Presentation is loading. Please wait.

Presentation is loading. Please wait.

1 SYMMETRICAL COMPONENETS OF POWER SYSTEM SYMMETRICAL COMPONENETS OF POWER SYSTEM.

Similar presentations


Presentation on theme: "1 SYMMETRICAL COMPONENETS OF POWER SYSTEM SYMMETRICAL COMPONENETS OF POWER SYSTEM."— Presentation transcript:

1 1 SYMMETRICAL COMPONENETS OF POWER SYSTEM SYMMETRICAL COMPONENETS OF POWER SYSTEM

2 2 OUTLINE OF THE PRESENTATION INTRODUCTION INTRODUCTION NEED FOR THE SYMMETRICAL COMPONENET METHOD NEED FOR THE SYMMETRICAL COMPONENET METHOD TECHINQUES USED TO ANALYSIS SYMMETRICAL TECHINQUES USED TO ANALYSIS SYMMETRICAL SYMMETRICAL METHODS USED TO STUDY POWER SYSTEM FAULTS SYMMETRICAL METHODS USED TO STUDY POWER SYSTEM FAULTS CONCLUSION CONCLUSION REFERENCES REFERENCES

3 3 INTRODUCTION The normal operating conditions of an electric power system are occasionally disrupted because of faults. The normal operating conditions of an electric power system are occasionally disrupted because of faults. Analysis of power systems usually implies the computation of network voltages and currents under a given set of conditions. Analysis of power systems usually implies the computation of network voltages and currents under a given set of conditions. Under many circumstances we tend to ignore the unbalanced operation in the system and unbalanced operation is always present. Under many circumstances we tend to ignore the unbalanced operation in the system and unbalanced operation is always present.

4 4 An organization of power system analysis problem Source (Reference #1) Source (Reference #1)

5 5 Effects of faults on power system Flow of excessive current Flow of excessive current Abnormal voltages Abnormal voltages Voltage elevation of system neutral Voltage elevation of system neutral Induce over voltages on neighbouring equipments. Induce over voltages on neighbouring equipments. Hazards to human, equipment and animals. Hazards to human, equipment and animals.

6 6 Need for fault analysis Design of protection system requires the knowledge of fault current. Design of protection system requires the knowledge of fault current. The information obtained from the fault studies are used: The information obtained from the fault studies are used: to select the sizes of circuit breaker, to select the sizes of circuit breaker, fuse and characteristic, fuse and characteristic, setting of relay. setting of relay.

7 7 Normal types of fault are: Fault due to lightning Fault due to lightning Tree limbs falling on the line Tree limbs falling on the line Wind damage Wind damage Insulation deterioration Insulation deterioration Vandalism Vandalism

8 8 Types of fault Symmetrical fault : Symmetrical fault : Usually three phase to ground fault Usually three phase to ground fault Unsymmetrical fault Unsymmetrical fault The fault is unbalanced in nature The fault is unbalanced in nature

9 9 Sources of Asymmetrical fault are: (Reference#2)

10 10 Sources of Asymmetrical fault are (cont.) One phase open circuit One phase open circuit Unbalanced in load mainly the arc loads Unbalanced in load mainly the arc loads

11 11 Sources of Asymmetrical fault are (cont.) One phase open circuit One phase open circuit

12 12 Sources of Asymmetrical fault are (cont.) SLG fault SLG fault

13 13 Need for the symmetrical component analysis Negative sequence relay in generator has helped in protecting the generator from over heating in the event of unbalanced loads. Negative sequence relay in generator has helped in protecting the generator from over heating in the event of unbalanced loads. The positive sequence segregating network is used to supply the sensing voltage to generator voltage regulators The positive sequence segregating network is used to supply the sensing voltage to generator voltage regulators Certain connections of CT and PT develop zero sequence components that are used in protective ground relaying scheme. Certain connections of CT and PT develop zero sequence components that are used in protective ground relaying scheme.

14 14 Method of adopted for symmetrical component analysis (cont) Mathematically: Mathematically: V a = V a1+ V a2+ V a V an V a = V a1+ V a2+ V a V an V b = V b1+ V b2+ V b V bn V b = V b1+ V b2+ V b V bn ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;; V n = V n1+ V n2+ V n V nn V n = V n1+ V n2+ V n V nn Where: Where: V a, V b……. V n are unbalanced set of phosors V a, V b……. V n are unbalanced set of phosors V a1, V b1…… V n1 first set of n balanced phasors with an angle 2pi/n V a1, V b1…… V n1 first set of n balanced phasors with an angle 2pi/n between components a,b,…..n between components a,b,…..n

15 15 Method of adopted for symmetrical component analysis (cont) Mathematically: Mathematically: V a2, V b2…… V n2 second set of n balanced phasors with an angle 4pi/n between components a, b………,…..n V a2, V b2…… V n2 second set of n balanced phasors with an angle 4pi/n between components a, b………,…..n ………………………………………………………. ………………………………………………………. V a(n-1), V b(n-1)…… V n(n-1)are (n-1)th set of n balanced phasors with an angle 2pi(n-1)/n between components a, b………,…..n V a(n-1), V b(n-1)…… V n(n-1)are (n-1)th set of n balanced phasors with an angle 2pi(n-1)/n between components a, b………,…..n

16 16 Phasor a or a-operator The phasor notation of a-operator The phasor notation of a-operator

17 17 Phasor a or a-operator

18 18 Phasor a or a-operator

19 19 Equation in matrix form

20 20 Symmetrical components for three Phase system The n-phase system presented above is of academic interest only and only the practical three phase system will be emphasised. The n-phase system presented above is of academic interest only and only the practical three phase system will be emphasised. Power is generated, transmitted and consumed mostly in three phase only. Power is generated, transmitted and consumed mostly in three phase only.

21 21 Symmetrical components for three Phase system (cont) The phasor representation of three phase system (source reference#2) The phasor representation of three phase system (source reference#2)

22 22 Symmetrical components for three Phase system (cont) The positive sequence set consisting of three components of equal magnitude, displaced by 120 & 240 o respectively and having the phase sequence of abca. The positive sequence set consisting of three components of equal magnitude, displaced by 120 & 240 o respectively and having the phase sequence of abca. The negative sequence set consisting of three components of equal magnitude displaced by 240 & 120 o respectively, having phase sequence of acba. The negative sequence set consisting of three components of equal magnitude displaced by 240 & 120 o respectively, having phase sequence of acba. The zero sequence set of the component of which being equal both in magnitude and and phase. The zero sequence set of the component of which being equal both in magnitude and and phase.

23 23 Symmetrical components for three Phase system (cont) Relations of voltage components in matrix form

24 24 Symmetrical components of generator

25 25 Symmetrical components of generator

26 26 Symmetrical components of transformer (zero)

27 27 Fault analysis using symmetrical components The most common type of fault is the single line to ground fault:

28 28 Fault analysis using symmetrical components (cont) The sequence component connection for the single line to ground fault:

29 29 Fault analysis using symmetrical components (cont)  The sequence component connection for the single line to ground fault:  The sequence components are connected in series.  The three currents in the case of SLG fault are equal. 

30 30 Fault analysis using symmetrical components (cont)  LL fault:

31 31 Fault analysis using symmetrical components (cont)  LL fault:  There is no zero sequence component due to absence of ground return path.  The positive and negative sequence components are connected in parallel.

32 32 Fault analysis using symmetrical components (cont)  LLG fault:

33 33 Fault analysis using symmetrical components (cont)  LLG fault:  For the zero sequence component it requires to add an external impedance of Z f +3Z g  The networks are connected in parallel.

34 34 Software available for carrying fault analysis  The most commonly used soft ware are:  MATLAB  EDSA  ETAP  CYME

35 35 Conclusion  Power system analysis using symmetrical component is very helpful in improving the reliability of the power system.  The principle adopted for the analysis of unbalanced fault system is symmetrical component method.  By knowing the principle, the results obtained from the computer can be analysed.

36 36 References: 1. Paul M. Anderson, Analysis of Faulted Power Systems. 2. W.D. Stevenson, Elements of Power System Analysis. 3. A.P.S Meliopoulos, Power System Grounding and Transients. 4. Olle. I. Elgerd, Electric Energy Systems Theory. 5. IEEE Transactions


Download ppt "1 SYMMETRICAL COMPONENETS OF POWER SYSTEM SYMMETRICAL COMPONENETS OF POWER SYSTEM."

Similar presentations


Ads by Google