1 SmartLetLoose/ONE Fire Extinction Board

2 SmartLetLoose/ONE Extinction Board Wiring SmartLine panel

3 Extinction Board Wiring SmartLight panel SmartLetLoose/ONE

4 Initial Wirings Balance MAN-EXT terminals with a 47k Ω resistance Balance STOP_EXT terminals with a 47k Ω resistance Balance PRESS terminals with a 47k Ω resistance SmartLetLoose/ONE

5 Initial Wirings SmartLetLoose/ONE If terminals arent balanced panel displays: Fault 01/03 Open I/O ManualExtinguish Extin.module Fault 02/03 Open I/O Lock extinguish Extin.module Fault 03/03 Open I/O Pressure switch Extin.module

6 Initial Wirings Balance PRE-EXT terminals with a 47k Ω resistance Balance RELEASED terminals with a 47k Ω resistance SmartLetLoose/ONE

7 Initial Wirings SmartLetLoose/ONE If terminals arent balanced panel displays: Fault 01/02 Open I/O Pre-extinguish Extin.module. Fault 02/02 Open I/O Released Extin.module

8 Electrovalve Wiring Electrovalv e 24V SmartLetLoose/ONE

9 If terminals arent connected panel displays: Fault 01/01 Open I/O Valve output Extin.module Electrovalve Wiring

10 Manual Extinguish Connect a callpoint or a generic NO contact to have a manual Extinguish input NO contact 15k Ω resistance 47k Ω resistance SmartLetLoose/ONE

11 Stop-Extinguish Connect a callpoint or a generic NO contact to have a manual Stop- Extinguish input NO contact 15k Ω resistance 47k Ω resistance SmartLetLoose/ONE

12 Stop-Extinguish If fire extinguishant system has been stopped, R terminal closes to GND: it can activate a device (eg a led) +24V +- Device SmartLetLoose/ONE

13 Pressure Switch A generic NO contact connected to PRESS teminals can be used as: NO contact 15k Ω resistance 47k Ω resistance SmartLetLoose/ONE - Supervisory: to monitor gas pressure - From pressure: to confirm that gas cylinders are empty - From flow detector: to confirm that gas has be released

14 Pre-Extinguish PRE-EXT output (terminals 10-11) is activated on Pre-Extinguish: it can activate some devices SmartLetLoose/ONE 47 k Ω End of Line resistance on the last device

15 Pre-Extinguish SmartLetLoose/ONE Fault 01/01 Short I/O Pre-extinguish Extin.module If panel displays Short I/O Pre- Extinguish it will need connect a diode in series (if devices havent it) 47 k Ω End of Line resistance on the last device

16 Released RELEASED output (terminals 12-13) is activated when gas extinguishant is released: it can activate some devices. SmartLetLoose/ONE 47 k Ω End of Line resistance on the last device

17 Released SmartLetLoose/ONE Fault 01/01 Short I/O Released Extin.module If panel displays Short I/O Released it will need connect a diode in series (if devices havent it) 47 k Ω End of Line resistance on the last device

18 Extinction Board Configuration Extinction Board have to be configured from panel SmartLetLoose/ONE Extinction Board Configuration

19 Extinction Board have to be configured from panel SmartLine Panel Enable panel programming phase SmartLetLoose/ONE

20 Extinction Board Configuration Extinction Board have to be configured from panel SmartLine Panel Control Panel IN PROGRAMMING Ver: /01/12 17:45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Acquire int.bus Acquire ext.bus Current Devices Extin.module O Expansion O Ok to execute Current Devices Extin.module 1 Expansion O Ok to execute SmartLetLoose/ONE

21 Extinction Board Configuration Extinction Board have to be configured from panel SmartLight Panel Enable panel programming phase SmartLetLoose/ONE

22 Extinction Board Configuration Extinction Board have to be configured from panel SmartLight Panel Panel IN PROGRAMMING Ver: /01/12 17:45 Settings Disablement Maintenace Programming Configuration Progr.Point Progr.Zone Progr. Timer Loop Bus Extinguish board O Smart Level O Repeater O Ok to continue Extinguish board 1 Smart Level O Repeater O Ok to continue SmartLetLoose/ONE

23 Programming Enable panel programming phase SmartLetLoose/ONE Programming Extinction board is programmed the same way both from SmartLine panel and from SmartLight panel

24 Programming Control Panel IN PROGRAMMING Ver: /01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Zone mask: Zone 01YES Zone 02YES Zone 03YES Mode: At least 2 SmartLetLoose/ONE YES: Zone activates extinguish commands NO: Zone doesnt activate extinguish commands At least 1: The extinguishant gas release will activate if at least one of the selected zones go into alarm status At least 2: The extinguishant gas release will activate if at least two of the selected zones go into alarm status All zones: The extinguishant gas release will activate if all selected zones go into alarm status

25 Programming Control Panel IN PROGRAMMING Ver: /01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Zone mask: Zone 01YES Zone 02YES Zone 03YES Confirm exting. Do not confirm SmartLetLoose/ONE Do not confirm: extinguishment module doesnt await confirmation Wait for press.: extinguishment module awaits confirmation from pressure switch Wait for flow: extinguishment module awaits confirmation from flow detector

26 Programming Control Panel IN PROGRAMMING Ver: /01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Zone mask: Zone 01YES Zone 02YES Zone 03YES Pressure switch Supervisory SmartLetLoose/ONE Supervisory: PRESS input monitors gas pressure From pressure: PRESS input confirm that gas cylinders are empty From flow det.: PRESS input confirm that gas has be released

27 Programming Control Panel IN PROGRAMMING Ver: /01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Zone mask: Zone 01YES Zone 02YES Zone 03YES Pressure switch Supervisory SmartLetLoose/ONE Other programming T.pre-extinct 00 min. 10 sec Pre-extinction time T. extinguish 00 min. 02 sec T. extinguish Extinguish time If it is undefined, valve switch will be open until reset T. pre-ext. man 00 min. 00 sec Manual Pre-extinction time T.Confirm ext. 00 min. 05 sec Delay between valve switch activation and confirmation T.Gap discharge 00 min. 05 sec Pause between one gas discharge and another in the event of non-confirmation

28 Advanced Programming SmartLetLoose/ONE - Lock extinguish when the room has open doors SmartLine Panel

29 Advanced Programming SmartLetLoose/ONE Connect the series of NC doors contact between I/O and - terminals

30 Advanced Programming SmartLetLoose/ONE Program I/O Line as Extinction control Input Stop Extinction Swap Alarm-Fault bands

31 Advanced Programming Control Panel IN PROGRAMMING Ver: /01/12 17:45 Configuration Progr. Zone Progr. Output Progr. Timer SmartLetLoose/ONE - Lock extinguish when the room has open doors SmartLine panel Programming from panel 01

32 Advanced Programming Control Panel IN PROGRAMMING Ver: /01/12 17:45 Configurazione Progr. Zone Progr. Uscite Progr. Timer SmartLetLoose/ONE - Lock extinguish when the room has open doors 01

33 Advanced Programming SmartLetLoose/ONE - Lock extinguish when the room has open doors I.EXTINGUISH Lock extinguish NC input YES Program NC input YES SmartLine panel Control Panel IN PROGRAMMING Ver: /01/12 17:45 Configurazione Progr. Zone Progr. Uscite Progr. Timer 01


Download ppt "SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel."