1 ICC Codes w/WI Amendments International Energy Conservation Code With Wisconsin Amendments zTraining As Developed by Randy Dahmen, WI PE John Spalding, WI Architect zWI Dept. of Commerce, Safety & Buildings Division, Madison, WI & La Crosse, WI zWeb Site: zDSPS.STATE.WI.US/SB

2 ICC Codes w/WI Amendments2 International Energy Conservation Code (IECC) Breakdown zCh. 1 Administration zCh. 2 Definitions zCh. 3 Climate Zones zCh. 4 Residential Energy Efficiency zCh. 5 Commercial Energy Efficiency zCh. 6 Reference Standards

3 ICC Codes w/WI Amendments3 Fenestration U-factor zHow to meet the requirement yFenestration product rating in accordance to NFRC 100 xLabeled & certified by the manufacturer Designer to define manufacturer on plans and provide product sheets demonstrating compliance yNon NFRC 100 rated fenestration xDefault Glazed Fenestration U-factor Table (1) IECC

4 ICC Codes w/WI Amendments4 ASHRAE Fundamental Data Comm zInformation on thermal properties, performance of building envelope sections, and components and heat transfer shall be obtained from ASHRAE Handbook of Fundamentals. yException: xLaboratory Testing results xSee Comm for acceptable test methods

5 ICC Codes w/WI Amendments5 IECC Offers Multiple Building Envelope Compliance Options For: zCh. 4 Low Rise Residential Buildings (< 3 stories) (Non-Transient--Do NOT use with for Hotels, Motels, etc.) zCh. 5 Commercial (Any Height) and High Rise Residential Buildings (> 4 Stories)

6 ICC Codes w/WI Amendments6 Certificate Comm zThere is a Wisconsin amendment that does not require the installation of a permanent energy certificate.

7 ICC Codes w/WI Amendments7 Insulation & Fenestration Requirements by Climate Zone Table Insulation and Fenestration Requirements by Component a a. R-values are minimums, U-factors and SHGC are maximums, R-19 batts compressed into a nominal 2 x 6 framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value. b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration. c. 15/19 means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. 15/19 shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. 10/13 means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall. d. R-5 shall be added to the required slab edge R-values for heated slabs. Insulation depth shall be the depth of the footing or 2 feet, whichever is less in Zones 1 through 3 for heated slabs. e. There are no SHGC requirements in the Marine Zone. f. Basement wall insulation is not required in warm-humid locations as defined by Figure and Table g. Or insulation sufficient to fill the framing cavity, R-19 minimum. h means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25 percent or less of the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25 percent of exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2. i. The second R-value applies when more than half the insulation is on the interior of the mass wall. j. For impact rated fenestration complying with Section R of the IRC or Section of the IBC, maximum U-factor shall be 0.75 in Zone 2 and 0.65 in Zone 3.

8 ICC Codes w/WI Amendments8 Air Sealing and Insulation IECC z2 options to demonstrate compliance yWhen tested air leakage is < 7 ACH when tested with a blower door at pressure of 33.5 psf (Section ) xTesting after rough in and installation of building envelope penetrations yWhen items listed in Table , applicable to the method of construction, are field verified (Section )

9 ICC Codes w/WI Amendments9 Fireplaces IECC zNew wood-burning fireplaces shall have gasketed doors & outdoor combustion air.

10 ICC Codes w/WI Amendments10 Programmable Thermostat Controls IECC zIf primary heating system is a forced-air furnace yAt least one programmable thermostat/dwelling unit yCapability to set back or temporarily operate the system to maintain zone temperatures xdown to 55ºF (13ºC) or xup to 85ºF (29ºC) yInitially programmed with: xheating temperature set point no higher than 70ºF (21ºC) and xcooling temperature set point no lower than 78ºF (26ºC) Mandatory Requirements

11 ICC Codes w/WI Amendments11 Ducts Insulation & Sealing IECC & Comm zInsulation (Prescriptive) yDucts outside the building envelope: R-8 yAll other ducts: R-6 zSealing (Mandatory) yJoints & seams shall comply with IRC, Section M zBuilding framing cavities shall not be used as supply ducts Mandatory Requirements

12 ICC Codes w/WI Amendments12 Ducts Insulation & Sealing Comm (2) zAll ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed. Joints & seams shall comply with IMC section 603.9

13 ICC Codes w/WI Amendments13 Piping Insulation IECC & zMinimum R-3 required on yHVAC systems xException: Piping that conveys fluids between 55 & 105°F zMinimum R-2 required on yAll circulating domestic hot water systems xSystems also require a readily accessible manual switch Mandatory Requirements

14 ICC Codes w/WI Amendments14 Ventilation & Equipment Sizing IECC & zEquipment Sizing yIECC references Section M of the IRC yLoad calculations determine the proper capacity (size) of equipment yCalculations shall be performed in accordance with ACCA Manual J OR yother approved methods Mandatory Requirements

15 ICC Codes w/WI Amendments15 Snow Melt System Controls IECC & zSnow- and ice-melting system controls yShall include xAutomatic controls capable of shutting off the system when the pavement temperature > 50ºF and no precipitation is falling; and xAutomatic or manual control that will allow shutoff when the outdoor temperature is > 40ºF Mandatory Requirements

16 ICC Codes w/WI Amendments16 Snow Melt System Controls IECC &

17 ICC Codes w/WI Amendments17 Pool Covers IECC 403.9/Comm & / Comm 0504 zThese sections to be amended so that heated pools do NOT require pool covers

18 ICC Codes w/WI Amendments18 Lighting Equipment (Prescriptive) IECC zA minimum of 50% of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps zDefinition of high-efficacy lamp yCompact fluorescent lamps T-8 or smaller diameter linear fluorescent lamps, or lamps with a minimum efficacy of: x60 lumens/W for lamps > 40 watts, x50 lumens/W for lamps > 15 watts up to 40 watts, and x40 lumens/W for lamps < 15 watts or less.

19 ICC Codes w/WI Amendments19 Simulated Performance Alternative Comm zWisconsin Accepts use of REScheck when set for 2009 IECC zDoes NOT include both envelope and equipment for trade-offs.

20 ICC Codes w/WI Amendments20 What are My Building Envelope Options for Complying with the IECC? zSection 502 of the IECC (Prescriptive Approach) xUse for < 40% of gross wall area in vertical fenestration xUse for < 3% of gross roof area in skylights zCOMcheck Computer Program (per Comm ) zSection 506 Total Building Performance Approach zASHRAE/IESNA Standard ySection Application requires 90.1 to be used in its ENTIRETY (Envelope, Lighting, Mechanical) if used as an alternate compliance path

21 ICC Codes w/WI Amendments21 Zone 6 Zone 7

22 ICC Codes w/WI Amendments22 Changes to IECC Tables & 502.2(1) zTable now separated by occupancy type yNon-Group R occupancies use All other column yGroup R occupancies use Group R column

23 ICC Codes w/WI Amendments23 Compliance with Chapter 5 Prescriptive Approach

24 ICC Codes w/WI Amendments24 Roof insulation should be installed Properly…

25 ICC Codes w/WI Amendments25 Compliance with Chapter 5 Prescriptive Approach

26 ICC Codes w/WI Amendments26 Hot Gas Bypass (common in large computer rooms) IECC zCooling systems cant use Hot Gas Bypass unless system designed w/ yMultiple steps of unloading; OR yContinuous capacity modulation zCapacity limited per Table yException: Unitary packaged systems w/ cooling capacities < 90,000 Btu/h Rated Capacity Maximum Hot Gas Bypass Capacity (% of total capacity) 240,000 Btu/h 50% > 240,000 Btu/h 25%

27 ICC Codes w/WI Amendments27 Hot Gas Bypass IECC (Graph via Brian Kammers, AAON Inc.)

28 ICC Codes w/WI Amendments28 Mandatory Requirements – Loading Dock Weatherseals IECC zCargo doors & loading dock doors shall be equipped with weather seals to restrict infiltration when vehicles are parked in the doorway zNot reqd if adjacent to unconditioned spaces w/insulated separations

29 ICC Codes w/WI Amendments29 Mandatory Requirements –Vestibules IECC Vestibules on Primary Entrance Doors zReqd to reduce infiltration into spaces zReqd on entrance doors leading into spaces 3,000 ft 2 zDoors MUST have self-closing devices zExceptions yDoors from a guest room or dwelling unit yDoors used primarily for vehicular movement, materials handling & adjacent personnel doors yNot reqd if adjacent to unconditioned spaces w/insulated separations to conditioned spaces

30 ICC Codes w/WI Amendments30 Mandatory Requirements –Vestibules IECC Conditioned Space > 3,000 FT 2 Exempted Revolving Door Vestibule w/Self- Closing Doors

31 ICC Codes w/WI Amendments31 Ch. 5 Commercial Bldgs (Any Height) & High Rise Residential Buildings (> 4 Stories) IECC 501 & Comm zASHRAE may be used in its entirety in place of the 2009 IECC requirements for satisfying ALL of the following topics: yIECC 502 Building Envelope yIECC 503 Building Mechanical Systems yIECC 504 Service Water Heating yIECC 505 Lighting

32 ICC Codes w/WI Amendments32 Ch. 5 Commercial Bldgs (Any Height) & High Rise Residential Buildings (> 4 Stories) IECC 501 & Comm zDesigners may NOT mix & matchie. Lighting & Building Envelope requirements from ASHRAE, with Bldg Mechanical Systems & Service Water Heating from IECC. The design must be COMPLETELY based on either the IECC or ASHRAE for ALL topics referenced. yDept. review will default to IECC, unless designer indicates otherwise on plans.

33 ICC Codes w/WI Amendments33 Demand Controlled Ventilation IECC zDemand Control Ventilation is reqd for spaces >500 sf and with an avg. occupant load of 40 per1,000 sf of floor area and served by systems w/one or more of the following: yAn air-side economizer; yAutomatic modulating control of the outdoor air damper; or yA design outdoor airflow > 3,000 cfm xExceptions

34 ICC Codes w/WI Amendments34 Demand Controlled Ventilation IECC zSequencing & all associated controls shall be explicitly addressed on the HVAC plan set. zAcceptable Example: yThe HVAC system shall operate & distribute outdoor air at acceptable levels (as justified by the designer and determined acceptable by the Dept.), when the space is occupied, immaterial if the CO 2 sensor has met its operational set-point (to be clearly defined on the plans). Sensor to activate additional outdoor air over baseline yExceptions: Natural ventilation or other listed code exception

35 ICC Codes w/WI Amendments35 Demand Controlled Ventilation IECC zAcceptable Example: yFan & HVAC system serving room or space only operates so as to meet set point temperature when not occupied yOccupancy sensor recognizes room is occupied, opens outside air damper, continuously provides defined amount of outdoor air until determined that the room or space is no longer occupied

36 ICC Codes w/WI Amendments36 Demand Controlled Ventilation IECC zAcceptable Example: yIn those buildings with a key card entry system, the system could account for all occupants, and provide outdoor air in amounts proportional to the number of people recognized as being located within the bldg y(7.5 cfm of outdoor air/person x # of people)

37 ICC Codes w/WI Amendments37 Demand Controlled Ventilation IECC zAcceptable Example: yPlans could indicate that the HVAC system will distribute outdoor air when the room or space is occupied. The content of CO 2 is to be compared between the relief air and the outdoor air. If the difference, as measured in ppms, exceeds the predefined set-point as justified to the Dept. and found acceptable, additional outdoor air is to be distributed.

38 ICC Codes w/WI Amendments38 Demand Controlled Ventilation IECC zUnacceptable Examples: yPlans indicate that the HVAC system will ONLY distribute outdoor air when a pre-defined CO 2 set-point is met. yPlans indicate the use of CO 2 sensors but do NOT define the how the sensors are to be used by way of a sequence of operation.

39 ICC Codes w/WI Amendments39 Piping Insulation IECC All piping serving heating or cooling system must be insulated in accordance with Table shown below. Exceptions (R-5.5) (R-11.1) (R-7.4) (R-5.5)

40 ICC Codes w/WI Amendments40 Heating Outside a Building IECC zSystems providing heat outside a building shall be radiant systems. zSystems shall be controlled by an occupancy sensing device or timer switch, so that the system is automatically de-energized when no occupants are present

41 ICC Codes w/WI Amendments41 Economizers IECC/COMM Table zUnless a listed exception is met (exception #1 is not viable), Economizers are required for : ySplit systems & water source heat pumps > 54,000 Btu/h Split Systems (furnace & condenser similar to those found in homes, small businesses) yAll other systems > 33,000 Btu/h xRooftop units, built-up VAV reheat/single fan dual duct, etc.

42 ICC Codes w/WI Amendments42 Economizers IECC /COMM Table & IECC 501.2/Comm IECC Economizer Reqts IECC / Comm (8)&(9) Economizer Reqts IECC 501.2/ Comm (2)/ Comm (8)&(9) ALL Mechanical Building System Requirements Per 2009 IECC ALL Building System Reqts Per ASHRAE MUST be indicated on BOTH Bldg & HVAC Plans 1 Exception 9 Exceptions

43 ICC Codes w/WI Amendments43 Economizers IEBC/COMM , , , IECC/COMM Table z Where a single room or space is supplied by multiple air systems, the aggregate capacity of those systems shall be used in applying the requirement (ie. for economizers) yIf the room is served by 2 split furnace/condenser systems, the total cooling capacity for the aggregate systems are referenced when determining when an economizer is required to be installed

44 ICC Codes w/WI Amendments44 Low-Rise Residential Buildings IECC zIECC Chapter 4 yIn the residential portions of the building, a minimum of 50% of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps. yBasically, the code requires 50% of the lamps to incorporate compact fluorescents, long tube fluorescents, LED etc, but NOT incandescent.

45 ICC Codes w/WI Amendments45 High Rise Residential Bldgs IECC zIECC Chapter 5 yUnique requirement for High Rise Residential Bldgs x> 3 stories above grade, and x> 3 dwellings or more zLighting within dwelling units where 50% or more of the permanently installed interior light fixtures are fitted with high efficacy lamps.

46 ICC Codes w/WI Amendments46 Lighting Code Application IECC 505 z1) Determine Required Controls z2) Determine Power Allowance in watts for interior and exterior use (add base site allowance for exterior allowance per IECC ) z3) Determine Actual Lighting Installation (inclusive of ballasts) in watts for the interior and exterior of the building z4) Compare--Actual installation wattage to be < Power allowance as applicable to interior and exterior use

47 ICC Codes w/WI Amendments47 IECC Interior Controls IECC zIECC Interior lighting controls zIECC Lighting reduction controls zIECC Automatic lighting shutoffs zIECC Daylight zone controls zIECC Sleeping unit controls zIECC Exterior lighting controls

48 ICC Codes w/WI Amendments48 IECC Interior Controls IECC / COMM (1) zDaylight Zone control required for ySpaces > 250ft 2 ; and ySpaces with a Lighting Power Density > 0.6W/ft 2; & - Spaces containing 3 or more light fixtures zDaylight Zones to have separate controls yVertical & horizontal daylight areas separately switched from general area lighting yMust apply lighting reduction controls as per IECC sec xNote – controlling all luminaires using daylighting controls is acceptable.

49 ICC Codes w/WI Amendments49 IECC Interior Controls IECC zDaylight Zone Vertical Glazing (windows): Ceiling Height Opaque Partition 2´ Daylight Zone Boundary 15´ S Daylight Zone Luminaires S

50 ICC Codes w/WI Amendments50 IECC Interior Controls IECC zDaylight Zone: Horizontal Glazing (skylights): Daylight Zone 10´

51 ICC Codes w/WI Amendments51 IECC Interior Power Req. IECC Table Footnote b Footnote b for Additional Retail Lighting Use it or Lose it Interior Lighting Power Allowances (ILPA) zCalculate Additional lighting power as follows: Additional Interior Lighting Power Allowance = 1,000 watts + (Retail Area 1 x 0.6 W/ft 2 ) + (Retail Area 2 x 0.6 W/ft 2 ) + (Retail Area 3 x 1.4 W/ft 2 ) + (Retail Area 4 x 2.5 W/ft 2 )

52 ICC Codes w/WI Amendments52 IECC Interior Power Req. IECC Table Footnote b zWhere: yRetail Area 1 = Floor area for all products not listed in Retail Areas 2, 3 or 4; yRetail Area 2 = Floor area used for the sale of vehicles, sporting goods and small electronics; yRetail Area 3 = The floor area used for the sale of furniture, clothing, cosmetics and artwork; yRetail Area 4 = Floor area used for the sale of jewelry, crystal and china. xNote: Other merchandise categories are permitted to be included in Retail Areas 2 through 4 based on justification provided to the Dept. deemed as reasonable.

53 ICC Codes w/WI Amendments53 IECC Interior Power Req. IECC Table Footnote b zAdditional Power Allowance Rules: yArea must be the display area and NOT the floor area of the space yMust be switched on separate circuits from that of other general lighting yMust be in addition to general lighting

54 ICC Codes w/WI Amendments54 IECC Exterior Power Req. IECC & zIECC 2009 & ASHRAE 2007 are equivalent yApplies to lighting powered through the building service xIECC Exception - low voltage landscape lighting yAll exterior luminaires > 100 W shall have an efficacy of 60 L/W unless controlled by a motion sensor (unless it is exempted)

55 ICC Codes w/WI Amendments55 IECC Exterior Lighting Zones IECC Table (1)] Lighting Zone Description 1Developed areas of national parks, state parks, forest land, & rural areas 2Areas predominantly consisting of residential zoning, neighborhood business districts, light industrial w/limited nighttime use & residential mixed use areas 3All other areas 4High-activity commercial districts in major metropolitan areas as designated by the local land use planning authority

56 ICC Codes w/WI Amendments56 Zone 1Zone 2Zone 3Zone 4 Base Site Allowance 500 W600 W750 W1300 W Tradable Surfaces Uncovered Parking Areas Parking areas and drives0.04 W/ft W/ft W/ft W/ft 2 Building Grounds Walkways less than 10 ft wide 0.7 W/linear foot 0.8 W/linear foot 1.0 W/linear foot Walkways 10 ft wide or greater 0.14 W/ft W/ft W/ft 2 Plaza areas, Special Feature Areas Stairways0.75 W/ft W/ft 2 Pedestrian Tunnels0.15 W/ft W/ft W/ft 2 IECC Exterior Lighting Zones

57 ICC Codes w/WI Amendments57 Zone 1Zone 2Zone 3Zone 4 Tradable Surfaces Building Entrances and Exits Main entries 20 W/linear ft of door width 30 W/linear ft of door width Other doors 20 W/linear ft of door width Entry Canopies0.25 W/ft W/ft 2 Sales Canopies Free-standing & attached 0.6 W/ft W/ft W/ft 2 Outdoor Sales Open areas (including vehicle sales lots)0.25 W/ft W/ft W/ft 2 Street frontage for vehicle sales lots in addition to open area allowance No Allowance10 W/linear ft 30 W/ linear ft

58 ICC Codes w/WI Amendments58 Zone 1Zone 2Zone 3Zone 4 Non- Tradable Surfaces Building Facades No allowance 0.1 W/ft 2 for each illuminated wall or surface or 2.5 W/linear ft for each illuminated wall or surface length 0.15 W/ft 2 for each illuminated wall or surface or 3.75 W/linear ft for each illuminated wall or surface length 0.2 W/ft 2 for each illuminated wall or surface or 5.0 W/linear ft for each illuminated wall or surface length Automated teller machines & night depositories 270 W per location plus 90 W per addl ATM per location Entrances and gatehouse inspection stations at guarded fac W/ft 2 of covered & uncovered area Loading areas for law enforcement, fire, ambulance & other emergency service vehicles 0.5 W/ft 2 of covered & uncovered area Drive-up windows/doors 400 W per drive-through Parking near 24-hour retail entrances 800 W per main entry

59 ICC Codes w/WI Amendments59 Simulated Performance Alternative Comm zWisconsin Accepts use of COMcheck when set for 2009 IECC zDoes NOT include both envelope and equipment for trade-offs Note: Lighting controls are not adequately addressed via Comcheck, thus the designer is still responsible to address by other means