1 FreeWave I/O for Rockwell
Curt Goldman Market Manager, Utilities Randy Maes Rockwell Specialist Bret Dianich Western Region BDE Nichole Pettway Eastern Region BDE February 27, 2012

2 Application examples

3 FreeWave I/O for Rockwell Agenda
Technology Overview FreeWave I/O Products: I/O Expansion Applications for FreeWave I/O and Rockwell Compatibility Between Allen-Bradley PLC’s and FreeWave I/O © 2011 FreeWave Technologies, Inc. 3/25/2017

4 FreeWave I/O for Rockwell: Technology Overview

5 FreeWave I/O for Rockwell Technology Overview
What is Wireless I/O? Replaces wires with wireless radio frequency technology to measure sensor outputs and control process elements using digital and analog signals FreeWave has the industry’s best radios for frequency-hopping spread spectrum radios for unlicensed frequencies and reliable licensed frequencies with distances over 60 miles © 2011 FreeWave Technologies, Inc. 3/25/2017 5

6 FreeWave I/O for Rockwell Technology Overview
What are the benefits of Wireless I/O? Wireless I/O saves time and money in engineering, material, installation, commissioning, logistics, maintenance, diagnostics, permitting and equipment lifetime. Wireless I/O is available for use with free or licensed radio frequencies and implies protection by the FCC Wireless I/O provides security, reliability and ease of use to automated measurement and control systems © 2011 FreeWave Technologies, Inc. 3/25/2017 6

7 FreeWave I/O for Rockwell Technology Overview
What do we measure? Sensor output for pressure, level, flow, temperature, chemicals, etc. Raw inputs for emergency stop, battery voltage, temperature, etc. What do we control? Relays, valves, latches, pumps, alarms, actuators, etc. © 2011 FreeWave Technologies, Inc. 3/25/2017 7

8 FreeWave I/O for Rockwell

9 Wireless I/O for Rockwell
I/O Expansion Modular, expandable I/O for wireless and wired applications Up to 192 I/O points at a single location without adding more radios Add I/O to any PLC, RTU or serial Modbus device © 2011 FreeWave Technologies, Inc. 3/25/2017 9

10 Wireless I/O for Rockwell
Key Features of I/O Expansion Maximum analog input reading error of 0.10% across entire temperature range 12 I/O channels per module Supports 4 to 20 mA, 1 to 5 V and 0 to 10 V sensors Non-isolated digital outputs drive 1 A and isolated relay digital outputs drive 2 A Integrated DIN-rail mounting clip Operational temperature range from -40 to 75 °C © 2011 FreeWave Technologies, Inc. 3/25/2017 10

11 Wireless I/O for Rockwell
Wired I/O Expansion

12 Wireless I/O for Rockwell
Wireless I/O Expansion

13 FreeWave I/O for Rockwell: Applications Electric Power Water Purification Wastewater Treatment

14 FreeWave I/O for Rockwell Applications
Typical Applications in Electric Power: Circuit breaker monitoring Transformer condition monitoring Switch monitoring © 2011 FreeWave Technologies, Inc. 3/25/2017 14

15 FreeWave I/O for Rockwell Applications
Typical Applications with Water: Pump control * Water tower monitoring * Irrigation © 2011 FreeWave Technologies, Inc. 3/25/2017 15

16 FreeWave I/O for Rockwell Applications
Typical Applications with Wastewater: Lift Stations * Water quality monitoring Chemical pumps © 2011 FreeWave Technologies, Inc. 3/25/2017 16

17 FreeWave I/O for Rockwell Applications

18 FreeWave I/O for Rockwell Applications
Pump Control Keep water tanks at purification plant input full during peak usage times Reservoirs and water tanks can be separated by many miles Manual pump operations are costly and inefficient © 2011 FreeWave Technologies, Inc. 3/25/2017 18

19 FreeWave I/O for Rockwell Applications
Pump Control with Wireless I/O In the main control room: Serial radio, Programmable Logic Controller (SLC), Human Machine Interface In the pump house: Serial I/O radio, variable frequency drive (PowerFlex), pressure transmitter, flow meter At the water tank: Serial I/O radio, level meter, pressure, flow meter © 2011 FreeWave Technologies, Inc. 3/25/2017 19

20 FreeWave I/O for Rockwell Applications
Benefits of Pump Control with Wireless I/O Monitor tank level to ensure supply during peak demand Monitor line pressure throughout the pipeline Control the variable frequency drive based on the reported flow rate when the pump is running Adds reliability with real-time measurements and controls wirelessly Reliable, flexible, cost-effective and scalable system for long- range systems © 2011 FreeWave Technologies, Inc. 3/25/2017 20

21 FreeWave I/O for Rockwell Applications
Water Tower Monitoring Pressure must be monitored for water towers providing distribution line pressure Water level must be monitored for water towers providing storage Manual reporting of water tower level and pressure can be hazardous and unreliable © 2011 FreeWave Technologies, Inc. 3/25/2017 21

22 FreeWave I/O for Rockwell Applications

23 Compatibility

24 FreeWave I/O for Rockwell Applications
Benefits of Water Tower Monitoring with Wireless I/O: Allows real-time reporting of water tower level, water tower temperature and line pressure Provides alarm capabilities from the water tower Increases employee efficiency Extends the range of the wireless SCADA network © 2011 FreeWave Technologies, Inc. 3/25/2017 24

25 FGR2-IO, Modbus RTU and Allen-Bradley PLC’S

26 Compatibility

27 FreeWave I/O for Rockwell Applications
Lift Stations Lift stations fill collection locations at the input of the wastewater treatment process Manual monitoring of sewage lift stations can easily result in overflows Wells with sewage stored over a long time can succumb to septic leakage © 2011 FreeWave Technologies, Inc. 3/25/2017 27

28 PLC overview

29 FreeWave I/O for Rockwell Applications
Benefits of Lift Station with Wireless I/O Automatic alarm capabilities notifies of overflow risk Continuous reporting of well level communicates excessive storage times of sewage and indicates septic risk Increases employee efficiency © 2011 FreeWave Technologies, Inc. 3/25/2017 29

30 FGR2-IO, Allen-Bradley compatibility
Micro 800 Family Micro 830 Micro 850 (when released) MicroLogix 1100 1200 1400 1500 SLC 5/03 5/04 5/05 CompactLogix 1769-L23 1769-L23E 1769-L31 1769-L32E 1769-L32C 1769-L35E 1769-L35CR 1769-L43 1769-L45 © 2011 FreeWave Technologies, Inc. 3/25/2017 30

31 Micro800 family PLC overview 31 © 2011 FreeWave Technologies, Inc.
3/25/2017 31

32 PLC overview Micro 830/850 Embedded communications port as well as USB programming port Communications port is Modbus RTU Master and ASCII only (no Modbus RTU Slave or DF1) Ladder logic uses function blocks with tags All message instruction programming is done via tags © 2011 FreeWave Technologies, Inc. 3/25/2017 32

33 MicroLogix family PLC overview 33 © 2011 FreeWave Technologies, Inc.
3/25/2017 33

34 PLC overview MicroLogix 1100, 1200, 1400 & 1500
All four have a channel 0 port that is capable of Modbus RTU Master or Slave The MicroLogix 1400 and 1500LRP have two serial ports capable of Modbus RTU Master or Slave When using a channel 0 port Allen-Bradley’s PMO2 cable is required for connectivity All needed communications programming is done in the message instruction The channel 0 port must be configured as a Modbus RTU Master before a message instruction can be correctly configured © 2011 FreeWave Technologies, Inc. 3/25/2017 34

35 SLC500 family PLC overview 35 © 2011 FreeWave Technologies, Inc.
3/25/2017 35

36 PLC overview SLC5/03,4 & 5 Firmware 10 or later needed for Modbus RTU functionality In SLC5/03 & 4 the firmware is upgraded by replacing a processor chip In SLC5/05 the firmware is upgraded via ControlFlash software There is no Modbus RTU Slave functionality The channel 0 port must be configured as a Modbus RTU Master before a message instruction can be correctly configured © 2011 FreeWave Technologies, Inc. 3/25/2017 36

37 CompactLogix family PLC overview 37 © 2011 FreeWave Technologies, Inc.
3/25/2017 37

38 Application examples

39 CompactLogix with 1769-SM2 module
PLC overview CompactLogix with 1769-SM2 module Provides three serial ports All three ports can be configured as a Modbus RTU Master No Modbus RTU Slave All three ports are RS-485 only Message instructions are “Generic CIP” type instructions All communication configuration parameters are configured via tags including port settings (baud rate, timing, etc…) © 2011 FreeWave Technologies, Inc. 3/25/2017 39

40 CompactLogix with MicroLogix 1100/1400
PLC overview CompactLogix with MicroLogix 1100/1400 MicroLogix communications run independently The MicroLogix and CompactLogix don’t have to be co- located (networked via EtherNet/IP) © 2011 FreeWave Technologies, Inc. 3/25/2017 40

41 Micro830 wired I/O expansion
Application examples Micro830 wired I/O expansion © 2011 FreeWave Technologies, Inc. 3/25/2017 41

42 MicroLogix 1500LSP with wireless I/O
Application examples MicroLogix 1500LSP with wireless I/O © 2011 FreeWave Technologies, Inc. 3/25/2017 42

43 SLC5/05 with multi-drop wireless I/O
Application examples SLC5/05 with multi-drop wireless I/O © 2011 FreeWave Technologies, Inc. 3/25/2017 43

44 Application examples CompactLogix w/ 1769-SM2 44
© 2011 FreeWave Technologies, Inc. 3/25/2017 44

45 Questions?

46 Application examples CompactLogix w/ MicroLogix as Modbus RTU Master
© 2011 FreeWave Technologies, Inc. 3/25/2017 46

47 Application examples CompactLogix w/ MicroLogix as Modbus RTU Master
© 2011 FreeWave Technologies, Inc. 3/25/2017 47