Presentation is loading. Please wait.

Presentation is loading. Please wait.

1Fan Coil RHOSS Electronic Board Technical Meeting SEDICAL S.A Codroipo, 30 JANUARY-01 FEBRUARY.

Similar presentations


Presentation on theme: "1Fan Coil RHOSS Electronic Board Technical Meeting SEDICAL S.A Codroipo, 30 JANUARY-01 FEBRUARY."— Presentation transcript:

1 1Fan Coil RHOSS Electronic Board Technical Meeting SEDICAL S.A Codroipo, 30 JANUARY-01 FEBRUARY

2 2Fan Coil RHOSS Electronic Board Fan Coil New Electronic Control New electronic board for all range of our UNIT SYSTEM BRIO, YARDY, FREND, UTNA, UTNB, UTC iDRHOSS compatible

3 3Fan Coil RHOSS Electronic Board Part of control CMS – Electronic board Ambient temperature probe ST1 Main coil temperature probe ST2 Addition coil temperature probe ST3 Receiver (for remote control) MVR – Control valve electronic board ON/OFF KiD-ISI/KRS485/KRS232/KFTT10 – Serial converter KUSB – RS485/USB Serial converter

4 4Fan Coil RHOSS Electronic Board CMS –Master/Slave Electronic board To install on the unit

5 5Fan Coil RHOSS Electronic Board ST1 – ST2 – ST3 probes To connect on CMS electronic board

6 6Fan Coil RHOSS Electronic Board MVR – Valve control electronic board ON/OFF To assemble and connect on electronic board

7 7Fan Coil RHOSS Electronic Board KiD-ISI –CAN-Bus serial converter To connect on main electronic board

8 8Fan Coil RHOSS Electronic Board KRS485 – RS485 serial converter To connect on main electronic board

9 9Fan Coil RHOSS Electronic Board KRS232 – RS485/RS232 serial converter To connect to KRS485

10 10Fan Coil RHOSS Electronic Board KUSB – Serial converter RS485/USB To connect to KRS485

11 11Fan Coil RHOSS Electronic Board ControlsControls KTCM – Infrared remote control KPCM – Remote control panel with display

12 12Fan Coil RHOSS Electronic Board ConnectionsConnections ST1, ST2,ST3 Valve control (MVR) El. Valve supply power Fan (3 speed + N) Display KPCM Serial converter KiSI - KRS485 KFTT10 El. supply power 230V

13 13Fan Coil RHOSS Electronic Board ConnectionConnection DI1 = SCR Display KPCM El. Board SLAVE DI2 = SIC DI3 = EIR DI4 = ECO Clamp M1

14 14Fan Coil RHOSS Electronic Board Main Funtion COOL – Cooling HEAT – Heating DRY – Dehudimifier FAN – Fan FULL AUTO – Automatic mode of function, std set-point, adjustable with ±2°C (I FEEL) HEAT/FULL AUTO + RES EL – Heating with electrical heater

15 15Fan Coil RHOSS Electronic Board Advanced function HOT START – In heating mode, when the water is too cold, the electrical fan doesnt start TOO COOL – In cooling mode, when the water is too hot, the electrical fan doesnt start PERIODIC VENTILATION – To avoid the stratification of air CONTINUOS VENTILATION – The electrical fan run at the minimun speed when the set point soddisfied (only with valves) SLEEP – During the night, this function increases the summmer set point and it decreases the winter set point TIMER – It switchs on and switchs off the fan at the setting time

16 16Fan Coil RHOSS Electronic Board Function by free voltage contac SCR (DI1) – Remote ON/OFF SIC (DI2) – Safety switch (i.e.: opened window); the display shows A07 EIR (DI3) – Remote Summer/Winter switch; started from dip-switch 2, only if the LOCK FUNCTION is ON ECO (DI4) – Economy, with SLEEP function

17 17Fan Coil RHOSS Electronic Board Configurazione Dip-Switch DIP SWITCH ONOFF 1 With valvesWithout valves 2 With EIRWithout EIR 3 LOCK FUNCTION actives LOCK FUNCTION doesnt active 4 4 pipes2 pipes 5 With electrical heater Without electrical heater 6PdC + BoilerChiller + Boiler Std configuation: all OFF

18 18Fan Coil RHOSS Electronic Board Dip-Switch configuration DS1 – VALVES: ON/OFF valves setting DS2 – EIR: Remote summer/winter switch DS3 – LOCK FUNCTION: limited funtion for the users DS4 – 2/4 PIPES: adictional heat coil DS5 – EL. HAETER: adictional electrical heater DS6 – PDC/CHILLER + CALDAIA: the adictional heat water coil can function with main water coil (with Heating Pump)

19 19Fan Coil RHOSS Electronic Board Probe IN / Probe OUT PROBE IN: the air probe is on the panel control PROBE OUT: the air probe is into the fan coil (ST1) Only with remote control panel, not with the infrared remote control PROBE IN - PROBE OUT

20 20Fan Coil RHOSS Electronic Board MASTER / SLAVE con pannello 1 MASTER, max 5 SLAVE With the electrical connection you have the automatic configuration of electronic board in master and slave configuration (no Dip-Switch) Use cable screening Once probe on control panel or with single probe on each fan coil. 2 fili3 fili CMS MASTERCMS SLAVE 2 fili KPCM

21 21Fan Coil RHOSS Electronic Board MASTER / SLAVE con telecomado 1 MASTER, max 5 SLAVE ATTENZION! Electrical heater only connected on MASTER Screen cable Only with probe on the fan coils Remote control work only with MASTER (escluded when MASTER faulty) 2 fili Res. elettrica CMS MASTERCMS SLAVE 2 fili KTCM

22 22Fan Coil RHOSS Electronic Board KCM vs KCMS CharatteristicKCMKCMS Remote infrared control NOSÌSÌ SLEEP NOSÌSÌ TIMER NOSÌSÌ ECONOMY NOSÌSÌ Remote summer/winter switch NOSÌSÌ Continuos ventilation NOSÌSÌ Supervisor interface NOSÌSÌ Electrical heater accessory To addIntegrated MASTER/SLAVE configuration Da Dip-SwitchAutoconfiguration Max number of SLAVE105