Corrosion of Padmount Equipment SWEDE Conference Michael Navarro May 2006.

Similar presentations


Presentation on theme: "Corrosion of Padmount Equipment SWEDE Conference Michael Navarro May 2006."— Presentation transcript:

1 Corrosion of Padmount Equipment SWEDE Conference Michael Navarro May 2006

2 2 TXU Electric Delivery Serves 402 cities in Texas - 3M Electric Delivery Points

3 3 New Installation

4 4 Example of Corrosion - Transformer

5 5

6 6 Change Out - Transformer Missed opportunity to correct problem

7 7 Example of Corrosion - Transformer

8 8

9 9

10 10 Example of Corrosion - Switchgear

11 11 Sprinkler Systems Fertilizer Pipelines Hard Water Below Grade, Standing in Water Heat Soil Conditions Accelerants of Corrosion

12 12 Trial & Error

13 13 Transformers - Complete overhaul of padmount transformer location, to include replacing with stainless steel transformer  Impacts –Cost Standard 50KVA Minipad - $1,100 Stainless Steel - $1,400 Change-Out Labor- $400 Spill, Clean-up, Disposal - $1,250  Customer Satisfaction  Lost Revenue (??) TXU Electric Delivery – Current Solution

14 14 Manufacturer’s – Transformer Cabinet Stainless Steel Standard

15 15 Stainless Steel – Transformer Cabinet

16 16 Switchgear Costs:  Base Spacer/Skirt –Mild Steel (Standard) - $1,000 –Stainless Steel - $1,600  Switchgear w/o Base Spacer/Skirt –Standard Cabinet - $10,000 –Stainless Steel – 4 to 5 times higher TXU Electric Delivery – Current Solution

17 17 Switchgear With 12” Skirt

18 Corrosion of Padmount Equipment SWEDE Conference Michael Navarro May 2006