ACS800 Multidrive Thyristor Supply Unit ACS800多传动 TSU

Similar presentations


Presentation on theme: "ACS800 Multidrive Thyristor Supply Unit ACS800多传动 TSU"— Presentation transcript:

1 ACS800 Multidrive Thyristor Supply Unit ACS800多传动 TSU
Zhang Gang 2005/07/05

2 Common supply modules / TSU
TSU = Thyristor supply unit ( 380 V V ) From 680 kVA upto 3600 kVA ( 6 pulse ) Two antiparallel bridges (4Q) DC Choke for current smoothing Autotransformer for improved line commutation while generating Microprocessor Control Software parameters for good functionality and reliability Independent unit Auxiliary control by I/O or through fieldbus Comissioning by panel and/or DriveWindow Charging of capacitors Internal protections

3 TSU 6-pulse [ B4 / B5 ] / Summary
Air- Circuit- breaker Earthing- Switch (Option) Forward Bridge B4 / B5 Reverse Bridge B4 / B5 F F F K K K K K A A Choke Trafo 400V / 230V

4 TSU B4/B 晶闸管整流单元 AC Thyristor Supply Unit 525 kVA DC B4 - B5 size

5 Main Circuit Diagram Of TSU TSU 主回路
3b V11 V13 V15 V24 V26 V22 3~ U d U c 1 2 V14 V16 V12 4 V21 V23 V25 Forward bridge Reverse bridge Intermediate circuit (DC) reactor

6 Main Circuit Diagram Of TSU TSU 主回路

7 TSU – B1~B3 ACU ICU Drive sections Boards 3b 3a I/O 4 Board

8 TSU – B4/B5 ACU ICU TSU Drive sections 1 2 5 3a 3b Boards I/O Board 4

9 ACS800 多传动TSU 模块装在RITTAL TS8柜体中
TSU module in RITTAL TS8 cabinet ACS800 多传动TSU 模块装在RITTAL TS8柜体中

10 Basic Information 公共供电单元 / TSU基本信息
( 380 V V ) 从 680 kVA 到 3600 kVA ( 6 脉波 ) 两个反并联的桥 (4Q) 直流电抗器,平波作用 自耦变压器用于发电时改善线路换向 微处理器控制 软件参数用于设定复杂功能和提高可靠性 独立的单元 可以通过 I/O 或现场总线控制 可通过控制盘或 DriveWindow调试 电容充电 内部保护

11 6-Pulse TSU 脉波TSU

12 12-Pulse TSU 脉波TSU Master Slave 12-pulse master, 12-pulse slave

13 12-Pulse TSU 脉波TSU Master Slave 12/6-Pulse Master, 12-Pulse Slave

14 AutoTransformer 自耦变压器
TSU Control Board L+ U V U c W L–

15 TSU power range TSU 功率范围
Thyristor Supply Unit (TSU) for regenerative systems 440, 460, 500 V 525, 575, 660, 690 V kVA kVA kVA 380, 400, 415 V Thyristor Supply Unit Module DC Choke Power Ratings [kVA] V V V TSU B1...B3 Internal B4...B5 External Internal DC Choke

16 TSU types 晶闸管整流单元型号

17 Boards of TSU TSU电路板

18 Boards 电路板

19 Connections of boards 电路板的连接

20 SDCS-CON-2 S2 Selection Normal start Start with initial values
4 6 8 X37 S2 X14 1 3 5 7 SSDCS-CON-2 AMC-DC SSDCS-IOE-2 X33 H1 X18 D33 D35 X21 X11 X17 D31 D32 24,5 cm ABB DDCS+ ASIC X12 X13 X16 X2 X1 Control Panel CDP312 connection 24,7 cm Master / Slave optical connection

21 Seven Segment Display 七段数码显示
Code . L 8 E 1 E 2 A XX E 3 E 4 E 5 E 6 F XX Description Normal situation; no fault, no alarm During downloading (PC->drive) sequence Program is not running Not in use No control program in memory Alarm, same number as in Fault logger, shown only if no fault is active Incompatible hardware Ram memory test error ROM memory test error Fault, same number as in fault logger Seven Segment Display/Status Codes A seven segment display shows the status of the supply unit. The status code consists of one to three characters. In case of two or three character code, the characters are blinking at 0.7 s intervals.The codes are listed in table below

22 SDCS-POW-1 SDCS-IOE-2 Power supply board 50W
- X3, X4, X5 and X96 not used in TSU - X / 115 V AC - X V DC - Output voltages: +48, +24, +15, -15, ja +5V WARNING: VOLTAGE ON COOLING ELEMENT Supply Voltage Monitoring The control board monitors the following auxiliary voltage levels: Voltage V +15V -15V +24V +48V Tripping Level V +12.4V -12.0V +19V +38V If +5V drops under the tripping level, it causes a master reset by hardware. All I/O-registers are forced to zero and the firing pulses are suppressed.

23 SDCS-IOB-21 SDCS-UCM-1 SDCS-UCM-1 X3 nominal motor voltage X2 X1 -Uc
60 SDCS-UCM-1 X2 X1 -Uc +Uc nominal motor voltage 690V 600V 500V 400V 150 RESISTOR BOARD WARNING! The terminals X1 and X2 on the Measurement Board SDCS-UCM-1 are at the main circuit potential. The board contains two resistor chains which are connected to the intermediate circuit voltage (DC). The voltage reduced by the resistor chain is connected to Measurement Board SDCS-IOE-2. The intermediate circuit DC voltage is wired to connectors X1 and X2. The positive DC busbar (+Uc) is connected to connector X1 and negative DC busbar (-Uc) to connector X2. The connection to X1 and X2 is done according to the supply voltage (AC) of the bridge according to the table below. Supply Interm. Circuit Motor Connection Connection Voltage/VAC Voltage Uc/VDC Voltage/VAC Bin in X1 Bin in X2 830* * 690* * Nominal supply voltage is higher than the nominal motor voltage. The forward bridge is controlled so that the intermediate circuit DC voltage and motor voltages are at the desired (lower) level. Nominal DC voltage in the output of the board is 7 V.

24 SDCS-PIN-41 & SDCS-PIN-51 SDCS-PIN-51 SDCS-PIN-41 Isolating A B C D E
F G G G G G G supports C C C C C C T4 T1 T6 T3 T2 T5 X1 X2 100 X113 X213 SDCS-PIN-41 Conductive supports 270 W5 R123 X23 2 X24 2 X25 2 U1 1 1 1 W5 W4 W3 W2 W1 X22 X122 S3 One NTC R R21 V1 Two NTC W11 W9 W8 W7 W6 W10 W70 W71 W72 R22 R26 W1 W16 W15 W14 W13 W12 W80 W81 W82 X12 X13 X413 X313 The board contains six pulse transformers with amplifiers. When the forward bridge and the reverse bridge are not inside the same module (typically the TSU frame sizes B4 & B5): one board fires the thyristors of the forward bridge, and the other the thyristors of the reverse bridge. When both the forward and reverse bridges are inside the same module (typically the TSU frame sizes B1 to B3): one board fires the upper leg thyristors of both the forward and reverse bridges, and the other board fires the lower leg thyristors. Interface Board SDCS-REB-1 In supply module frame sizes B4 & B5, there is a Interface Board SDCS-REB-1 in addition to two Pulse Transformer Boards SDCS-PIN-41 (see section Connections Between the Boards). One SDCS-PIN-41 board is located inside the forward bridge module, and it fires all thyristors of the forward bridge. The other board is located inside the reverse bridge module, and it fires all thyristors of the reverse bridge. X12 W83 Flat cable GND C1 100 W21 W20 W19 W18 W17 S2 S1 D1 W26 W25 W24 W23 W22 X513 X113 X213 X413 X313 X13 Isolating SDCS-PIN-51 supports Conductive supports 305

25 SDCS-PIN-51 TSU Current Measurement Setting
TSU Module U N R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16 R17 R18 R19 R20 R21 R22 R23 R24 R25 R26 ACN 500 ACN 500 ACN 500 ACN 500 ACN 6x 500 ACN 6x 500 ACN 6x 500 ACN 6x 500 ACN 500 ACN 500 ACN 500 ACN 500 ACN 6x 690 ACN 6x 690 ACN 6x 690 ACN 6x 690 ACN 6x 690 ACN 690 ACN 690 ACN 690 ACN 690 TSU Current Measurement Setting The Table above shows the current measurement scaling for each TSU module. The scaling is done by cutting off resistors. The scaling is preset at the factory for each TSU module. On field the setting needs to be done only if the board or module is changed. ACN ACN ACN ACN 830 ACN 830 ACN 830 ACN 830

26 SDCS-PIN-51 Resistor Supply Voltage W1, 6, 12, 17, W2, 7, 13, 18, W3, 8, 14, 19, 24 500V 690V 830V Un-cut zero ohm resistor Cut zero ohm resistor TSU Voltage Measurement Setting Main circuit voltages are measured by the voltage dividing circuits. Scaling of voltages is done by activating 1M resistors (i.e. by cutting off parallel zero ohm resistors). The table above shows the voltage measurement scaling. The scaling is preset at the factory for each TSU module. On field the setting needs to be done only if the board or module is changed

27 AMC-DC AMC-DC - Communication board. Fibre Optic Links
TxD CH 0 Power On RxD TxD CH 2 RxD TxD Programs are running CH 3 RxD 8,4 cm Fault - Communication board. Fibre Optic Links There are three fibre optic links on the board: CH0 is reserved for the overriding control system (e.g. AC80). CH2 is not used as default. CH3 is reserved for the PC connection. 15,6 cm

28 Digital Outputs 数字输出 Fan Control Ready Main contactor Programmable I/O
Fault indication DO1: Non-programmable I/O. Reserved for the TSU cooling air fan control. DO2: Non-programmable I/O. Reserved for the Supply-Unit-Ready indication. DO3: Non-programmable I/O. Reserved for the main contactor/breaker control. DO4: Programmable I/O. For the actual use see the circuit diagrams and Parameter DO4 INDEX. DO5: Programmable I/O. For the actual use see the circuit diagrams and Parameter DO5 INDEX. DO6: Programmable I/O. For the actual use see the circuit diagrams and Parameter DO6 INDEX. DO7: Programmable I/O. For the actual use see the circuit diagrams and Parameter DO 7INDEX. DO8: Non-programmable I/O. Reserved for the fault indication

29 Digital Inputs 数字输入 FAN & thermistor ON/OFF Control Main Contactor
Programmable External earth fault Master or slave ready RESET Function Selection Mode Control Earthing capacitor DI1: Non-programmable I/O. Reserved for the supply unit cooling air fan supervision. DI2: Non-programmable I/O. Reserved for the supply unit ON/OFF control. DI3: Non-programmable I/O. Reserved for the supervision of the main contactor/air circuit breaker state. DI4: Programmable I/O. Reserved for the external earth fault detection. For the actual use see the circuit diagrams and Parameter DI4 EARTH FLT SEL. DI5: Programmable I/O. Reserved for the 12-pulse bridge application. For the actual use see the circuit diagrams and Parameter REDUNDANT SEL. DI6: Non-programmable I/O. Reserved for the supply unit fault resetting DI7: Programmable I/O. Reserved for the external control of the reverse bridge (enable/disable) and/or intermediate DC circuit voltage reference. For the actual use see the circuit diagrams and Parameter DI7 FUNCTION SEL. DI8: Programmable I/O. Reserved for the external control of the reverse bridge (enable/disable). For the actual use see the circuit diagrams and Parameter DI8 FWD BRIDGE SEL. Grounding selection with short circuit resistors: - cut out for internal W2....W16 - cut out for external W1....W15

30 DC Voltage Control DC电压控制

31 Capacitance Values 逆变模块电容值

32 Capacitance Values 逆变模块电容值

33 Frame L/H B1 1250 B2 300 B3 140 B4 55 B5 30 DC-choke Values 电抗器值
- B1 to B5 are frame sizes of the TSU units. - Corresponding power see in the Technical catalogue data of the User’s Manual.

34 TSU bridge selection TSU正桥/反桥的选择

35 Bridge Change Logic 正反桥切换逻辑

36 Start with DI2 DI2启动TSU时序
Fan confirm DI2 ON Main Contactor confirm Fan Control Main Contactor Control TSU RUNNING Synchronizing > 0.5s Fan confirm < 12s

37 Start with DI2+FB DI2+FB启动时序

38 Parameters Group 1 ACTUAL VALUES Group 2 ACTUAL VALUES
Group PULSE SIGNALS Group 4 INFORMATION Group 7 CONTROL WORDS Group 8 STATUS WORDS Group 9 FAULT/ALARM WORDS Group 14 DIGITAL OUTPUTS Group 15 ANALOG OUTPUTS Group 16 SYS CONTROL INPUTS Group 18 LED PANEL CTRL Group 19 DATA STORAGE Group 20 LIMITS

39 Parameters Group 23 VOLTAGE REFERENCE Group 30 FAULT FUNCTIONS
Group 40 UNDERVOLT MONIT Group PULSE OPERATION Group 51 COMMUNICATION MODULE Group 70 DDCS CONTROL Group 90 D SET REC ADDR Group 91 D SET REC ADDR Group 92 D SET TR ADDR Group 93 D SET TR ADDR Group 94 CONV VALUE SELECT Group 98 OPTION MODULES Group 99 START UP DATA

40 Group 2 ACTUAL VALUES 2.11 RL DC CURRENT
Intermediate circuit DC current in percents of the nominal value 2.12 RL DC VOLTAGE Intermediate circuit voltage in percents of the nominal value 2.13 RL MAINS VOLTAGE Supply voltage in volts 2.14 FIRING ANGLE Thyristor firing angle in degrees 2.15 CONV_VALUE_2MS Selected actual signal updated every 2ms. 2.16 CONV_VALUE_8MS Selected actual signal updated every 8ms. 2.11 RL DC CURRENT Intermediate circuit DC current in percents of the nominal value (Ic) measured every 3,3ms (50Hz supply) or 2,8 ms (60Hz supply) 2.12 RL DC VOLTAGE Intermediate circuit voltage in percents of the nominal value measured every 3,3 ms (50Hz supply) or 2,8 ms (60Hz supply) 2.13 RL MAINS VOLTAGE Supply voltage in volts measured every 3,3 ms (50Hz) or 2,8 ms (60Hz) 2.14 FIRING ANGLE Thyristor firing angle in degrees, update interval is 3,3 ms (50Hz) or 2,8 ms (60Hz). 2.15 CONV_VALUE_2MS Selected actual signal updated every 2ms. See Parameter CONV VALUE 2MSSEL. 2.16 CONV_VALUE_8MS Selected actual signal updated every 8ms. See Parameter CONV VALUE 8MSSEL.

41 Group 94 CONV VALUE SELECT
94.01 CONV VALUE 2MSSEL Selects value for Parameter 2.15 CONV_VALUE_2MS. 94.02 CONV VALUE 8MSSEL Selects value for Parameter 2.16 CONV_VALUE_8MS. 94 Group 94 CONV VALUE SELECT Group 94 parameters select two core signals of the TSU control to be updated into Parameter Group 2 ACTUAL VALUES. 94.01 CONV VALUE 2MSSEL Selects value for Parameter 2.15 CONV_VALUE_2MS. The value is updated in 8ms cycle. 94.02 CONV VALUE 8MSSEL Selects value for Parameter 2.16 CONV_VALUE_8MS. The value is updated in 8ms cycle. See Appendix C – Core TSU Signals in User’s Manual for the alternatives.

42 Group 16 SYS CONTROL INPUTS
16.02 PARAMETER LOCK LOCKED / OPEN Default: OPEN 16.03 PASSCODE 16.04 LOCAL LOCK FALSE / TRUE Default: OFF 16.11 BRIDGE FORCE NO FORCE / FWD FORCE / REV FORCE Default: NO FORCE 16.12 DI7 FUNCTION SEL NOT USED / BRAKING ENABLE / LOW REF / COMBINATION Default: REV ENABLE 16.13 DI8 FWD BRIDGE SEL NOT USED / DI OPEN Default: NOT USED 16.02 PARAMETER LOCK LOCKED, Parameter Group 0 to 99 parameter changes with the Control Panel are disabled. OPEN, Parameter Group 0 to 99 parameter changes with the Control Panel are enabled. 16.03 PASSCODE Pass code for the parameter lock. To open the parameter lock, change the value to 358. The value automatically changes back to 0. 16.04 LOCAL LOCK FALSE, Lock is off TRUE, Control location change from remote (external) to local (Control Panel) is disabled (locked). 16.11 BRIDGE FORCE NO FORCE, Normal operation of the bridges is allowed. FWD FORCE, The reverse bridge is blocked. REV FORCE, The forward bridge is blocked. 16.12 DI7 FUNCTION SEL NOT USED, Digital input DI7 is not connected. BRAKING ENABLE, Digital input DI7 is on (“1”)=Reverse bridge is enabled. LOW REF, Digital input DI7 is off (“0”)=Control program sets the intermediate circuit (DC) voltage reference to minimum. See Parameter UD REF MIN. COMBINATION, Digital input DI7 is off (“0”)=Control program sets the intermediate circuit (DC) voltage reference to minimum and allows reverse bridge. See Parameter UD REF MIN. DI7 is on (“1”)=Control program allows intermediate circuit maximum reference and blocks reverse bridge. See Parameter UD REF MAX 16.13 DI8 FWD BRIDGE SEL NOT USED, Digital input DI8 input is not in use. DI OPEN, DI8 is on (“1”)=Reverse bridge is enabled. DI8 is off (“0”)=Reverse bridge is disabled (blocked).

43 99 Start-up Data Default 99.01 Language English 99.02 Device Name 0
99.09 Applic Restore No 99.10 Drive ID number 99.20 Oper Mode Select 6 P Single 99.21 Auto Trafo Ratio 100% 99.22 S Conv Nom Curr 99.23 S Conv Nom Volt Start-up parameters are normally factory preset. 99.01 LANGUAGE Language selection. Note: Only the English version of the TSU control program is available by the time of publishing this manual. Default: ENGLISH 99.02 DEVICE NAME Name of the device. The name can be given from the DriveWindow PC tool. Default: 0 99.09 APPLIC RESTORE NO / YES Restores parameters to factory setting values except Parameter Group 99 START UP DATA. Default: NO 99.10 DRIVE ID NUMBER 0 to 32767 Typically there is no need to adjust this parameter. Parameter can be used by the overriding control system to check the right connections of the optical cables to the unit. Default: 0 99.20 OPER MODE SELECT This parameter defines the supply unit operating mode. The setting depends on the configuration of the supply section. 6 P SINGLE, 12 P MASTER, 12 P SLAVE, 12/6 P MASTER, 12/6 P SLAVE Default: 6 P SINGLE 99.21 AUTO TRAFO RATIO Transformation ratio of the optional autotransformer connected to the reverse bridge. If the unit is not equipped with the autotransformer do not change the default setting (100%). If the unit is equipped with the autotransformer, set according to the transformer rating. (Typically the ratio is 120%). Default: 100% 99.22 S CONV NOM CURR Nominal intermediate circuit DC current of the forward supply module. Note: The Parameter setting must correspond to the hardware setting on the Measurement Board SDCS-PIN-51. Default: 0 99.23 S CONV NOM VOLT Rated AC voltage of the forward bridge. See the rating plate. Default: 50V

44 99 Start-up Data Default 99.24 Nom Supply Volt 50V
99.25 Mains Phase order R-S-T 99.26 L Net FWD 99.27 L Net REV 99.28 L DC Reactor 99.29 C Capacitance 99.30 Conv Par Store 99.24 NOM SUPPLY VOLT Nominal voltage of the supply network. Default: 50V 99.25 MAINS PHASE ORDER R-S-T Standard supply phase order. R-T-S Non-standard supply phase order. Note: If a non-standard phase order is allowed at the supply terminals of the module, check that the 3-phase cooling fans rotate in right direction. Change the cable connections when necessary. Default: R-S-T 99.26 L NET FWD Network inductance of motoring bridge in microhenrys (mH) if the supply transformer data is known, calculate as follows if the supply transformer ratings are not known, set this parameter to 50mH. Default: 0 99.27 L NET REV Network inductance of generator bridge in microhenrys (mH). If the unit is not equipped with the optional autotransformer, use the same value as for Parameter L NET FWD. If the unit is equipped with the optional autotransformer, use the value 1.5 · (99.26 L NET FWD) Default: 0 99.28 L DC REACTOR DC Reactors inductance in microhenrys (mH). See the Technical Data appendix. Default: 0 99.29 C CAPACITANCE Sum capacitance in millifarads of the inverters connected to the system. See the Technical Data appendix. Default: 0 99.30 CONV PAR STORE 0 / 22 When set to 22 all parameters are loaded from the Communication Board AMC-DC to the non-volatile flash PROM of the Control Board SDCS-CON-2. Value restores automatically to zero. Note: After changing the Group 99 START UP DATA parameters, the changes must be loaded to the Control Board SDCS-CON-2. Default: 0

45

46

47 正桥fan 反桥fan Fan DI1 正桥风机

48 2 DO1风机启动 DO2 TSU 故障 1 正桥、反桥风机过温保护 2 DO3主接触器合闸保持 1 1 3 DI2 DI3 FAN DI1 DC Choke 风机启动 延时关断 X X

49 正桥、反桥风机启动 DC choke SDCS-IOB-2x DC reactor 过温保护 启动按钮 急停回路 主接触器确认 接地故障保护回路 复位 SDCS-CON-2

50 SDCS-IOB-2x 启动风机 故障指示 主接触器合闸

51

52

53


Download ppt "ACS800 Multidrive Thyristor Supply Unit ACS800多传动 TSU"