Presentation is loading. Please wait.

Presentation is loading. Please wait.

Common Electrical Hazards in the Workplace Including

Similar presentations


Presentation on theme: "Common Electrical Hazards in the Workplace Including"— Presentation transcript:

1 Common Electrical Hazards in the Workplace Including
Arc Flash

2 Introduction This material was produced under grant number SH F-12 from the Occupational Safety and Health Administration, U.S. Department of Labor. It does not necessarily reflect the views or policies of the U.S. Department of Labor, nor does mention of trade names, commercial products, or organizations imply endorsement by the U.S. Government. This material was produced by the Workplace Safety Awareness Council, a 501(c)(3) not-for-profit organization dedicated to safety in the workplace. For further information about the council or upcoming safety related training, please visit our website at or call us at (863)

3 What’s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection Association's (NFPA) National Electrical Code (NEC), NFPA On January 16, 1981, OSHA revised its Electrical standard with Part I of National Fire Protection Association's (NFPA) 70E On August 13, 2007, OSHA revised its Electrical standard to reference National Fire Protection Association's (NFPA) 70E NOTE: OSHA has decided not to base the final rule as a whole on NFPA 70E-2004, which was published on April 9, 2004, shortly after OSHA's proposal was published.

4 Common Hazards Common hazards when working with energized electrical equipment include: Electric Shock / Burns Blast Arc Flash Fast Fact: It doesn’t take much for human skin to burn – in fact an exposure of 203 F for just one-tenth of a second (6 cycles) is enough to cause a third degree burn!

5 GFCI Protection (b)(3)(i) Receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel. (b)(3)(i) All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel.

6 GFCI Protection (b)(3)(ii)(A) Receptacle outlets (including cord sets) that are not part of the permanent wiring of the building shall have ground-fault circuit-interrupter protection for personnel. Note: A cord connector on an extension cord set is considered to be a receptacle outlet if the cord set is used for temporary electric power. (b)(3)(ii)(A) All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel. Note 1 to paragraph (b)(3)(ii)(A) of this section: A cord connector on an extension cord set is considered to be a receptacle outlet if the cord set is used for temporary electric power. Note 2 to paragraph (b)(3)(ii)(A) of this section: Cord sets and devices incorporating the required ground-fault circuit-interrupter that are connected to the receptacle closest to the source of power are acceptable forms of protection.

7 Flexible Cords – Permitted Use
(g)(1)(ii)(A)-(L) Pendants; Wiring of fixtures; Connection of portable lamps or appliances; Portable and mobile signs; Elevator cables; Wiring of cranes and hoists; Appliances to permit removal for maintenance and repair Quiz Question (g)(1)(ii) Flexible cords and cables may be used only for: (g)(1)(ii)(A) Pendants; (g)(1)(ii)(B) Wiring of fixtures; (g)(1)(ii)(C) Connection of portable lamps or appliances; (g)(1)(ii)(D) Portable and mobile signs; (g)(1)(ii)(E) Elevator cables; (g)(1)(ii)(F) Wiring of cranes and hoists; (g)(1)(ii)(I) Appliances where the fastening means and mechanical connections are designed to permit removal for maintenance and repair; Pendant, or Fixture Wiring Portable lamps, tools or appliances Stationary equipment to facilitate interchange

8 Flexible Cords – Permitted Use
(g)(1)(ii)(A)-(L) Connection of stationary equipment to facilitate their frequent interchange; Prevention of the transmission of noise or vibration; Appliances where the fastening means and mechanical connections are designed to permit removal for maintenance and repair; Data processing cables approved as a part of the data processing system; Connection of moving parts; and Temporary wiring as permitted in paragraph (a)(2) of this section. Quiz Question

9 Prohibited Uses of Flexible Cords 1910.305(g)(1)(iv)(A)-(F)
As a substitute for the fixed wiring of a structure; Where run through holes in walls, ceilings, or floors; Where run through doorways, windows, or similar openings; Where attached to building surfaces; Where concealed behind building walls, ceilings, or floors; or Where installed in raceways, except as otherwise permitted in this subpart. Quiz Question (g)(1)(iv) Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: (g)(1)(iv)(A) As a substitute for the fixed wiring of a structure; (g)(1)(iv)(B) Where run through holes in walls, ceilings, or floors; (g)(1)(iv)(C) Where run through doorways, windows, or similar openings; (g)(1)(iv)(D) Where attached to building surfaces; Concealed behind or attached to building surfaces Substitute for fixed wiring Run through walls, ceilings, floors, doors, or windows

10 Flexible Cords (b)(3)(ii)(C)(3) Extension cords must be visually inspected before each use on any shift. Examine the cord for Missing grounding pin Damaged other jacket (tear in insulation) Possible internal damage (pinched cord) (b)(3)(ii)(C)(3) Each cord set, attachment cap, plug, and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired;

11 Grounding Pin (b)(3)(ii)(C)(4)(i) – (iii) Ensure that grounding pin on extension cords is in place and operable All equipment grounding conductors shall be tested for continuity: Before first use Before return to service (repairs) Before use after an incident that may have caused damaged and Intervals not to exceed three (3) months (b)(3)(ii)(C)(4)(i) All equipment grounding conductors shall be tested for continuity (b)(3)(ii)(C)(4)(ii) Each receptacle and attachment cap or plug shall be tested for correct attachment of the equipment grounding conductor. The equipment grounding conductor shall be connected to its proper terminal (b)(3)(ii)(C)(4)(iii) All required tests shall be performed before first use; before equipment is returned to service following any repairs; before equipment is used after any incident which can be reasonably suspected to have caused damage (for example, when a cord set is run over); and at intervals not to exceed 3 months, except that cord sets and receptacles which are fixed and not exposed to damage shall be tested at intervals not exceeding 6 months;

12 Splices (g)(2)(ii) Flexible cords may be used only in continuous lengths without splice or tap. (g)(2)(ii) Flexible cords may be used only in continuous lengths without splice or tap. Hard-service cord and junior hard-service cord No. 14 and larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. Note: Black electrical tape does not provide suitable insulation and is not acceptable

13 Flexible Cords (g)(2)(i) Durably marked as to type, side, and number of conductors Strain relief must be provided (g)(2)(i) A conductor of a flexible cord or cable that is used as a grounded conductor or an equipment grounding conductor shall be distinguishable from other conductors. Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, and STOO flexible cords and Types G, G-GC, PPE, and W flexible cables shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.) with the type designation, size, and number of conductors.

14 Inadequate Wiring Hazards
Using a portable tool with an extension cord that has a wire too small for the tool: The tool will draw more current than the cord can handle, causing overheating and a possible fire without tripping the circuit breaker The circuit breaker could be the right size for the circuit but not for the smaller-wire extension cord Wire Gauge WIRE Note that wire-gauge size is inversely related to the diameter of the wire. For example, a No. 12 flexible cord has a larger diameter wire than a No. 14 flexible cord. Wire gauge measures wires ranging in size from number 36 to 0 American wire gauge (AWG)

15 Minimum Depth of Working Space 1910.303(g)(1)(i)(A) Table S-1
Nominal voltage to ground Minimum clear distance for condition2 3 Condition A Condition B Condition C m ft Condition A -- Exposed live parts on one side and no live or grounded parts on the other side Condition B -- Exposed live parts on one side and grounded parts on the other side Condition C -- Exposed live parts on both sides Quiz Question

16 Labeling of Breakers Overcurrent devices or disconnecting devices:
shall be legibly marked to indicate its purpose shall be of sufficient durability to withstand the environment involved. (f)(2) Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. (f)(3) Durability of markings. The markings required by paragraphs (f)(1) and (f)(2) of this section shall be of sufficient durability to withstand the environment involved.

17 Cabinets, Boxes and Fittings 1910.305(b)(1)(i)
Conductors entering shall be protected Openings shall be effectively closed Cable is fastened within 12” from box or raceway (b)(1)(i) Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. (b)(2)(i) All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear

18 Cabinets, Boxes and Fittings 1910.305(b)(1)(i)
Conductors entering shall be protected Openings shall be effectively closed Cable is fastened within 12” from box or raceway (b)(1)(i) Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. (b)(2)(i) All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear

19 Cabinets, Boxes and Fittings 1910.305(b)(1)(i)
Conductors entering shall be protected Openings shall be effectively closed Cable is fastened within 12” from box or raceway (b)(1)(i) Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. (b)(2)(i) All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear

20 Cabinets, Boxes and Fittings 1910.305(b)(2)(i)
In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Quiz Question (b)(2)(i) All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear

21 Arc Flash Event A dangerous release of energy created by an electrical fault Release will contain: Thermal energy Acoustical energy Pressure wave Debris

22

23 Arc Flash Intensity Variables that effect the size and energy of an electric arc flash: Amperage Voltage Arc Gap Closure time Distance away from arc 3 phase v single phase Confined space

24 Arc Energy Basics Exposure energy expressed in cal/cm2
½ to 1 cal/cm2 = hottest part of lighter in 1 sec 1-2 calorie exposure will cause second degree burn on human skin Typical non-FR workwear can Arcs typically release 5-30 cals - energies of cals are not uncommon

25 Arc Flash Events Can reach 35,000 F Fatal burns >10 feet
Majority of hospital admissions are arc flash burns, not shock 30,000 arcs and 7000 burn injuries per year Over 2000 people admitted to burn centers yearly with severe arc flash burns

26 What Is Important Three factors are critical when discussing burns:
Extent (% of body burned – related to survivability) Severity (linked to quality of life) Location (linked to quality of life)

27 What Is a Burn? A chemical process which progressively injures skin; severity relates to depth 1st : redness, pain – not permanent 2nd: blistering – skin will regenerate 3rd: total skin depth destroyed. Will not regenerate – requires grafting 4th : Underlying muscle damaged

28 Burn Survival Burn percentage, more than severity, predicts survival because skin is infection barrier 2nd and 3rd degree break skin, providing an infection pathway Most hospital deaths 2-4 weeks post-exposure are infection (gram-neg staph)

29 Burn Survival Factors Odds of survival fall with total % burn
Odds of survival fall precipitously above 50% burn Odds of survival fall as age increases

30 Burn Injury Burn treatment requires approx. 1.5 days hospitalization per % burn Average hospitalization is 19 days, at costs exceeding $18,000/day Total hospitalization cost typically ranges from $200,000 to $750,000, with many over $1,000,000 USD

31 Deenergized Equipment
The most effective and fool-proof way to eliminate the risk of electrical shock or arc flash is to simply deenergize the equipment. . .

32 Lockout / Tagout A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed. (b)(2)(iii)(A) A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools. Note: Electric equipment that have been deenergized but have not been locked out or tagged shall be treated as energized.

33 Working Live OSHA has also made allowances for not deenergizing electrical equipment when it would increase current hazards or create additional hazards, for example: interruption of life support equipment, deactivation of emergency alarm systems, shutdown of hazardous location ventilation equipment, removal of illumination for an area. Working live is also allowable due to infeasibility of deenergization (i.e. testing of electric circuits)

34 Hot Work Requirements Employer must develop and enforce safety-related work practices to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts. These safety related work practices could include: Energized Electrical Work Permit Pre-work Job Briefing Personal Protective Equipment Insulated Tools Written Safety Program Qualified Person Training Flash Hazard Labeling

35 Definitions A number of “approach boundaries” exist and both qualified and non-qualified persons must understand these definitions. Quiz Question

36 Flash Protection Boundary
Flash Protection Boundary (outer boundary): The flash boundary is the farthest established boundary from the energy source. If an arc flash occurred, this boundary is where an employee would be exposed to a curable second degree burn (1.2 calories/cm2)

37 “Working Near Live Parts”
Limited Approach Boundary Limited Approach: An approach limit at a distance from an exposed live part where a shock hazard exists. “Working Near Live Parts” Occurs when any activity inside the Limited Approach Boundary is undertaken

38 Restricted Approach Boundary
Restricted Approach: An approach limit at a distance from an exposed live part which there is an increased risk of shock.

39 “Working On Live Parts”
Prohibited Approach Boundary Prohibited Approach (inner boundary): A distance from an exposed part which is considered the same as making contact with the live part. “Working On Live Parts” Occurs when coming in contact with live parts, including test equipment, body, PPE, tools etc. . .

40 Flash Protection Labeling
Arc Flash Hazard labeling must be posted which identifies: Approach boundaries PPE required

41 How to Determine Boundaries
NFPA Tables: Refer to NFPA 70E – 2000 Table or Table 130.7(C)99)(a) NFPA 70E – 2004. Pro: Easiest and quickest method Con: Provides the least amount of accuracy. Limited tasks are covered in tables

42 How to Determine Boundaries
Formula Method: NFPA 70 E and IEEE Standard 1584 provides formulas that can be used to accurately determine the approach boundaries. Pro: More accurate and all inclusive than NFPA tables Con: Is time consuming, requires an engineer level of expertise and is subject to human error. 

43 How to Determine Boundaries
Approach Calculator: IEEE and others have provided a spreadsheet based calculator to assist in determining approach boundaries. Pro: Quicker than formula method Con: Still requires detailed information about the equipment and circuit often requiring the use of an electrical engineer.

44 How to Determine Boundaries
Software: There exists on the market various software products that can simplify and expedite the approach boundary calculations. Pro: Creates one-line diagrams and arc flash labels based on data entered Con: Cost and equipment / circuit knowledge is still required often requiring an engineer.

45 Qualified Persons Qualified person: One who has received training in and has demonstrated skills and knowledge in the construction and operation of electric equipment and installations and the hazards involved.

46 Qualified Person Training 1910.332(b)(3)(i) – (iii)
Qualified persons shall at a minimum be trained in the following areas: The skills to distinguish exposed live parts from other parts of electric equipment. The skills to determine the nominal voltage of exposed live parts, and The clearance distances specified in (c) and the corresponding voltages to which the qualified person will be exposed. Quiz Question


Download ppt "Common Electrical Hazards in the Workplace Including"

Similar presentations


Ads by Google