Spec Stoppers Sweet Spots Specials 1. How To Make $6,000 MORE on a 26 ton Data Aire Series DX Unit 2.

Similar presentations


Presentation on theme: "Spec Stoppers Sweet Spots Specials 1. How To Make $6,000 MORE on a 26 ton Data Aire Series DX Unit 2."— Presentation transcript:

1 Spec Stoppers Sweet Spots Specials 1

2 How To Make $6,000 MORE on a 26 ton Data Aire Series DX Unit 2

3 3 Increase Liebert Cost Reduce Data Aire Cost Liebert can still be basis of design Specification Control = $$$

4 4 Spec Stopper Locking Disconnect Switch –Standard option with Data Aire –Liebert charges about $50 more than Data Aire Liebert standard is non-locking disconnect

5 5 Justification Locking Disconnect Switch –Safety Locking disconnect can be locked in the off position preventing accidental power up of the unit while it is being serviced

6 6 Spec Stopper Dual Float Condensate Pump with Alarm –Standard option with Data Aire –Liebert charges about $60 more than Data Aire Liebert standard is single float no alarm

7 7 Justification Dual Float Condensate Pump with Alarm –Provides an alarm if condensate pump fails –Alerts operator before water is under floor

8 8 Spec Stopper Fire Stat –Standard with Data Aire –Liebert charges about $75 Liebert standard is no firestat

9 9 Justification Fire Stat –Responds to heat not smoke –Required by some codes

10 10 Spec Stopper Crankcase heaters –Standard with Data Aire –Liebert charges about $125

11 11 Justification Crankcase heaters –Prevents refrigerant from diluting compressor oil –Extends compressor life

12 12 Spec Stopper Steam Generator Humidifier –Standard with Data Aire –Liebert charges about $350

13 13 Justification Steam Generator Humidifier –Capacity 36% higher capacity than infrared –Efficiency 22% more efficient than infrared –Maintenance Five minutes to replace canister –Indoor Air Quality Enclosed water reservoir heated to boiling

14 Spec Stopper Minimum 18 gauge panels –Standard with Data Aire –Liebert standard is 20 gauge 18 gauge not available Charge about $550 for 16 gauge panels 14

15 Justification Minimum 18 gauge panels –Superior sound attenuation 15

16 Spec Stopper R-407c Refrigerant –No added cost with Data Aire –Liebert charges about $

17 Spec Stopper R-407c Refrigerant –Environmentally friendly 17

18 Liebert Data Aire Non-Locking Disconnect $ 50 0 Dual Float Condensate Pump $ 60 0 Firestat $ 75 0 Crankcase Heaters $ Steam Generator $ Gauge Panels $ R-407C $ Total Increase in Cost $1,960 0 Specification Control = $$$ 18

19 19 Spec Stopper (Ceiling Units) Belt Drive Fans –Standard with Data Aire –Liebert cost about $575

20 20 Justification Belt Drive Fans –Generates higher external static pressure to overcome duct losses

21 21 Spec Stopper (for Liebert) 4 Analog Inputs –Standard with Liebert –Data Aire *Cost about $250 * Example only; refer to PSG for current price

22 22 Reason to Omit 4 Analog Inputs –Seldom, if ever used –Increases cost –Only provide information, perform no useful function

23 23 Spec Stopper (for Liebert) Motor overload alarm –Liebert Cost about $100 –Data Aire *Cost about $300 to $400 * Example only; refer to PSG for current price

24 24 Reason to Omit Motor overload alarm –Redundant alarm No air flow alarm does same thing Internal overloads protect motor

25 25 Spec Stopper (for Liebert) Infrared Humidifier –Standard Liebert –Data Aire *Cost about $1,400 * Example only; refer to PSG for current price

26 26 Reason to Omit Infrared Humidifier –Efficiency 22% less efficient than steam generator –Maintenance Difficult and time consuming to clean –Indoor Air Quality Infrared has pan of standing water in air stream in violation of ASHRAE

27 27 Spec Stopper (for Liebert) Field split frame into 3 pieces –Standard Liebert DS –Data Aire *Cost about $1,300 / split * Example only; refer to PSG for current price

28 28 Reason to Omit Field split frame into 3 pieces –Spec only when required –Increases Data Aire cost needlessly

29 29 Spec Stopper (for Liebert) Self adjusting motor base –Not available from Data Aire 5 year warranty on drive train –Standard with Liebert –Data Aire adds 8% to our price

30 30 How to Handle Specify direct drive plug fans instead of warranty and self-adjusting motor base –Cost less –More efficient –No maintenance –No belt dust –Better airflow management

31 31 Spec Stopper (for Liebert) Semi-hermetic Compressors –Standard with Liebert –Data Aire *Cost about $2,500 * Example only; refer to PSG for current price

32 32 How to Handle Specify Scroll Compressors In Lieu of Semi-hermetic Compressors –Scrolls are 11.5% more efficient –Scrolls are More reliable by 5 to 1 –Scrolls are Less expensive

33 Liebert Data Aire 4 Analog Inputs $ 0 $ 250 Motor Overload Alarm $ 100 $ 300 Infrared Humidifier $ 0 $1,400 Split Frame $ 0 $1,300 5 Year Drive Train Warranty $ 0 $1,600 Semi-Hermetic Compressors $ 0 $2,500 Total Increase in Cost $ 100 $7,350 Specification Control = $$$ 33

34 34 Increased Liebert Cost by adding Data Aire Spec Stoppers $1,960 Reduced Data Aire Cost by Deleting Liebert Spec Stoppers $7,250 Specification Control = $$$

35 $ 8,860 Price Difference On Data Aire Series DX $ 5,835 Price Difference On Chilled Water Unit Specification Control = $$$ 35

36 We Are Just Getting Started! There Are More Ways to Lock up a Job! Specification Control = $$$ 36

37 37 Spec Stopper (for Liebert) Digital Scroll Compressors –Option with Liebert –Data Aire cannot do

38 38 How To Handle Digital Scroll Compressors –Proprietary Liebert is only CRAC manufacturer allowed to buy digital scroll. –Specify hot gas bypass instead Functionally equivalent –Not needed in a room with multiple 2 compressor units

39 39 Spec Stopper DAFC with factory mounted pumps –Standard Data Aire product –Liebert only offers free-standing pumps

40 40 Justification DAFC with factory mounted pumps –Less field labor –Single point power connection –Takes up less space

41 41 Sweet Spot Floor mounted DX equipment –Especially with 2 compressors Promote economy of DX systems Suggest use of dual cooling units Suggest use of a DX unit as a CW backup

42 42 Sweet Spot 10 ton and 13 ton ceiling units –Standard Data Aire product –Liebert does not offer

43 43 Special Plug fans in floor units –Data Aire *Cost about $1,000 to $1,500 net per fan –Available On Data Aire DX and CW units Both on up flow and down flow –Only On Liebert Chilled Water >= 30 tons Only on down flow * Example only; contact Data Aire for current price

44 44 Justification Plug fans in floor units –Up to 50% energy savings –Less than one year payback on cost of fans –No maintenance –No belt dust under floor –Excellent air flow management under floor

45 45 Special Condensing unit > 10 tons –Data Aire *Cost about $1,200 net –Liebert will not do * Example only; contact Data Aire for current price

46 46 Justification Condensing unit > 10 tons –Fewer service techs in the data room Improved security Fewer disruptions

47 47 Special R-410a –Data Aire *Cost, add 10% to price –Liebert will only offer R-407c * Example only; contact Data Aire for current price

48 48 Justification R-410a –All major manufacturers have made R-410a the standard –R-407c charge cannot be topped off When a leak is repaired entire charge must be recovered and circuit charged with new refrigerant –Refrigerant Cost R-407c costs 33% more than R-410a R-407c costs are rising and R-410a costs are falling

49 49 Special Dual power source with automatic power transfer switch –Data Aire *Cost about $1,400 net –Liebert does not like to do? Eliminates a single point of failure * Example only; contact Data Aire for current price

50 Special Condenser fans with EC Motors –Have not seen Liebert quote this –Stulz will supply them 50

51 Justification Condenser fans with EC Motors –Saves 40% of condenser fan energy –Increased motor reliability –Lower noise level at off peak loads 51

52 52 Special Stainless steel DARC cabinet –Data Aire *Cost about $600 net / fan section –Will Liebert do? –How much? * Example only; contact Data Aire for current price

53 Data Aire Is Flexible! Following Are Examples of Specials Reps Have Requested Specials 53

54 54 VFD mounted and wired High AIC disconnects TEFC Motors 2 condensate pumps with auto changeover Special location for electrical connections Special reheat kW Electrical Specials

55 55 Isolation damper control relays Various relays for special purposes Red/Blue/Yellow alarm beacon Mount and wire controls by others (CW only) Custom control sequence of operation Controls Specials

56 56 Alternate piping locations Copper fin coils Heresite coating on coils Stainless steel coil casing Special chilled water valves Special coil circuiting, row and fin count Dual chilled water or dual DX coils Coil Specials

57 57 Reverse blowers Aluminum panels on ceiling units Lead-lined acoustical insulation 16 gauge panels Double wall construction Cabinet Specials

58 58 Foil faced insulation Special length, width, and height Mirror image units Return air plenums on down flow units Plenums to hide duct on up flow units Cabinet Specials

59 59 Special filters V-bank filter sections Floor stands enclosed with insulated panels Factory painted ceiling units Totally special unit e.g. Exxon-Mobil unit Cabinet Specials