Presentation is loading. Please wait.

Presentation is loading. Please wait.

Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington.

Similar presentations


Presentation on theme: "Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington."— Presentation transcript:

1 Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

2 Purpose of Lock-Out and Tag Personal Safety Prevent Undue Exposure to Energized Circuits Reduce Electrical Fatalities and Accidents

3 Coal Fatals - Total & Electrical –Year Total Electrical –1970 – 1999 2946 229 –2000 38 2 –2001 42 2 –2002 27 4 –2003 29 4 –2004 8 1 –Total 3090 242

4

5 Coal Fatals - Total & Electrical –Average = 90.6 Electrical = 7.1 [7.8%] – (For 1970 to 2003 and Based on 3082 fatalities; 241 electrical)

6 Electricity Next to a nuclear reaction, an electrical arc is the hottest thing on earth, being seven times the temperature at the sun’s surface. Electricity can cause shock, burns, ignitions, explosions and even electrocution. Be Wise! Stay Alive! Always Deenergize!

7 Circuits that must be Locked- Out and Tagged Electrical Hydraulic Pneumatic Mechanical Thermal

8 Who must Lock-Out and Tag When Performing Electrical Work All person(s) doing electrical work on the circuit

9 Trouble Shooting Procedure For Equipment and Circuits Energized Circuit and EquipmentEnergized Circuit and Equipment –Low- and Medium-Voltage Only –Only to determine the problem Lock- and Tag- out to perform electrical workLock- and Tag- out to perform electrical work

10 EFFECTS OF CURRENT ON THE AVERAGE BODY

11 Current Effects How much current does it take to illuminate a 60 watt, 120 volt light bulb? The answer is 0.5 amperes or 500 milliamps. This is over five times the current that it takes to electrocute someone.

12 CURRENT EFFECT 1 MILLIAMPTHRESHOLD OF PERCEPTION 1 MILLIAMPTHRESHOLD OF PERCEPTION 1 TO 8 MILLIAMPS SENSATION OF SHOCK1 TO 8 MILLIAMPS SENSATION OF SHOCK 8 TO 15 MILLIAMPSPAINFUL SHOCK8 TO 15 MILLIAMPSPAINFUL SHOCK 15 TO 20 MILLIAMPSLOSS OF MUSCULAR CONTROL15 TO 20 MILLIAMPSLOSS OF MUSCULAR CONTROL

13 20 TO 50 MILLIAMPSBREATHING IS DIFFICULT 100 TO 200 MILLIAMPSVENTRICULAR FIBRILLATION (NO KNOWN REMEDY)100 TO 200 MILLIAMPSVENTRICULAR FIBRILLATION (NO KNOWN REMEDY) OVER 200 MILLIAMPSSEVERE BURNSOVER 200 MILLIAMPSSEVERE BURNS

14 Why People Do Not Lock- & Tag-Out Takes too long! Too far to travel to remove power! Will only take a minute! I’ll do it hot! I know what I’m doing! Have seen others do it or have done it themselves!

15 ELECTRICAL FATALITIES BY STATE 1970 - 2003 3 6 3

16 Percentage of Electrical Fatalities by Location

17

18

19

20

21

22

23 American Eagle Mine 4605437 02/18/2000 AGE 44 EMPLOYEE ENTERED SUBSTATION TO DETERMINE WHAT WORK WILL BE REQUIRED TO REMOVE THE TRANSFORMER. HE CLIMBED THE TRANSFORMER TO LOOK AT TOP WHEN HE CAME IN CONTACT WITH LINE.

24 PE 2 Underground 1518008 04/30/2000 AGE 26 A CERTIFIED ELECTRICIAN WAS GOING TO MAKE REPAIRS ON THE RIGHT SIDE POWER CENTER IN THE NO. 5 ENTRY, AND WAS FOUND LYING BESIDE THE POWER CENTER. IT APPEARS HE RECEIVED A FATAL ELECTRICAL SHOCK

25 Still Run No. 4 4608726 03/13/2001 AGE 44 AFTER INSTALLATION OF A BANK OF CAPACITORS ON THE HIGH VOLTAGE LINES FEEDING THE MINE SUBSTATION, EE (ACCORDING TO WITNESSES) UNPLUGGED THE 110 V CONTROL CIRCUIT FROM THE RECEPTACLE, THREW IT TO THE GROUND, PICKED IT BACK UP TO INSPECT & AT THIS TIME CAME IN CONTACT WITH ELECTRICAL CURRENT.

26 #77 1509636 07/20/2001 AGE 26 EE WAS FATALLY ELECTROCUTED AS HE DISASSEMBLED A CONVEYOR BELT STARTING BOX SOURCE OF POWER CAUSING DEATH IN UNKNOWN AT THAT TIME.

27 Mine No. 5 4406051 01/24/2002 AGE 42 SECTION POWER MOVE HAD BEEN MADE. WORK BEING DONE TO CONNECT THE PHASING. EMPLOYEE APPROXIMATELY 2 CROSSCUTS FROM POWER CENTER STATED HE HEARD A STRANGE SOUND FROM THE AREA OF THE POWER CENTER AND WENT TO THE POWER CENTER AND FOUND THE DECEASED SLUMPED OVER THE POWER CENTER.

28 Mine 84 3600958 05/11/2002 AGE 46 EE WAS OPERATING A STAMLER COAL HAULER AND HAD ATTEMPTED TO TRAM AROUND AN UN CUT CORNER. IN DOING SO HIS HAULER APPARENTLY PINCHED THE ENEGIZED LOADER CABLE BETWEEN THE HAULER AND THE COAL RI B. EE EXITED THE MACHINE TO LOOK AT THE DAMAGE TO THE CABLE AND WAS APPARENTLY ELECTROCUTED WHEN HE CONTACTED THE FRAME OF THE COAL HAULER.

29 Huff Creek No 1 1517234 05/21/2002 AGE 50 EMPLOYEE WAS WORKING ON A POWER DISTRIBUTION BOX TO DETERMINE WHY A CIRCUIT BREAKER WOULD NOT OPERATE. HE APPARENTLY CAME IN CONTACT WITH AN ENERGIZED CIRCUIT DURING THE TROUBLE SHOOTING PROCESS.

30 Calvary No. 80 1516349 05/23/2002 AGE 58 THE ELECTRICIAN WAS WORKING ON A GROUNDED SHUTTLE CAR CABLE AND RECEIVED FLASH BURNS WHEN A SHORT CIRCUIT OCCURED AT THE FEMALE RECEPTACLE ON THE ELECTRICAL POWER CENTER.

31 Mine No. 4 4407052 01/21/2003 AGE 33 THE VICTIM WAS ELECTROCUTED NEAR THE FACE OF NO. 8 ENTRY OF THE 001-0 MMU WHILE INSTALLING SUPPLEMENTAL ROOF SUPPORTS. WHEN ANOTHER WORKER FINISHED CUTTING A STEEL BEAM WITH A TORCH, AN ENERGIZ ED TRAILING CABLE WAS DAMAGED CAUSING THE BEAM & TRAILER ON WHICH IT RESTED TO BECOME ENERGIZED. THE VICTIM THEN CAME IN CONTACT WITH THE TRAILER, RESULTING IN ELECTROCUTION.

32 No. 50 Mine 4608776 03/23/2003 AGE 49 BREAKER BLEW UP AND BURNED EMPLOYEE.

33 Beaver Valley 3608725 06/13/2003 AGE 41 WHILE TROUBLE SHOOTING MAIN OUTSIDE SUBSTATION, EMPLOYEE CAME IN CONTACT WITH HIGH VOLTAGE RESULTING IN DEATH.

34 Upper Big Branch Mine-South 4608436 07/19/2003 AGE 27 EMPLOYEE WAS IN THE PROCESS OF REPAIRING #3 SHUTTLE CAR CABLE. POWER TO CABLE HAD BEEN TAGGED & LOCKED OUT. HE WAS DISCOVERED LYING ON HIS BACK & NOT BREATHING. CPR WAS ADMINISTERED AND HE WAS TRANSPORTED TO THE HOSPITAL WHERE HE WAS PRONOUNCED DEAD AT APPROX. 8:20 P.M. MSHA/STATE INVESTIGATIONS ARE INCONCLUSIVE AT THIS TIME.

35 Ruby Energy 4608808 02/05/2004 AGE 33 ELECTRICIAN WAS FATALLY ELECTROCUTED WHILE REPAIRING A MINER CABLE. THE CABLE WAS NOT LOCKED AND TAGGED OUT BY THE ELECTRICIAN.

36 Regulations requiring Disconnecting Devices? 30 CFR 75.509 "All power circuits and electric equipment shall be de-energized before work is done on such circuits and equipment, except when trouble shooting or testing".

37 75.509 Policy states, PPM states in part, …"a violation of this Section shall be cited only when electrical work is being performed on an energized machine.... Troubleshooting or testing does not include the repair of electrical, hydraulic, or mechanical problems".

38 75.511 No electrical work shall be performed on low-, medium-, or high-voltage distribution circuits or equipment, except by a qualified person or a person trained to perform electrical work and to maintain electrical equipment under the direct supervision of a qualified person....

39 75.511 cont. Disconnecting devices shall be locked out and suitably tagged by such persons. Locks or tags shall be removed only by the persons who installed them or, if such persons are unavailable, by persons authorized by the operator or his agent.

40 75.511 Policy states, "For the purpose of this Section, electrical work is considered to be work required to install or maintain electric equipment or conductors..... The phrase "under the direct supervision of a qualified person" must, as a minimum, include the following:

41 75.511 PPM cont. 1.The qualified person shall examine and/or test an electric circuit or machine and determine the need for repair or maintenance; 2.The qualified person must give specific instructions to the employee assigned to perform this work with respect to the nature and extent of the repairs to be performed and, where necessary, prescribe the manner in which the work is to be performed;

42 75.511 PPM cont. 3.The qualified person is, at all times, under continuing duty to instruct, advise, or consult with the employee in the event the work which he has assigned cannot be performed by the employee in the manner prescribed; and 4.The qualified person must examine and test, if necessary, the completed work before the circuit is energized or the machine is returned to service.

43 75.511 PPM cont. Disconnecting devices shall be locked out, where possible, and suitably tagged by persons who perform the work. In all instances, trailing cables equipped with cable couplers or fuse nips shall be opened, tagged and locked out. The person doing the work shall keep the key to the padlock in his/her possession to insure that the circuit or cable will not be inadvertently energized while he or she is in contact with the conductors.

44 75.511 PPM cont. In every instance, the padlock shall be removed by the person who installed it if the person is present in the mine. If the person who installed the padlock is not present, the operator or the operator's agent (a responsible official) must designate a person to remove the padlock. "Suitably tagged" means that a sign with the wording such as "Danger, Repairs in Progress," shall be attached to the locked disconnecting device.

45 Disconnecting Devices Installed On-Board Mine Equipment When disconnecting devices are installed on-board mine equipment, they may be used to meet the requirements of 30 CFR 75.509, 75.511 and 75.1725 (c)....

46 Disconnect PPM cont. To meet the requirements of 30 CFR 75.509, 75.511 and 75.1725 (c), disconnecting devices must function so as to provide positive visual conformation that the equipment or circuit is deenergized. The worker must be able to easily see the power disconnect blades or contacts to determine, without any doubt, that the equipment or circuit is deenergized and...

47 Disconnect PPM cont. To meet the requirements of 30 CFR 75.520, disconnecting device enclosures must be explosion-proof..... In addition, the enclosure housing the disconnecting device must be the first enclosure on-board the machine that the trailing cable enters....

48 Disconnect PPM cont. Permitting a disconnecting device installed on- board a machine to be used as the visual disconnect for the equipment creates a change in established electrical work procedures. As a result, all miners who perform maintenance on this equipment must receive task training as required by 30 CFR 48.7 (a) (3). This training must include clear instructions that the disconnecting device will only deenergize the machine, and that the trailing cable will remain energized.

49 75.519 In all main power circuits, disconnecting switches shall be installed within 500 feet of the bottoms of shafts and boreholes through which main power circuits enter the underground area of the mine and within 500 feet of all other places where main power circuits enter the underground area of the mine.

50 75.519-1 Policy, Main Power Circuit; Disconnecting Switches; Locations This Section applies to low- and medium- voltage power circuits entering a mine and to low-, medium-, and high-voltage power circuits at the bottom of shafts and boreholes. The requirements for disconnecting switches for high-voltage power circuits entering a mine are contained in Section 75.802 (c).

51 75.519-1 PPM cont. A high-voltage cable coupler, switch, or other device not designed for load-breaking duty that is located at the bottom of a shaft or borehole may be used in conjunction with a high-voltage circuit breaker located on the surface provided: (1) A remote control switch that, when activated, will open the circuit breaker is provided at the shaft or borehole; and

52 75.519-1 PPM cont. (2) A visual or audible means to indicate that the circuit breaker has opened when the remote control switch is activated is provided at the bottom of the shaft or borehole. Signal lights will be acceptable if the lights receive power through the auxiliary contacts on the circuit breaker.

53 75.519-1 PPM cont. Unless fuse-type and knife-blade cutout switches are designed for load-breaking duty on high-voltage circuits, such switches shall be used for a disconnecting means only when some other means is first used to deenergize the circuit.

54 75.601 states in part,… “Disconnecting devices used to disconnect power from trailing cables shall be plainly marked and identified and such devices shall be equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.”

55 75.601 Policy states, Enclosed circuit breakers are not acceptable as visual evidence that the power is disconnected. Plugs and receptacles located at the circuit breaker and trolley nips are acceptable as visual means of disconnecting the power.

56 75.705 states in part,... “High-voltage lines, both on the surface and underground, shall be deenergized and grounded before work is performed on them,…”

57 75.705-1 (b) states in part,... “No high-voltage line, either on the surface or underground, shall be regarded as deenergized for the purpose of performing work on it, until it has been determined by a qualified person (as provided in 75.153) that such high-voltage line has been deenergized and grounded. Such qualified person shall by visual observation

58 75.705-1 (b) cont. (1) determine that the disconnecting devices on the high-voltage circuit are in open position and (2) ensure that each ungrounded conductor of the high-voltage circuit upon which work is to be done is properly connected to the system-grounding medium…”.

59 75.705-1 (c) states, “No work shall be performed on any high- voltage line on the surface which is supported by any pole or structure which also supports other high-voltage lines until: (1) All lines supported on the pole or structure are deenergized and grounded in accordance with all the provisions of this section which apply to the repair of energized surface high-voltage lines; or

60 75.705-1 (c) cont. (2) the provisions of 75.705-2 through 75.705-10 have been complied with, with respect to all lines, which are supported on the pole or structure.”

61 75.802 (c) states in part,... “Within 100 feet of the point on the surface where high-voltage circuits enter the underground portion of the mine, disconnecting devices shall be installed and so equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected,….”

62 75.808 states, “Disconnecting devices shall be installed at the beginning of branch lines in high- voltage circuits and equipped or designed in such a manner that it can be determined by visual observation that the circuit is deenergized when the switches are open.”

63 75.808 Policy states in part,... Cable couplers are acceptable as a disconnecting device only when used with an acceptable device such as a circuit breaker or oil-filled fused cutouts that are used to deenergize the circuit before the cable coupler is uncoupled.

64 75.808 PPM cont. If a remote switch in the ground check circuit is used to trip a circuit breaker prior to uncoupling the coupler, visible or audible evidence must be provided to indicate that the circuit breaker has opened before the coupler is uncoupled.

65 75.815(a) states The section power center must be equipped with a main disconnecting device installed to deenergize all cables extending to longwall equipment when the device is in the ``open'' position.

66 75.815(b) states Disconnecting devices for motor-starter enclosures must be maintained in accordance with the approval requirements of paragraph (f) of Sec. 18.53 of part 18 of this chapter. The compartment for the disconnect device must be provided with a caution label to warn miners against entering the compartment before deenergizing the incoming high- voltage circuits to the compartment. Sec. 18.53

67 Each motor-starter enclosure, with the exception of a controller on a high-voltage shearer, must be equipped with a disconnect device installed to deenergize all high-voltage power conductors extending from the enclosure when the device is in the ``open'' position. (1) When multiple disconnect devices located in the same enclosure are used to satisfy the above requirement they must be mechanically connected to provide simultaneous operation by one handle. (2) The disconnect device must be rated for the maximum phase-to- phase voltage and the full-load current of the circuit in which it is located, and installed so that-- (i) Visual observation determines that the contacts are open without removing any cover; (ii) The load-side power conductors are grounded when the device is in the ``open'' position; (iii) The device can be locked in the ``open'' position; (iv) When located in an explosion-proof enclosure, the device must be designed and installed to cause the current to be interrupted automatically prior to the opening of the contacts; and (v) When located in a non-explosion-proof enclosure, the device must be designed and installed to cause the current to be interrupted automatically prior to the opening of the contacts, or the device must be capable of interrupting the full-load current of the circuit. 18.53(f) states

68 75.815(c) states Disconnecting devices must be rated for the maximum phase-to- phase voltage of the circuit in which they are installed, and for the full-load current of the circuit that is supplied power through the device.

69 75.815(d) states Each disconnecting device must be designed and installed so that -- (1) Visual observation determines that the contacts are open without removing any cover; (2) All load power conductors can be grounded when the device is in the ``open'' position; and (3) The device can be locked in the ``open'' position.

70 75.815(d) states Disconnecting devices, except those installed in explosion- proof enclosures, must be capable of interrupting the full-load current of the circuit or designed and installed to cause the current to be interrupted automatically prior to the opening of the contacts of the device. Disconnecting devices installed in explosion-proof enclosures must be maintained in accordance with the approval requirements of paragraph (f)(2)(iv) of Sec. 18.53 of part 18 of this chapter.Sec. 18.53

71 75.903 states, “Disconnecting devices shall be installed in conjunction with the circuit breaker to provide visual evidence that the power is disconnected.”

72 75.903 Policy, Disconnecting Devices “A connecting plug on the outby end of the trailing cable connected to the power center or distribution box will be accepted as a disconnecting device. Other means, such as switches with visible contacts, may also be acceptable for this purpose. Molded-case circuit breakers are not acceptable as visible disconnecting devices.”

73 75.1725 (c) states, “Repairs or maintenance shall not be performed on machinery until the power is off and the machinery is blocked against motion, except where machinery motion is necessary to make adjustments.”

74 75.1725 (c) Policy states in part,.. “The trailing cable shall be disconnected from the source of power before repairs are made on portable or mobile equipment, except when the equipment must be operated for making adjustments.” “Opening a circuit breaker which is installed on the machine, and which opens all power conductors entering the machine, shall be acceptable as compliance with this Section for lubrication or changing bits.”

75 77.500 states, “Power circuits and equipment shall be deenergized before work is done on such circuits and equipment, except necessary for trouble-shooting or testing.”

76 77.500 Policy states in part,... “When electrical work is being performed on equipment, it is not necessary to completely deenergize the power system if means are provided on the equipment to deenergize the particular part or circuit on which repair work is to be done.”

77 77.500 PPM cont. “When work is performed in close physical proximity to exposed electrical circuits or parts, they shall be deenergized. High-voltage circuits that are not equipped with metallic shielding are considered to be exposed. Sections 110-16 and 710-34 of the 1968 National Electrical Code pertaining to working clearances can be used as a guide in determining “close physical proximity”.”

78 77.500 PPM cont. “All circuits within an electrical enclosure shall be deenergized before work is performed within the enclosure unless such energized circuits are guarded by suitable physical guards or adequate physical separation.”

79 77.500 PPM cont. “As the accident and injury data associated with working on energized circuits and equipment clearly indicates, this type of work presents a significant risk of hand injury. Therefore, gloves worn in accordance with 75.1720 (c) and 77.1710 (c) will be required whenever miners trouble-shoot or test energized electrical power circuits or electric equipment.”

80 77.501 states, “No electrical work shall be performed on electric distribution circuits or equipment, except by a qualified person or by a person trained to perform electrical work and to maintain electrical equipment under the direct supervision of a qualified person.”

81 77.501 cont. “Disconnecting devices shall be locked out and suitably tagged by the persons who perform such work, except that in cases where locking out is not possible, such devices shall be opened and suitably tagged by such persons. Locks or tags shall be removed only by the persons who installed them or, if such persons are unavailable, by persons authorized by the operator or his agent.”

82 77.501 Policy states in part,... “Electrical work”, as referred to in this Section, includes the design, installation, maintenance or repair of electric equipment and circuits.” “The term “direct supervision” shall not be interrupted to mean that the qualified person be physically present at all times during the performance of such repairs, but the qualified person has the following responsibilities:

83 77.501 PPM cont. 1.The qualified person shall examine and/or test an electric circuit or machine and determine the need for repair or maintenance; 2.The qualified person must give specific instructions to the employee assigned to perform this work with respect to the nature and extent of the repairs to be performed and, where necessary, prescribe the manner in which the work is to be performed;

84 77.501 PPM cont. 3.The qualified person is, at all times, under continuing duty to instruct, advise, or consult with the employee in the event the work which he has assigned cannot be performed by the employee in the manner prescribed; and 4.The qualified person must examine and test, if necessary, the completed work before the circuit is energized or the machine is returned to service.

85 77.501 PPM cont. It is MSHA’s policy that a person trained to perform electrical work and to maintain electric equipment under the direct supervision of a qualified person shall not be assigned the duty of testing or trouble-shooting energized circuits. Persons trained to perform electrical work and to maintain electric equipment may only do testing and trouble-shooting on energized circuits as part of their training program.

86 77.501 PPM cont. During this testing and trouble-shooting operation, a qualified person, as defined in Section 77.103, must be present at all times to observe, instruct, and aid the trainee.

87 77.501 PPM cont. “Suitably tagged” means that a sign with the wording such as “Danger - Hands Off - Do Not Close - Miners Working on Line,” shall be attached to the opened disconnecting device. The tag should bear the name of the workman who installed it.” “Keys to locks used to lock out switches should be kept by the person working on the circuit or equipment.”

88 77.600 states in part,... “Disconnecting devices used to disconnect power from trailing cables shall be plainly marked and identified and such devices shall be equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.”

89 77.600 Policy states in part,... “A visual means of disconnecting the power from the trailing cable must be provided so that it can readily be determined whether or not the cable is deenergized. Enclosed circuit breakers are not acceptable as visual evidence that power is disconnected. Plugs and receptacles located at the circuit breaker would be acceptable as the visible means of disconnecting the power.”

90 77.704 states in part,... “High-voltage lines shall be deenergized and grounded before work is performed on them, except that repairs may be permitted on energized high-voltage lines if…”

91 77.704 Policy states, “High-voltage lines shall be deenergized with a disconnecting device so that it can be determined by visual observation that the circuit is deenergized before the lines are grounded (refer to Section 77.704-9 when operating disconnecting devices), except that repairs may be permitted on energized high-voltage lines as specified in the regulations.”

92 77.704-1 states, (a) “No high-voltage line, either on the surface or underground, shall be regarded as deenergized for the purpose of performing work on it, until it has been determined by a qualified person (as provided in 77.103) that such high-voltage line has been deenergized and grounded. Such qualified person shall by visual observation

93 77.704-1 cont. (1) determine that the disconnecting devices on the high-voltage circuit are in open position and (2) ensure that each ungrounded conductor of the high-voltage circuit upon which work is to be done is properly connected to the system-grounding medium…”.

94 77.704-1 (b) states, “No work shall be performed on any high- voltage line which is supported by any pole or structure which also supports other high- voltage lines until: (1) All lines supported on the pole or structure are deenergized and grounded in accordance with all the provisions of this 77.704-1 which apply to the repair of energized surface high-voltage lines; or

95 77.704-1 (b) cont. (2) the provisions of 77.704-2 through 77.704-10 have been complied with, with respect to all energized lines, which are supported on the pole or structure.”

96 77.704-1 Policy states, There may be instances where one qualified electrician will go back some distance from the work site and deenergize and ground the high-voltage system to be repaired. This qualified electrician must be in either direct telephone or radio communication with the qualified electrician performing the actual work, and when he/she has deenergized and grounded the system, can inform the qualified electrician to make the repairs.”

97 77.808 states, “Disconnecting devices shall be installed at the beginning of branch lines in high- voltage circuits and equipped or designed in such a manner that it can be determined by visual observation that the circuit is deenergized when the switches are open.”

98 77.808 Policy states in part,... “Visual observation,” as referred to in this Section, means that a physical separation in the current-carrying parts of the disconnecting device can actually be seen. Enclosed circuit breakers, oil-filled cutout switches, and other devices which do not have a visual means of determining that the circuit is deenergized do not meet the requirements of this Section.

99 77.808 PPM cont. A cable coupler or other device that is not designed for load-break purposes is not acceptable as a disconnecting device unless it is used in conjunction with a current- interrupting device such as a circuit breaker or oil-filled cutout which can be used to deenergize the circuit before the cable coupler of other device is opened.

100 77.808 PPM cont. If a remote switch in the ground check circuit is used to trip a circuit breaker prior to uncoupling the coupler, visual or audible evidence must be provided to indicate that the circuit breaker has opened when the control switch is operated.

101 77.903 states, “Disconnecting devices shall be installed in circuits supplying power to portable or mobile equipment and shall provide visual evidence that the power is disconnected.”

102 77.903 Policy, Disconnecting Devices “Visual evidence,” as used in this Section, means that a physical separation of the current-carrying parts of the disconnecting device can actually be seen.

103 77.903 PPM cont. Consequently, molded-case circuit breakers are not acceptable as disconnecting devices. A connecting plug on the outby end of a cable with which the cable is connected to the power source box shall be accepted as a disconnecting device. Other visible disconnecting means, such as switches with visibly open contacts, will also meet the requirements of this Section.

104 77.404 (c) states, “Repairs or maintenance shall not be performed on machinery until the power is off and the machinery is blocked against motion, except where machinery motion is necessary to make adjustments.”

105 77.404 (c) Policy states in part,... “MSHA’s policy on Paragraph (c) of this section is similar to the policy on Section 77.500, which states that it is not necessary to completely deenergize large surface mining equipment where means are provided in the equipment to deenergize any part where repair work is to be done.

106 77.404 (c) PPM cont. Similarly, to comply with Paragraph (c), it is not necessary to completely deenergize large surface mining equipment where the motion of the operating equipment does not pose a hazard, and means are provided in the equipment to deenergize that part where the repair or maintenance work is to be done.

107 77.404 (c) PPM cont. Each repair or maintenance job must be examined separately for hazards related to that particular job or area. If the machine’s operation poses a hazard to the employee performing the work, the machine shall be shut down until the work is completed or the hazard no longer exists.

108 77.404 (c) PPM cont. General maintenance and housekeeping can normally be performed while the machine is in motion except around unguarded energized electric or moving mechanical equipment.

109 To Prevent Electrical Fatalities and Accidents Properly assess task to be performed and communicate! Team work. Never troubleshoot alone! Always lock out and tag the circuit or equipment before making any repairs! Always use equipment rated for circuit voltages! Always wear proper personal protection! Remember, it’s your life that is on the line!

110 Total Electrical Fatalities 1970-Present 242 total electrical fatalities

111 Five Steps To Safety Turn equipment off and disconnect the energy source Lock and tag energy source (electrical, mechanical, pneumatic, hydraulic, etc.) Release energy in charged conductors, pipes, and etc. Test the equipment to assure energy source is isolated Restore energy safelyRestore energy safely

112


Download ppt "Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington."

Similar presentations


Ads by Google