 64 bit Re-Flash will erase the control program as well as any bindings or balancing data Perform an upload of that data if it hasn’t previously been done Plan sufficient time to re-download/re-bind all re-flashed devices

4 Re-Flash Tool Here is what the re-flash tool will do
Scan the network to find Spyders on the network Spyder Lon devices are discovered by their Program ID, if that has been modified the user can open the UserDefinitions.ini file in the directory of installation and add the new Program ID to the list Determine the current version of the Spyder firmware Filters the list of firmware images down to the only valid choices for re-flashing the Spyder Allows the user to choose one of those destinations Downloads that firmware image to the Spyder at which point it will be in a factory configured state Program ID’s on Spyder Lon devices will remain unchanged

5 Re-Flash Tool Failure to follow the steps below may result in a Spyder which is not recoverable Ensure that nothing else is running on the PC used for re-flash Ensure power will not be interrupted to the PC, Spyders or the rest of the communication network Ensure that other PC’s are not flashing the same Spyder at the same time Disconnect the JACE from the Spyder’s Lon or BACnet network Tunneling through the JACE to re-flash is not supported

6 Re-Flashing Spyder Lon
Open the tool (after disconnecting the JACE) A splash screen will display briefly Then the setup screen will display Select LON USB to use the Echelon USB Plug (Q7752C2007) Select the Correct USB Plug (ensure AX isn’t running a station and occupying the USB Plug) Select the Node Address of the USB Plug Select the Domain of the network Press Connect once correct choices have been made

7 Re-Flashing Spyder Lon
Discover devices Select “Scan For Devices” and only Spyder devices will appear This device was brand new so no Device Name existed

8 Re-Flashing Spyder Lon
Other Information Press this button to select a new firmware image to download Device Name (Blank if new from factory, deleted after re-flash) Use this button to automatically select all Spyders with identical re-flash versions (useful for batch jobs, limit is 30 devices per batch) Use this button to automatically de-select all devices Lon network information Neuron ID Firmware currently loaded in device Status, OS Number and Brand Select devices to be re-flashed. Only devices of identical hardware can be re-flashed in a single batch job. The flashing tool defaults to finding Lon Spyders with the factory Program ID. If you’ve changed the Program ID of a Lon Spyder within AX, the UserDefinitions.ini file which by default resides in “My Documents” e.g. C:\Users\[UserName]\Documents\ReflashTool2.0 of the re-flash tool must be updated with the Program ID’s of those Spyders or they will not be discovered. See next page for details.

9 Re-Flashing Spyder Lon
Adding a new Program ID to the Device Discovery Not necessary unless you’ve previously altered the Program ID Double click on the UserDefinitions.ini file in C:\Users\[UserName]\Documents\ReflashTool2.0 of the re-flash tool. Copy/Paste the existing Program ID line below and then change the Program ID to match the Spyder’s new Program ID. “My Documents” Location: For Windows XP its C:\Documents and Settings\[UserName]\My Documents\ReflashTool2.0 For Win7/Vista its C:\Users\[UserName]\My Documents\ReflashTool2.0

10 Re-Flashing Spyder Lon
After “Download Firmware to Devices” is pressed Select desired firmware image to download. The list is automatically filtered so only valid selections can be chosen Any option you choose will include the latest firmware fixes, even if you’re flashing back Select “Start Downloads” to begin. If a download is cancelled, the tool will complete downloading the current device and cancel the re-flash of any remaining units

11 Re-Flashing Spyder Lon
Start the download Re-flash will take about 13 minutes per device Status window will pop up and show job activity Time Remaining is based on previous re-flashes once a re-flash has been completed A Cancel will stop re-flash operations AFTER the current device has been re-flashed

12 Re-Flashing Spyder Lon
Job Complete Pre Re-Flash Post Re-Flash Firmware updated

13 Re-Flashing Spyder BACnet
Ensure your BACnet Router is setup properly Example for Contemporary Controls router shown below Set the IPv4 properties of your network card to use Open a web browser and type in the address bar Selecting a higher MS/TP Baudrate will speed up the flashing process but add risk if there are already devices talking on the network

14 Re-Flashing Spyder BACnet
Open the tool (after disconnecting the JACE) A splash screen will display briefly Then the setup screen will display Select BACNET IP to use a BACnet router like the Contemporary Controls router Select Lowest/Highest device ID’s to search for (may speed up discovery of devices) Select number of retries for discovering devices Select the Ethernet adapter connected to the router (in this case, the local LAN connection on your PC) Select the UDP Port (must match UDP port on router). Ensure UDP port not in use by other tools like Niagara Press Connect once correct choices have been made

15 Re-Flashing Spyder BACnet
Discover devices Select Scan For Devices and only Spyder devices will show up

16 Re-Flashing Spyder BACnet
Other Information Press this button to select a new firmware image to download (must first select a device) Use this button to automatically select all Spyders with identical Re-flash versions (useful for batch jobs, limit is 30 devices per batch) Use this button to automatically de-select all devices Device Name (Blank if new from factory, deleted after re-flash) BACnet Device ID BACnet network information Status, OS Number and Brand Firmware image currently loaded in device Select devices to be re-flashed. Only devices of identical re-flash version can be re-flashed in a single batch job.

17 Re-Flashing Spyder BACnet
After “Download Firmware to Devices” is pressed Select desired firmware image to download. The list is automatically filtered so only valid selections can be chosen Any option you choose will include the latest firmware fixes, even if you’re flashing back Select “Start Downloads” to begin. If a download is cancelled, the tool will complete downloading the current device and cancel the re-flash of any remaining units

18 Re-Flashing Spyder BACnet
Start the download Re-flash will take about 3 minutes per device Status window will pop up and show job activity Time Remaining is based on previous re-flashes once a re-flash has been completed A Cancel will stop re-flash operations AFTER the current device has been re-flashed

19 Re-Flashing Spyder BACnet
Job Complete Pre Re-Flash Post Re-Flash Firmware updated

20 If You Encounter Problems
Gather this information before starting a case From the Help  About Reflash Tool screen Reflash Tool version Reflash Definition File version From the Download Firmware screen Firmware Definition version From the main screen OS number, brand and firmware of the device in question Approximate date/time of the problem (local from the PC) Gather the following files from C:\Users\[TheUser]\Documents\ReflashTool2.0 directory <projectName>.search.log.txt <projectName>.summary.log.txt <projectName>.transfer.log.txt