1 Building Services By John Bradley– licensed under the Creative Commons Attribution – Non-Commercial – Share Alike License

2 John Bradley

3 INTRODUCTION

4 Hot water

5

6

7

8 E =Expansion (m 3 ) C=Volume of water in system (m 3 ) ρ 1 =Density of water before heating (kg/m 3 ) ρ 2 = Density of water after heating (kg/m 3 )

9

10 DHW Systems Instantaneous Multi point Single point Stored VentedUnvented

11 CONVENTIONAL VENTED SYSTEM

12 Conventional vented system In a conventional vented system, the mains cold water from the rising main supplies a header tank or Cold Water Storage Cistern (CWSC), usually located in the roof space, to give the system a head of pressure. A cold water feed pipe from the CWSC feeds the base of a hot water cylinder. The water in the cylinder is heated by a heat exchanger coil in the cylinder, in which circulates water that has been heated by the boiler. In this indirect system the water in the boiler is kept separate from the water in the cylinder, allowing the water in the boiler and central heating radiators to be treated with chemicals and kept free of dissolved oxygen to prevent corrosion of radiators and boilers. When the water is heated it rises to the top of the cylinder where it can be drawn off through the hot water supply pipes and tap or shower outlets. The water is automatically replaced in the cylinder via the CWSC. Heating causes the water within the cylinder to expand. A vent pipe allows a safe route for excess pressure, air bubbles and steam should the system overheat. It runs from the top of the cylinder back up to the CWSC where its open vent is located just above the water level. The CWSC is sometimes called a feed and expansion tank, reflecting the functions it performs. Water pressure and flow within the system is driven by gravity, i.e. the weight of stored water in the CWSC is usually sufficient to push water down the pipe that feeds the hot water cylinder and back up to any tap or shower outlet, providing it is lower than the stored water level.

13 Cold water supply from rising main Cold water storage cistern Boiler Cylinder Coil heat exchanger to hot water outlets Cold feed pipe Immersion heater Vent pipe (at least 19mm) Overflow pipe Primary circuit Secondary circuit

14 Heating and hot water system

15

16

17

18 CWSC Normal expansion space Additional expansion space Overflow pipe Vent pipe Rising main Cold feed pipe 80mm Support for CWSC Flat, level, rigid platform to extend > 150mm beyond cistern

19 Conventional vented system: direct An alternative to the indirect system that is not now commonly used, but occurs in many older properties, is a direct system. In direct systems the water in the cylinder is heated directly, either by an electric immersion heater in the cylinder, or by the water being circulated around a boiler. This was a common arrangement with back-boilers behind open fireplaces and ranges such as Agas and Rayburns, but is not generally used with central heating boilers. The hot water from the boiler mixes directly with the water in the cylinder. Water that has circulated in the boiler and primary circuit is drawn off through the taps and can therefore be contaminated. If used in a soft water area the boiler must be rust-proofed. This system is not suited to hard waters. When heated the calcium in the water precipitates to line the boiler and primary pipework, eventually furring up the system making it ineffective and dangerous.

20 Immersion heaters Immersion heater

21 Legionella There is an increased risk of bacterial growth in water held at temperatures between 20°C and 46°C for prolonged periods. This can cause Legionnaires disease. The elderly are particularly vulnerable. Control of the bacteria is therefore vital in settings such as hospitals and care homes. The following measures are recommended for use with hot water systems: – Stored hot water temperature 60 to 65 o C throughout the storage vessel – Pipework dead-legs to be minimal – All pipework to be insulated to reduce water temperature losses – Distribution temperature to outlets >55 o C

22

23 UNVENTED SYSTEM

24 Unvented Systems Until the 1985 Building Regulations and the new Model Water Byelaws of 1986, a domestic hot water storage system in the UK was required to have an open vent pipe (a vented system). The majority of new houses now built in the UK are designed with sealed, unvented mains pressure hot water systems: norm in Europe and USA. Expansion of water dealt with by the use of an expansion vessel. This replaces the CWSC. The system is normally supplied direct from the mains and is sealed to the atmosphere (rather than being vented to the atmosphere). There is therefore no need for a vent pipe. Hence the term unvented system. A full description of the system would therefore be a mains pressure, unvented sealed domestic hot water system. The installation of an unvented system is notifiable building work. Installers registered with a competent person scheme can self-certify that the work complies with relevant Building Regs and the owner/occupier will be given a Building Regs certificate of compliance.

25 Unvented hot water and space heating system No roof space required for CWSC or feed and expansion tank Expansion vessel replacing CWSC for hot water system Expansion vessel replacing feed and expansion tank for heating system

26 Unvented Systems Water in the unvented cylinder comes directly from the cold water main and is at (nearly) mains pressure. To contain this pressure the cylinder has to be much stronger than in a gravity-fed system. Unvented cylinders are therefore made of thick copper or stainless steel. The outlet of the cylinder is to hot water taps which are normally closed. The inlet is from the cold water main which may incorporate non-return (check) valves or other devices preventing expansion back into the supply pipe. Therefore measures have to be taken to accommodate the expansion of the hot water which could otherwise give rise to enormous pressure in the cylinder. These take the form of some type of container of gas which can be compressed as the water expands. This may be arranged as a bubble of air in the cylinder or a separate expansion vessel.

27 Unvented Systems: expansion vessel An expansion vessel contains a diaphragm and a volume of air or nitrogen to absorb the expansion. It should be able to accommodate >4% of the systems overall water content. The photograph below shows an unvented hot water cylinder and two expansion vessels: one for the primary circuit and one for the secondary circuit. Diaphragm expansion vessels

28 Unvented Systems: air gap A purpose made hot water storage cylinder designed with provision for an air gap is an alternative to installing a separate expansion vessel. As the water expands on heating, the volume of trapped air is compressed to provide adequate delivery pressure and flow. Some manufacturers fit a floating baffle between the water and the air, to reduce the effect of turbulence. Hot water cylinder incorporating air gapBaffle

29 Safety of unvented systems At atmospheric pressure water boils at 100 o C. At higher pressures boiling point increases so that pressurised water can be heated to over 100 o C and remain liquid. However if the pressure is released (when a tap is opened) it will turn to steam, expanding and causing a steam explosion. Therefore unvented systems must have safety systems to control the temperature and pressure of the water. The expansion vessel is fitted with an expansion relief valve in case the vessel should fail. Beyond this there are 3 levels of safety : 1.Thermostat, set to operate at 60 to 65 o C 2.Non self-resetting energy cut-out, set to operate at 85 to 90 o C, to disconnect the supply of heat to the cylinder in the event of the thermostat failing and the storage system overheating, by turning the boiler off 3.Temperature/pressure relief valve, to discharge water to a safe and visible place open to the atmosphere, through a tundish (a small funnel with a pipe discharging into it to provide an air break in the overflow) if the water temperature reaches 95 o C

30 Unvented system with safety features Pressure reducing valve (to keep pressure less than the expansion valve opening pressure) Line strainer (to remove dirt) Cold water main Stop valve Check valve (to stop water returning to cold water main) To cold taps Expansion vessel Expansion relief valve To drains Tundishes To hot taps Boiler Thermostat Energy cut out Hot water cylinder Temperature/pressure relief valve

31 Temperature and pressure relief valve

32 Safe discharge from T&P relief valve Discharge from T&P relief valve The diagram shows the method prescribed in AD G for the discharge of water from safety devices The tundish should be: – Vertical; – Located in the same space as the cylinder; and – Fitted as close to the valve with no more than 600mm of pipe between the valve outlet and the tundish. The discharge pipe from the tundish should: – Have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in the pipework; and – Be installed with a continuous fall thereafter of at least 1 in 200.

33 AdvantagesDisadvantages Balanced hot and cold water supply to all outlets at high pressure No storage back up if mains water fails Allows greater system design flexibilityPoor mains water pressure will cause poor performance Cylinder can be sited almost anywhereRequires high level of maintenance High performance showers without need for pumpsNeed for discharge pipe (overflow) Simple plumbing system, less pipework No risk of water stagnation No risk of frost damage to pipework No noise of filling cisterns Less space consuming and saves installation costs as there is no CWSC Potable (drinking) water at all taps

34 MAINS PRESSURE VENTED SYSTEM

35 Thermal stores Unvented systems are normally at mains pressure. Thermal store systems have been developed that are at mains pressure but are vented. A container of water (the thermal store) is heated by the boiler via a heat exchanger coil at the bottom of the store. Mains pressure cold water passes through a second heat exchanger coil in the top of the store where it is heated by the stored hot water surrounding it and supplies the hot water outlets at mains pressure. Expansion of hot water in the store is accommodated by a feed and expansion cistern located just above the store (ie it is a vented hot water system).

36 Thermal store The thermal storage system is supplied with primary water from the boiler which heats the store via a primary coil. Secondary water flows directly from the cold mains into a secondary coil where it is heated by the store before being delivered to the taps at mains pressure. Thermal store (configuration for a sealed central heating system) Primary coil heat exchanger Thermal store Secondary coil Feed and expansion cistern for DHW system

37 INSTANTANEOUS SYSTEMS

38 Multi-point instantaneous heaters: Combi boiler The combi gas boiler functions as an instantaneous water heater only heating water as required. Water supply is from the mains, providing a balanced pressure at both hot and cold water outlets. Ideal for showers. System is sealed and has an expansion vessel which is normally included in the manufacturer's pre-plumbed, pre-wired package. Saves space: no need for cisterns in roof space, no hot water storage cylinder and associated pipework

39 SOLAR HOT WATER SYSTEMS 0 – – – 25.15

40 Solar irradiation Contours show solar irradiation in kWh/m 2 pa 811 kWh/m 2 /year 1115 kWh/m 2 /year

41 30 o – 40 o

42

43 System efficiencies Solar irradiation 100%60% 45% 30% Useful energy to taps Losses Glazing Collector Reflection Conductivity Losses Pump Primary pipes Losses Storage Secondary pipes

44 ComponentOption Solar collectorFlat plateEvacuated tube Heat transferPumpedThermo-siphon Heat storageCombined solar pre-heat and boiler heated water Separate solar pre-heat and boiler heated water ExpansionUnventedVented

45 Solar collectors Flat plate collector Evacuated tube collector

46 Flat plate collectors Insulated metal box with either a glass or plastic covering and a dark absorber plate usually made out of copper or aluminium. This absorber plate transfers the heat to a tube where the heat transfer fluid flows, picks up the heat from the plate, and returns it to the storage tank. The main distinction in the types of solar collector is between glazed and unglazed: The most common type of unit for DHW purposes is the glazed type

47 Evacuated tube collectors Evacuated tube collectors are more efficient than flat plate collectors and can provide higher output temperatures, but are more expensive. They are more efficient because the absorber is mounted in an evacuated and pressure-proof glass tube which reduces conductive and convective heat losses.

48 Evacuated tube collectors There are two main types: direct flow and heat pipe: In a direct flow collector, cold return fluid passes through the manifold and circulates round the absorber tubes in series and is heated in the process, returning to the flow stream of the manifold

49 Evacuated tube collectors: heat pipe Heat pipe evacuated tube collectors contain a copper heat pipe, which is attached to an absorber plate, inside a vacuum sealed solar tube. The heat pipe is hollow and the space inside is also evacuated. Heat pipe contains liquid. Vacuum enables liquid to boil at low temperature. When sunlight falls on surface of absorber, liquid in heat tube turns to hot vapour and rises to top of pipe. Water or glycol, flows through a manifold and picks up the heat. The fluid in the heat pipe condenses and flows back down the tube.

50 Evacuated tube collectors: heat pipe Heat pipe collectors must be inclined at an angle of > 25 o to allow internal fluid of the heat pipe to return to the hot absorber

51

52 Flat plateEvacuated tube BenefitsSimple design and proven technologyHigher water temperatures (can be used for space heating) Cheaper than evacuated tubeHigher efficiency LimitationsLower efficiency, requiring more roof space than evacuated tube More expensive Lower water temperaturesHigh stagnation temperature Cannot be embedded in roof structure

53 Heat transfer The system contains water and low toxicity polypropylene glycol (anti-freeze for frost protection) and corrosion inhibitors as a heat transport mechanism. If the solar collectors can be mounted below the level of the solar store circulation will occur by natural circulation (the thermo-syphon effect). This system is often used in Mediterranean countries. In the UK, the solar collectors are usually mounted on the roof so circulation in the solar primary circuit is pumped. Pump controlled by a differential temperature controller which compares the temperature at the collector panel outlet with the temperature of the water in the solar store and switches pump on when sufficient thermal gain.

54 Heat storage A solar DHW system requires the solar heat to be stored in a vessel to allow the heat to build-up during the day. Because of the pattern of solar gain, a back-up heat source will also have to be integrated into the system. This can either be in separate storage cylinders or in a combined cylinder. Separate solar cylinder Combined cylinder Solar coil at bottom of cylinder pre heats water

55 Combined cylinder heat storage The solar coil should be the below the boiler coil, allowing the solar pre-heated water to rise up the cylinder for any top-up heating from the boiler coil. Solar coil Boiler coil

56 Safety of solar systems Solar energy can quickly accumulate enough heat in a high performance collector to convert the circulating liquid to steam under significant pressure. Sometimes a high temperature situation arises during a circulation failure, eg a faulty pump, power cut and both the primary and secondary system may overheat. The state in which there is no net heat extraction from the collector is described as stagnation. This can be dealt by either: – Vented system: hot water vented to the atmosphere into a CWSC – Unvented sealed system, either: An expansion vessel and safety valve Drain-back: switch-off pump and drain away from a collector into a vessel

57 Vented system A solar DHW open vented primary system has features that distinguish it from conventional open vented heating systems: – If antifreeze is used, the feed and vent cistern is not normally connected to the cold water mains via a float valve, in case of dilution due to long-term evaporation. Hence, re-filling of the header cistern with antifreeze has to be undertaken manually. – Cistern needs to be fitted high up to gain the greatest static pressure (head) above the collector. It is not always practicable to achieve sufficient height. Schematic pipework layout of open vented solar primary system

58 Unvented system An unvented system contains a vessel capable of holding the primary fluid contents of the collector at all the permitted pressures in the system. This vessel can be of the membrane expansion type or of the drainback air-pocket type. Schematic pipework layout of unvented expansion vessel type

59 Unvented system: drainback The location of a solar collector normally above the store, allows the possibility the ability to drainback. The system is only partially filled, leaving an air pocket permanently present in the circulatory circuit. When the pump is off, the fluid does not fill the collector but instead rests wholly within the lower part of the circuit. When on, the pump pushes the air out of the collector replacing it with fluid, the air is then displaced down to inside a drainback vessel Schematic layout of drainback solar primary

60 Solar hot water with a combi boiler Because a combi boiler heats the hot water directly from the mains, there is no hot water cylinder. It is therefore more difficult to install a solar system. It is possible to pre-heat the mains water inlet to a combi boiler but the boiler must be solar compatible ie have approved temperature blending equipment and be able to monitor the temperature of water entering the system and modulate the flame accordingly. An alternative arrangement is shown below whereby a twin-coiled cylinder supplies the majority of outlets and the combi directly supplies a shower for example.

61 FITTINGS

62 Fittings: taps About 20% of domestic water flows through sink and basin taps. Long, un-insulated pipe runs (dead-legs) waste water whilst waiting for the tap to run hot. Spray taps (aerators) can save about 80% of the water and energy used for hand washing The amount of water used by a tap is related to frequency of use, flow rate and duration. Flow restrictors that reduce flow rate do not necessarily reduce water use, since some functions of taps are volume dependent (e.g. filling sinks, kettles) rather than duration dependent (rinsing, hand washing).

63 Fittings: showers and baths In new houses, showers and baths account for around 45% of water used.In new houses, showers and baths account for around 45% of water used. Showers can use a third of the water of a bath but people tend to take them more frequently and power showers and mains pressure systems have increased flow rate: long shower can use more water than a bath.Showers can use a third of the water of a bath but people tend to take them more frequently and power showers and mains pressure systems have increased flow rate: long shower can use more water than a bath. Showering is single largest use of hot water in modern homes. Water saver showers introduce air or atomise the water drops to improve wetting for a given flow rate. Feels like a power shower but uses less water.Showering is single largest use of hot water in modern homes. Water saver showers introduce air or atomise the water drops to improve wetting for a given flow rate. Feels like a power shower but uses less water. Or, flow rate can be limited. Minimum acceptable 4 litres/minute.Or, flow rate can be limited. Minimum acceptable 4 litres/minute. Typical standard bath capacity is 225 litres. Reduced capacity (shallow) baths are available with a capacity of 140 litres which retain a standard bath footprint.Typical standard bath capacity is 225 litres. Reduced capacity (shallow) baths are available with a capacity of 140 litres which retain a standard bath footprint.


Download ppt "Building Services By John Bradley– licensed under the Creative Commons Attribution – Non-Commercial – Share Alike License"